Adjustment and control system
36
ACCESS PATH
:
→
DATA AND METERS
→
→
DIAGRAMS
No.
Parameter Description
Reading level
Writing level
Visibility Conditions
02.31 Boiler pressure setpoint in Bar
USER
-
Always
11.03 Boiler pressure in Bar
USER
-
Always
11.15 Steam flow pressure in Bar
USER
-
If the steam control valve is enabled
13.23 Steam flow valve modulation percentage
USER
-
If the valve is enabled
11.17 Cascade pressure value in Bar
USER
-
If the cascade is enabled
11.01 Ambient temperature in °C
USER
-
If the sensor is enabled
11.13 Flue gas temperature in °C
USER
-
Always
11.27 Value O
2
in %
USER
-
If the oxygen sensor is enabled
11.28 Value CO
2
in %
USER
-
If the oxygen sensor is enabled
11.09
TDS
value in µS
USER
-
If the
TDS
sensor is enabled
11.04 Burner fed
USER
-
Always
11.05 Burner flame presence
USER
-
Always
13.01 Burner modulation percentage
USER
-
Always
14.01 Number of burner starts
USER
-
Always
14.02 Burner hours of operation
USER
-
Always
14.05 Burner power output estimation
USER
-
Always
14.06
Burner total energy output estimation
It is the integral of power by time, calculated with the same
PID sampling interval.
USER
-
Always
14.07
Combustion efficiency estimation
Efficiency = 100-(0.86+36.6/CO
2
)*(TF-TA)/100.
Efficiency is not calculated if the flue gas probe is not present.
If the ambient probe is not present, an air temperature of 25 °C
is estimated
USER
-
Always
14.08 Number of openings of the drain valve
USER
-
Only if the valve is enabled
14.09 Opening hours of the drain valve
USER
-
Only if the valve is enabled
14.10 Number of openings of the
TDS
valve
USER
-
Only if the valve is enabled
14.11 Opening hours of the
TDS
valve
USER
-
Only if the valve is enabled
04.05 Level setpoint
SERVICE
SERVICE
If the level probe is enabled
11.07 Level value in %
USER
-
Always
14.12 Number of starts of pump 1
USER
-
Always
14.13 Pump 1 hours of operation
USER
-
Always
13.02 Pump 1 modulation percentage
USER
-
Always
14.14 Number of starts of pump 2
USER
-
Only if the second pump is enabled
14.15 Pump 2 hours of operation
USER
-
Only if the second pump is enabled
13.03 Pump 2 modulation percentage
USER
-
Only with level sensor and pump 2
enabled
13.04 Feed valve modulation percentage
USER
-
Only with feed valve enabled
11.19 Pump flow pressure in Bar
USER
-
If the flow pressure sensor is enabled
14.18 Number of electrical power F1 rising edges
SERVICE
-
Always
14.19 Electrical power hours F1
SERVICE
-
Always
14.20 Number of electrical power F3 rising edges
SERVICE
-
Always
14.21 Electrical power hours F3
SERVICE
-
Always
14.22 Make-up water total flow rate
USER
-
Only if the meter is enabled (PT9 E2 inlet)
14.23 Make-up water instant flow rate
USER
-
Only if the meter is enabled (PT9 E2 inlet)
14.24 Gas total flow rate
USER
-
Only if the meter is enabled (PT1 E1 or
PT10E2 inlet)
14.25 Gas instant flow rate
USER
-
Only if the meter is enabled (PT1 E1 or
PT10E2 inlet)
14.26 ECX1 water total flow rate (delivery)
USER
-
Only if the ModBus meter or the PT3E2
inlet is enabled
14.27 ECX1 water instant flow rate (delivery)
USER
-
Only if the ModBus meter or the PT3E2
inlet is enabled
14.28 ECX1 energy
USER
-
Only if the ModBus meter or the PT3E2 -
PT1E2 - PT2E2 inlets are enabled
14.29 ECX1 power
USER
-
Only if the ModBus meter or the PT3E2 -
PT1E2 - PT2E2 inlets are enabled
14.32 ECX2 energy
USER
-
Only if the ModBus meter or the PT6E2 -
PT4E2 - PT5E2 inlets are enabled
14.33 ECX2 power
USER
-
Only if the ModBus meter or the PT6E2 -
PT4E2 - PT5E2 inlets are enabled
17.01 Total absorbed electrical energy (kWh)
USER
-
Only if the relevant ModBus meter is
enabled
17.03 Total absorbed power (W)
USER
-
Only if the relevant ModBus meter is
enabled
Содержание ECOVAPOR Series
Страница 78: ...Appendixes for Technical Personnel 78...
Страница 79: ...Appendixes for Technical Personnel 79...