I-7530A-MR Modbus RTU to CAN
Converter User’s Manual (Version 1.07, 06/2016) ------------- 73
3. Change RS-232/RS-422/RS-485 setting
This command is used to Change RS-232/RS-422/RS-485 setting. After
successfully setting, the module will response a successful setting message,
and then reboots.
Request command:
Field Name
Size
Value Range
Example
Hexadecimal rule
Node ID
1 byte
0x01~0xF7
0x01
Function Code
1 byte
0x10
0x10
Start Address
2 bytes
0x0100
0x0100
Word Count
2 bytes
0x0005
0x0005
Byte Count
1 byte
0x0A
0x0A
Data-1
2 bytes
0x0003 (Note1)
0x0003
Data-2
2 bytes
0x0002~0x000C
(Note2)
0x000B
(115200 bps)
Data-3
2 bytes
0x0000~0x0003
(Note3)
0x0000 (8)
Data-4
2 bytes
0x0000~0x0001
(Note4)
0x0001 (1)
Data-5
2 bytes
0x0000~0x0002
(Note5)
0x000 (N)
Note1: This value is command field.
Note2: This value is baud rate of RS-232/RS-422/RS-485.
Baud rate
Description
Hexadecimal rule
0x0002
300 bps baud rate of RS-232/RS-422/RS-485.
0x0003
600 bps baud rate of RS-232/RS-422/RS-485.
0x0004
1200 bps baud rate of RS-232/RS-422/RS-485.
0x0005
2400 bps baud rate of RS-232/RS-422/RS-485.
0x0006
4800 bps baud rate of RS-232/RS-422/RS-485.
0x0007
9600 bps baud rate of RS-232/RS-422/RS-485.
0x0008
19200 bps baud rate of RS-232/RS-422/RS-485.
0x0009
38400 bps baud rate of RS-232/RS-422/RS-485.
0x000A
57600 bps baud rate of RS-232/RS-422/RS-485.