Appendixes for Technical Personnel
75
(Loc. "c")
Err.Code
(Loc. "d") Diagn. Code
Cause
Possible remedy
99
#
Relay operation internal error
Unlock, if it occurs again replace the appliance.
3
Relay operation internal error
Unlock, if it occurs again replace the appliance.
Software version V03.10: with error C:99 D:3 during a
standardisation of the frequency converter, temporarily disable
the Alarm function in case of start lock (parameter 210 = 0, using
an enabling contact) or interrupt the ON controller signal.
100
#
Relay operation internal error
Unlock, if it occurs again replace the appliance.
105
#
Contact inquiry internal error
0 = min. pressure switch
1 = max / POC pressure switch
2 = pressure switch sealing check
3 = air pressure
4 = feed controller OFF
5 = feed controller ON / OFF
6 = feed controller CLOSED
7 = safety circuit / burner flange
8 = safety valve
9 = fuel valve 1 ignition transformer
10 = 1 ignition transformer
11 = fuel valve 2
12 = fuel valve 3
13 = unlock
"Stuck At" error
It can be caused by a capacity load or by direct current supply
on the mains voltage inputs. The inlet where the problem
occurred is indicated in the diagnosis code.
106
#
Contact inquiry internal error
Unlock, if it occurs again replace the appliance.
107
#
Contact inquiry internal error
Unlock, if it occurs again replace the appliance.
108
#
Contact inquiry internal error
Unlock, if it occurs again replace the appliance.
110
#
Voltage switch test internal error
Unlock, if it occurs again replace the appliance.
#
Mains voltage too low.
111
#
Mains undervoltage
Diagnosis code calculation factor; electrical power value (AC 230
V: 1.683; AC 120 V: 0.843).
112
0
Mains voltage restore
Error code to provoke a reset to resume mains voltage (no error).
113
#
Mains voltage monitoring internal
error
Unlock, if it occurs again replace the appliance.
115
#
System meter internal error
116
0
Designed liftetime exceeded (250,000
cycles)
The warning threshold has been reached. The appliance must
be replaced.
117
0
Lifetime exceeded
Operation no longer reliable
The turning off threshold has been reached.
120
0
Fuel meter input interruption
limitation
Too many interference pulses at fuel meter inlet. Improve the
EMF measures.
121
#
EEPROM access internal error
Unlock, repeat / check the last parametrisation, restore the
dataset, if it occurs again replace the appliance.
122
#
EEPROM access internal error
Unlock, repeat / check the last parametrisation, restore the
dataset, if it occurs again replace the appliance
123
#
EEPROM access internal error
Unlock, repeat / check the last parametrisation, restore the
dataset, if it occurs again replace the appliance.
124
#
EEPROM access internal error
Unlock, repeat / check the last parametrisation, restore the
dataset, if it occurs again replace the appliance.
125
#
EEPROM reading access internal error
Unlock, repeat / check the last parametrisation, if it occurs again
replace the appliance.
126
#
EEPROM writing access internal error
Unlock, repeat / check the last parametrisation, if it occurs again
replace the appliance.
127
#
EEPROM access internal error
Unlock, repeat / check the last parametrisation, restore the
dataset, if it occurs again replace the appliance.
128
0
EEPROM access internal error –
Initialisation synchronisation
Unlock, if it occurs again replace the appliance.
129
#
EEPROM access internal error – Task
synchronisation
Unlock, repeat / check the last parametrisation, if it occurs again
replace the appliance.
130
#
EEPROM access internal error – Time-
out
Unlock, repeat / check the last parametrisation, if it occurs again
replace the appliance.
240
#
Internal error
Unlock, if it occurs again replace the appliance.
245
#
Internal error
Unlock, if it occurs again replace the appliance.
250
#
Internal error
Unlock, if it occurs again replace the appliance.