ET-7000/PET-7000 AIO Series User Manual, version 1.0.1 beta3 Page: 97
Copyright © 2009 ICP DAS Co., Ltd. All Rights Reserved. E-mail: [email protected]
Detailed Modbus Address Table for ET-7005/PET-7005 (D)
(0xxxx) DO address
Begin
address
Point
s
Description
Registers
per Point
Range
Access
Type
0
0~31
(32)
Digital Out
1
0=off
1=on
R/W
32~161
Reserved
162
0~31
(32)
Clear AI Latch High (single)
1
1=clear
W
(Pulse)
194
0~31
(32)
Clear AI Latch Low (single)
1
1=clear
W
(Pulse)
226
1
Recover all I/O default settings
1
1=clear
W
(Pulse)
233
1
Reboot ET-7000
1
1=reboot
W
(Pulse)
250
0~89
(90)
DO mapping address for external
Modbus devices.
1
0=off
1=on
R/W
340~346
7
Reserved
347
1
Enable the average value of the
previous AI values of one channel
for all AI
1
0=disable
1=enable
(Default=0)
R/W/E
348
1
Enable Average of all enabled
channel, High/Low Alarm value of
all AI average value and Average
latched values for all AI channels.
1
0=disable
1=enable
(Default=0)
R/W/E
349
1
Save Module Nick Name to
EEPROM
1
1=write
W/E
(Pulse)
350~430
Reserved
431
1
Write DO Power on value to
EEPROM
1
1=write
W
(Pulse)
432
1
Write DO Safe value to EEPROM
1
1=write
W
(Pulse)
435
0~79
(80)
Power on value for DO
1
0=disable
1=enable
(Default=0)
R/W/E
515
0~79 Safe value for DO
1
0=off
R/W/E