P15.04
Remote access password
OFF
OFF/1-9999
P15.01
– If set to OFF, password management is disabled and anyone has access to the settings and commands menu.
P15.02
– With P15.01 enabled, this is the value to specify for activating user level access. See Password access chapter.
P15.03
– As for P15.02, with reference to Advanced level access.
P15.04
– If set to a numeric value, this becomes the code to specify via serial communication before sending commands from a remote control.
(*) Available value only if the controller is not installed on the ICAR cabinet
M16 –COMMUNICATION (COMn,n=1…2)
Psw (M15)
UoM
Default
Range
P16.n.01
Node serial address
Usr
01
01-255
P16.n.02
Serial speed
Usr
bps
9600
1200
2400
4800
9600
19200
38400
57600
115200
P16.n.03
Data format
Usr
8 bit – n
8 bit, no parity
8 bit, odd
8bit, even
7 bit, odd
7 bit, even
P16.n.04
Stop bits
Usr
1
1-2
P16.n.05
Protocol
Usr
(various)
Modbus RTU
Modbus ASCII
Modbus TCP
P16.n.06
IP address
Usr
192.168.1.1
000.000.000.000 –
255.255.255.255
P16.n.07
Subnet mask
Usr
255.255.255.0
000.000.000.000 –
255.255.255.255
P16.n.08
IP port
Usr
1001
0-9999
P16.n.09
Channel function
Usr
Slave
Slave
Gateway
Mirror
P16.n.10
Client/server
Usr
Server
Client
Server
P16.n.11
Remote IP address
Usr
000.000.000.000
000.000.000.000-
255.255.255.255
P16.n.12
Remote IP port
Usr
1001
0-9999
P16.n.13
IP gateway address
Usr
000.000.000.000
000.000.000.000-
255.255.255.255
Note: this menu is divided into 2 sections for communication channels COM1..2.
The front IR communication port has fixed communication parameters, so no setup menu is required.
P16.n.01
– Serial (node) address of the communication protocol.
P16.n.02
– Communication port transmission speed.
P16.n.03
– Data format. 7 bit settings can only be used for ASCII protocol.
P16.n.04
– Stop bit number.
P16.n.05
– Select communication protocol.
P16.n.06, P16.n.07, P16.n.08
– TCP-IP coordinates for applications with Ethernet interface. Not used with other types of communication modules.
P16.n.09
- Role of the communication channel.
Slave
=Slave Modbus.
Gateway
=Bridge between Ethernet and serial ports.
Mirror
=Remote panel mirror
(reserved/function not operative yet)
P16.n.10
- Enabling TCP-IP connection.
Server
=Awaits connection from a remote client.
Client
=Establishes a connection to the remote server.
P16.n.11...P16.n.13
- Coordinates for the connection to remote server when P16.n.10 is set to Client.
M17 – BASIC PROTECTIONS
Psw (M15)
UoM
Default
Range
P17.01
Temperature unit of measure
Adv
°C
°C
°F
P17.02
Panel interior temperature measurement
source
Adv
Internal sensor
Internal sensor
AINx
NTCx
P17.03
Channel nr. (x)
Adv
1
1-99
P17.04
Fan start temperature
Adv
°C/°F
25
0-212
P17.05
Fan stop temperature
Adv
°C/°F
20
0-212
P17.06
Panel interior temperature alarm threshold
Adv
°C/°F
55
0-212
P17.07
Capacitor current overload
Adv
ON
OFF
ON
P17.08
Capacitor current overload threshold
Adv
%
50
OFF / 0 – 150
P17.09
Immediate step disconnection threshold
Adv
%
83
OFF / 0 – 200
P17.10
Current overload alarm reset time
Adv
min
15
1 – 30
P17.11
Step trimming
Adv
ON
OFF / ON
P17.13
Maximum voltage threshold
Adv
%
110
OFF / 90...150
P17.14
Minimum voltage threshold
Adv
%
90
OFF / 60..110