Appendixes for Technical Personnel
77
(Loc. "c")
Err.Code
(Loc. "d") Diagn. Code
Cause
Possible remedy
5 (-5)
TÜV test time-out
No flame loss after the disabling of fuel valves:
-Check the extraneous light
-Check the wiring to exclude short circuits
-Check valve tightness
165
#
Internal error
166
0
Watchdog internal error-reset
167
#
Manual lock
The appliance has been manually shut-off (no error).
1
Manual shut-off through contact
2
Manual shut-off through AZL2
3
Manual shut-off through PC software
8
Manual shut-off through AZL2 time-
out / communication interruption
During the setting of a curve with AZL2, menu use time-out
(setting with parameter 127) or communication interrupted
between LMV37.4 and AZL2.
9
Manual shut-off through the
interruption of the PC software
communication
During the setting of a curve with ACS410, the communication
between LMV37.4 and ACS410 has been interrupted for more
than 30 seconds.
33
Manual shut-off after the unlock
attempt of the PC software
The PC software has attempted to unlock a system without
errors.
168
#
Error management internal error
Unlock, if it occurs again replace the appliance.
169
#
Error management internal error
Unlock, if it occurs again replace the appliance.
170
#
Error management internal error
Unlock, if it occurs again replace the appliance.
171
#
Error management internal error
Unlock, if it occurs again replace the appliance.
200 OFF
#
System without errors
No error.
201 OFF
Upr
#
Start lock
Start lock in an unparametrised. In case of turning off during
the first curve setting, the original cause of the error must be
detected through the error log, item 702.
Bit 0
Significance 1
No selected operating mode
Bit 1
Significance 2-3
No defined fuel gas train
Bit 2
Significance 4-7
No defined curve
Bit 3
Significance 8-15
Standard rpm not defined
Bit 4
Significance 16-31
The backup / restore could not be run
202
#
Internal error for operating mode
setting
Re-define the operating mode (parameter 201).
203
#
Internal error
Re-define the operating mode (parameter 201). Unlock, if it
occurs again replace the appliance.
204
Phase number
Programme stop
Active programme stop (no error).
205
#
Internal error
Unlock, if it occurs again replace the appliance.
#
206
0
Device combination not allowed
(appliance AZL2)
207
#
Appliance version compatibility –
AZL2
0
The version of the appliance is too old
1
AZL2 version too old
208
#
Internal error
Unlock, if it occurs again replace the appliance.
209
#
Internal error
Unlock, if it occurs again replace the appliance.
210
0
The selected operating mode is not
enabled for the appliance
Select an operating mode enabled for the appliance.
240
#
Internal error
Unlock, if it occurs again replace the appliance.
245
#
Internal error
Unlock, if it occurs again replace the appliance.
250
#
Internal error
Unlock, if it occurs again replace the appliance.