I-7530A-MR Modbus RTU to CAN
Converter User’s Manual (Version 1.07, 06/2016) ------------- 72
2. Reset CAN bus
This command is used to reset CAN bus of module. After successfully
setting, the module will response a successful setting message.
Request command:
Field Name
Size
Value Range
Example
Hexadecimal rule
Node ID
1 byte
0x01~0xF7
0x01
Function Code
1 byte
0x10
0x10
Start Address
2 bytes
0x0100
0x0100
Word Count
2 bytes 0x0002
0x0002
Byte Count
1 byte
0x04
0x04
Data-1
2 bytes 0x0002(Note1)
0x0002
Data-2
2 bytes 0x0001(Note2)
0x0001
Note1: This value is command field.
Note2: Except 0001
hex
, other values are useless
Response command:
Field Name
Size
Value Range
Response
Example
Hexadecimal rule
Node ID
1 byte
0x01~0xF7
0x01
Function Code
1 byte
0x10
0x10
Start Address
2 bytes
0x0100
0x0100
Word Count
2 bytes 0x0002
0x0002