ET-7000/PET-7000 AIO Series User Manual, version 1.0.1 beta3 Page: 124
Copyright © 2009 ICP DAS Co., Ltd. All Rights Reserved. E-mail: [email protected]
Detailed Modbus Address Table for ET-7019
(0xxxx) DO address
Begin
address
Points
Description
Registers
per Point
Range
Access
Type
0
4
Digital Out
1
0=off
1=on
R/W
162
8
Clear AI Latch High
1
1=clear
W
(Pulse)
194
8
Clear AI Latch Low
1
1=clear
W
(Pulse)
226
1
Recover all I/O default settings
1
1=clear
W
(Pulse)
233
1
Reboot ET-7000
1
1=clear
W
(Pulse)
347
1
Enable the average value of the
previous AI values of one channel
for all AI
1
0=disable
1=enable
(Default=0)
R/W/E
348
1
Enable average of all enable
channel, High/Low Alarm value of
all AI average value and Average
latched values for all AI channels
1
0=disable
1=enable
(Default=0)
R/W/E
431
1
Write DO Power on value to
EEPROM
1
1=write
W
(Pulse)
432
1
Write DO Safe value to EEPROM
1
1=write
W
(Pulse)
435
4
Power on value for DO
1
0=off
1=on
(Default=0)
R/W/E
515
4
Safe value for DO
1
0=off
1=on
(Default=0)
R/W/E
595
8
Enable/Disable AI channel
1
0=disable
1=enable
(Default=1)
R/W/E
627
1
Enable/Disable CJC
1
0=normal
(16 bit)
R/W/E