I-7530A-MR Modbus RTU to CAN
Converter User’s Manual (Version 1.07, 06/2016) ------------- 64
5.1 Supported Modbus Functions
The Modbus function codes supported by the I-7530A-MR are shown in the
following table.
Table 5-1: Supported Modbus Function Codes
Function Code
Function Name
Description
3 (03 Hex)
Reading Output
Register
Read multiple registers for a sent
CAN messages
4 (04 Hex)
Reading Input
Register
Read multiple input registers for
reading CAN messages
6 (06 Hex)
Write Output
Register
1. Write single registers for
sending a CAN message.
2. This function is implemented
in firmware version v1.11 or
later.
16 (10 Hex)
Preset Multiple
Registers
1. Write multiple registers for
sending a CAN message
2. Configuration Command
(00256~00512)
5.2 Modbus Address
According to the different purposes these register are divided into three
fields,
“Normal CAN Message Field”, “Specific CAN Message Field” and
“Module Status Field”. The diagram of Input Register are shown below
: