ET-7000/PET-7000 AIO Series User Manual, version 1.0.1 beta3 Page: 106
Copyright © 2009 ICP DAS Co., Ltd. All Rights Reserved. E-mail: [email protected]
(3xxxx) AI address
Begin
address
Points
Description
Registers
per Point
Range
Access
Type
0
7
Analog Input
word
-32768 ~
+32767
R
(4xxxx) AO address
Begin
address
Points
Description
Registers
per Point
Range
Access
Type
110
7
Temperature offset
word
-128 ~ 127
R/W/E
271
1
Modbus NetID
word
1 ~ 255
R/W
142
7
Resistance offset
word
0 ~ 255
R/W/E
427
7
Type code for AI
word
20 ~ 83 (hex)
R/W/E
Note:
Unit of temperature offset is 0.1 °C, valid range: -128 ~ 127
Unit of resistance offset is 0.1 ohm, valid range: 0 ~ 255