I-7530A-MR Modbus RTU to CAN
Converter User’s Manual (Version 1.07, 06/2016) ------------- 104
0x03
It indicates the current Modbus command is
transmitted completely, but the I-7530A-MR
receives a
“Modbus Exception” command.
From Data Byte4 to Data Byte7, they indicate the
“Modbus
Exception
” message. The “Modbus Exception” message includes
Slave Node ID, Exception Function Code, and Exception Code.
When the Identifier code is 0x03, this message is shown in the error
response CAN message. Otherwise, these data value are 0x00.
Modbus Exception
Modbus Exception
Byte4
Byte5
Byte6
Byte7
Slave
Node ID
Exception
Function Code
Exception Code
Reserved
Function Code and Exception Function Code relation
Function
Code (Hex)
Exception Function
Code (Hex)
0x01
0x81
0x02
0x82
0x03
0x83
0x04
0x84
0x05
0x85
0x06
0x86
0x0F
0x8F
0x10
0x90
Modbus Exception Code
About more Modbus exception code description, please refer to
the Modbus protocol specification.
Modbus Slave Response Timeout:
This field is used for setting Modbus command timeout value. When
sending a Modbus command, the I-7530A-MR module will start to wait
for a response command from the Modbus slave device until timeout