I-7530A-MR Modbus RTU to CAN
Converter User’s Manual (Version 1.07, 06/2016) ------------- 43
3.5 Testing the I-7530A-MR module
The following procedure will guide users to learn how to
transmit/receive CAN messages to/from other devices/PCs by using the I-
7530A-MR converter.
1. Set the Init/Normal switch to the Normal position, which is found on the
back of the I-7530A-MR module.
2. Connect the I-7530A-
MR’s CAN port into the CAN network, which must
at least have one CAN device on the network.
3. Supply the 10~30 V
DC
power into the I-7530A-MR module through the
power terminal.
4. The PWR LED on the I-7530A-MR module will be turned on and the
other LEDs will be turned off. That means the I-7530A-MR is working in
the operation mode.
5. Run the UART2CAN Utility software after connecting the PC and the I-
7530A-MR via cable CA-0910. Please refer to the figure 2-14.
6. Select the PC COM port, baud rate and data format, which will be used
to connect with the COM port of the I-7530A-MR.
Figure 3-28: The configuration for the PC COM port.
7. Press the
“Connect” button. Then the UART2CAN Utility will show the
diagnostic window, as the figure below.