ET-7000/PET-7000 AIO Series User Manual, version 1.0.1 beta3 Page: 102
Copyright © 2009 ICP DAS Co., Ltd. All Rights Reserved. E-mail: [email protected]
(4xxxx) AO address
Begin
address
Points
Description
Registers
per Point
Range
Access
Type
0~58
Reserved
59
1
Average times for every channel
word
0 ~ 40
R/W/E
60
0~49
(50)
AO mapping address for external
Modbus devices
word
0x0000 ~ 0xffff
R/W/E
110~141
0~31
(32)
Temperature offset of channel
word
R/W/E
142~173
0~31
(32)
Resistance offset of channel
word
R/W/E
174
1
Enable/Disable AI channel
word
0 ~ 65535
R/W
175~197
Reserved
198
1
High alarm value for average value
of all AI channel
word
0 ~ 65535 or
-32768 ~ +32767
R/W/E
199
1
Low alarm value for average value
of all AI channel
word
0 ~ 65535 or
-32768 ~ +32767
R/W/E
200~270
Reserved
271
1
Modbus address (Net ID)
word
1 ~ 255
R/W/E
272~295
Reserved
296
0~31
(32)
High alarm value for AI
word
-32768 ~ +32767
(Default=32767)
R/W/E
328
0~31
(32)
Low alarm value for AI
word
-32768 ~ +32767
(Default=-32768)
R/W/E
360~426
Reserved
427
1
Type code for AI
word
Refer to type
code table
R/W/E
428~554
Reserved
555
1
CPU reset status
word
1=by power on
2=by 0.8 second
WDT
3=by Reset
command
R/W
556
1
CPU reset events
word
When CPU is
reset by one of
R/W/E