I-7530A-MR Modbus RTU to CAN
Converter User’s Manual (Version 1.07, 06/2016) ------------- 66
Table5-2: Modbus address arrangement of
“Normal CAN Message” field.
Protocol Addresses
(Base 0)
PLC Addresses
(Base 1)
Word
Count
Description
Decimal rule
00000 ~ 00008
30001 ~ 30009
9
RX CAN Message #001
00009 ~ 00017
30010 ~ 30018
9
RX CAN Message #002
…
…
…
…
01782 ~ 01790
31783 ~ 31791
9
RX CAN Message #199
01791 ~ 01799
31792 ~ 31800
9
RX CAN Message #200
The format of each received CAN Message is described below:
Word number
Description
1
Bit 15: 0
valid data, 1
invalid data
Bit 6~14: Reserved
Bit 5: CAN Specification, 0
2.0A, 1
2.0B
Bit 4: RTR, 0
No, 1
Yes
Bit 0~3: Data length, value=0~8
2
Most significant two bytes of CAN identifier. (Big-
endian)
3
Least significant two bytes of CAN identifier. (Big-
endian)
4
The data 1 and data 2 of CAN data field.
5
The data 3 and data 4 of CAN data field.
6
The data 5 and data 6 of CAN data field.
7
The data 7 and data 8 of CAN data field.
8
Most significant two bytes of the RX timestamp
message. (Big-endian)
9
Least significant two bytes of the RX timestamp
message. (Big-endian)