ET-7000/PET-7000 AIO Series User Manual, version 1.0.1 beta3 Page: 127
Copyright © 2009 ICP DAS Co., Ltd. All Rights Reserved. E-mail: [email protected]
(3xxxx) AI address
Begin
address
Points
Description
Registers
per Point
Range
Access
Type
0
8
Analog Input
word
-32768 ~ +32767
R
143
1
CJC data
word
-32768 ~ +32767
R
144
8
Average value of one channel
word
0 ~ 65535 or
-32768 ~ +32767
R
176
1
Average value of all enabled AI
channel
word
0 ~ 65535 or
-32768 ~ +32767
R
177
1
Average value of all maximum
latched AI value
word
0 ~ 65535 or
-32768 ~ +32767
R
178
1
Average value of all minimum
latched AI value
word
0 ~ 65535 or
-32768 ~ +32767
R
236
8
Analog Latched value (High)
word
0 ~ 65535 or
-32768 ~ +32767
R
268
8
Analog Latched value (Low)
word
0 ~ 65535 or
-32768 ~ +32767
R
310
1
DO (channel number)
word
4
R
320
1
AI (channel number)
word
8
R
350
1
OS image version
word
123 means
version = 1.2.3
R
351
1
Total firmware version
word
R
352
1
CPU lib version
word
123 means
version = 1.2.3
R
353
1
I/O firmware version
word
123 means
version = 1.2.3
R
354
1
MFW lib version
word
123 means
version = 1.2.3
R
355
1
TCP/IP lib version
word
123 means
version = 1.2.3
R
356
1
Modbus lib version
word
123 means
version = 1.2.3
R
357
1
Web lib version
word
123 means
version = 1.2.3
R
360
1
Pair connection
word
0=Normal
1=Timeout
2=Disconnected
R