Adjustment and control system
37
No.
Parameter Description
Reading level
Writing level
Visibility Conditions
18.06 Pump 1 absorbed power (W)
USER
-
Only if the Pump 1 ModBus is enabled
18.07 Pump 1 total absorbed energy (kWh)
USER
-
Only if the Pump 1 ModBus is enabled
19.06 Pump 2 absorbed power (W)
USER
-
Only if the Pump 2 ModBus is enabled
19.07 Pump 2 total absorbed energy (kWh)
USER
-
Only if the Pump 2 ModBus is enabled
20.01 Steam total flow rate (kg)
USER
-
Only if the relevant ModBus meter is
enabled
20.02 Steam instant flow rate (kg/h)
USER
-
Only if the relevant ModBus meter is
enabled
20.04 Steam temperature (°C)
USER
-
Only if the relevant ModBus meter is
enabled
11.27 Value O
2
in %
USER
-
If the oxygen sensor is enabled
11.28 Value CO
2
in %
USER
-
If the oxygen sensor is enabled
GENERATOR PARAMETER MENU
ACCESS PATH
:
→
PRESSURE SETTINGS
No.
Description
Range
unit of
measurement
Default
Reading
Writing
Visibility
02.01
Soft start.
With the control enabled, burner stays at the minimum power
until reaching the “Soft start threshold”.
Enabled /
Disabled
-
Enabled
USER
USER
ALWAYS
02.02
Soft start threshold.
With the soft start enabled, burner stays at the value set in
parameter 2.22 until reaching this threshold.
0.0 – 12.0
Bar
1,0
USER
USER
ALWAYS
02.22
Soft start power
USER
USER
ALWAYS
02.10
Pressure setpoint.
0.1 – 20.0
Bar
0,0
USER
USER
ALWAYS
02.21
Boiler maximum pressure
Maximum limit at which the OFF can be set.
0.0 – 20.0
Bar
12
USER
OEM
ALWAYS
02.23
Turning off differential.
When the measured pressure reaches the setpoint (parameter
02.10) plus this differential, the burner stops
0.1 – 2.0
Bar
0,5
USER
USER
ALWAYS
02.24
Ignition differential.
When the measured pressure reaches the setpoint (parameter
02.10) less this differential, the burner starts again
0.1 – 2.0
Bar
0,5
USER
USER
ALWAYS
ACCESS PATH
:
→
BURNER SETTINGS
No.
Parameter Description
Range
unit of
measurement
Default
Reading
Writing
Visibility
02.03
Type of burner
02.11
Low modulation range.
Pressure range, above the setpoint, inside which the PID system
is active.
0.1 – 10.0
Bar
2,0
SERVICE
SERVICE
ALWAYS
02.12
High modulation range
Pressure range, under the setpoint, inside which the PID system
is active.
0.1 – 10.0
Bar
1,0
SERVICE
SERVICE
ALWAYS
02.13
Stabilisation time.
Time, since burner start (flame presence), during which power is
kept at the minimum value.
0 – 300
s
90
SERVICE
SERVICE
ALWAYS
02.14
Sampling period.
Time interval taken as a reference by burner PID system.
1 – 60
s
20
SERVICE
SERVICE
ALWAYS
02.15
Sampling time adaptation.
Within the range between setpoint and modulation field
limits, the frequency progressively increases until reaching the
percentage indicated by this parameter.
0 – 1000
%
0
SERVICE
SERVICE
ALWAYS
02.16
Burner PID proportional factor.
Weight of the proportional factor
taken as a reference by the burner PID system. The proportional
length is used to accelerate / decelerate the approaching speed
to the setpoint. The definition of the correct speed stabilises the
system since it prevents a too quick approach to the setpoint
that could result in overshoots due to inertia. The proportional
length also increases control responsiveness.
0 – 20
-
10
SERVICE
SERVICE
ALWAYS
02.17
Burner PID integral factor
SERVICE
SERVICE
Always
02.18
Burner PID derivative factor
SERVICE
SERVICE
Always
02.19
Time from minimum power to maximum power