![background image](http://html1.mh-extra.com/html/icp-das-usa/et-7000-pet-7000-series/et-7000-pet-7000-series_user-manual_3614829115.webp)
ET-7000/PET-7000 AIO Series User Manual, version 1.0.1 beta3 Page: 115
Copyright © 2009 ICP DAS Co., Ltd. All Rights Reserved. E-mail: [email protected]
(4xxxx) AO address
Begin
address
Points
Description
Registers
per Point
Range
Access
Type
59
1
Average times for every channel
word
0 ~ 40
R/W/E
174
1
Enable/Disable AI channel
word
0 ~ 65535
R/W
198
1
High alarm value for average
value of all AI channel
word
0 ~ 65535 or
-32768 ~ +32767
R/W/E
199
1
Low alarm value for average
value of all AI channel
word
0 ~ 65535 or
-32768 ~ +32767
R/W/E
296
8
High alarm value for AI
word
-32768 ~ +32767
(Default=32767)
R/W/E
296
8
Low alarm value for AI
word
-32768 ~ +32767
(Default=-32768)
R/W/E
427
1
Type code for AI
word
Refer to type
code table
R/W/E