Adjustment and control system
42
Bit Parameters
Read: Read Output Status (01) or Read Input Status (02).
ModBus PARAMETER
REF.
Parameter Description
0
1
Inlets
000001 or 100001
11.04 Burner supply presence
NO
YES
000002 or 100002
11.05 Flame presence
NO
YES
Outputs
000011 or 100011
13.05 Burner enabling from PLC
NO
YES
000014 or 100014
13.09 Blowdown valve opening control
NO
YES
000015 or 100015
13.10 Pump 1 ignition digital control
NO
YES
000016 or 100016
13.11 Pump 2 ignition digital control
NO
YES
000017 or 100017
13.12 Opening control of the
TDS
valve
NO
YES
000018 or 100018
13.13 Acoustic signal active
NO
YES
BUS SIGNALS
000021 or 100021
16.10 Fan ON
NO
YES
000022 or 100022
18.09 Pump 1 enabling
NO
YES
000023 or 100023
19.09 Pump 2 enabling
NO
YES
Alarms
000031 or 100031
12.01 General alarm
OK
ALARM
000032 or 100032
12.02 Bus communication alarm
OK
ALARM
000033 or 100033
12.03 Minimum level 1
OK
ALARM
000034 or 100034
12.04 Minimum level 2
OK
ALARM
000035 or 100035
12.05 Maximum level
OK
ALARM
000037 or 100037
12.07 Burner shut-off
OK
ALARM
000038 or 100038
12.08 Wrong power supply
OK
ALARM
000039 or 100039
12.09 Safety circuit fault
OK
ALARM
000040 or 100040
12.10 Pump 1 failure
OK
ALARM
000041 or 100041
12.11 Pump 2 failure
OK
ALARM
000042 or 100042
12.12 Deaerator alarm
OK
ALARM
000043 or 100043
12.13 Emergency button pressed
OK
ALARM
000044 or 100044
12.14 Level sensor failure
OK
ALARM
000045 or 100045
12.15 Ambient temperature probe failure
OK
ALARM
000046 or 100046
12.16 Burner modulation feedback failure
OK
ALARM
000047 or 100047
12.17 Level sensor failure
OK
ALARM
000048 or 100048
12.18
TDS
sensor failure
OK
ALARM
000049 or 100049
12.19
TDS
high value
OK
ALARM
000050 or 100050
12.20 Flue gas temperature probe failure
OK
ALARM
000051 or 100051
12.21 High flue gas temperature 1
OK
ALARM
000052 or 100052
12.22 High flue gas temperature 2 + burner stop
OK
ALARM
000053 or 100053
12.23 Fan inverter fault
OK
ALARM
000054 or 100054
12.24 Fan inverter high temperature
OK
ALARM
000055 or 100055
12.25 Wrong fan supply
OK
ALARM
000056 or 100056
12.26 Fan excessive absorption
OK
ALARM