Tighten the fixing screw with a maximum torque of 0,5Nm.
In case it is necessary to dismount the system, repeat the steps in opposite order.
For the electrical connection, see the wiring diagrams in the dedicated chapter and the requirements reported in the technical
characteristics table.
27
A20 ALARM RESET PROCEDURE
From the main page press one time the
▲
button to access at the
page “SERVICE”:
Press and hold the ◄ button until the hours of maintenance will
not return to be 9000.
28
VENTILATION SYSTEM TEST
From the main page, press three times the
▼
button to access at
the page TEMPERATURE:
From the page TEMPERATURE press and hold the ◄
button until
the indication
“FAN STATUS” changes from “OFF” to “ON”.
After 30 seconds the ventilation system will stop.
29