ET-7000/PET-7000 AIO Series User Manual, version 1.0.1 beta3 Page: 128
Copyright © 2009 ICP DAS Co., Ltd. All Rights Reserved. E-mail: [email protected]
(4xxxx) AO address
Begin
address
Points
Description
Registers
per Point
Range
Access
Type
59
1
Average times for every
channel
word
0 ~ 40
R/W/E
174
1
Enable/Disable AI channel
word
0 ~ 65535
R/W
198
1
High alarm value for average
value of all AI channel
word
0 ~ 65535 or
-32768 ~ +32767
R/W/E
199
1
Low alarm value for average
value of all AI channel
word
0 ~ 65535 or
-32768 ~ +32767
R/W/E
271
1
Modbus address (Net ID)
word
1 ~ 255
R/W/E
296
8
High alarm value for AI
word
-32768 ~ +32767
R/W/E
328
8
Low alarm value for AI
word
-32768 ~ +32767
R/W/E
427
1
Type code for AI
word
Refer to type code
table
R/W/E
491
1
CJC offset of channel
word
-9999.0 ~ +9999.0
R/W/E
523
1
CJC Offset (for all channel)
word
-9999.0 ~ +9999.0
R/W/E
555
1
CPU reset status
word
1=by power on
2=by 0.8 second WDT
3=by Reset command
R/W
556
1
CPU reset events
word
When CPU is reset by
one of the situations
described in register
555, the event
increases one count
R/W/E
557
1
Set host watch dog timer
word
<5: Disable
5 ~ 65535: Enable
(Unit: second)
R/W/E
558
1
Host watch dog events
word
0 ~ 32767
R/W
559
1
Module name
word
16 ASCII characters
R
563
1
Module nick name
4 word
16 ASCII characters
R/W
589
1
CJC update settings
8 word
0: Stop
1: Start
2: Read once
R/W/E