ICAR PQS
rev8 may18
37 / 86
18
PARAMETER SETTING (SETUP) WITH PC
You can use the
PFC Remote Monitoring
software to transfer (previously programmed) set-up parameters from the power factor
really to the hard drive of the PC and vice versa. The parameter may be partially transferred from the PC to the power factor
controller, transferring only the parameters of the specified menus.
The PC can be used to set parameters and also the following:
o
Info page where you can enter application information, characteristics, data, etc.
19
PARAMETER SETTING (SETUP) FROM FRONT PANEL
To open the parameters programming menu (setup):
turn the power factor controller in MAN mode and disconnect all the steps
in normal measurements view, press
to call up the main menu
select the icon
. If it is disabled (displayed in grey) you must enter the password (see chapter 7. Password access).
press
to open the setup menu.
The table shown in the illustration is displayed, with the settings sub-menus of all the parameters on the basis of their function.
Select the required menu with keys ▲▼and confirm with
.
Press ◄ to return to the values view.
Settings: menu selection
The following table lists the available submenus:
Cod
MENU
DESCRIPTION
M01
UTILITY
Language, brightness, display pages etc.
M02
GENERAL
Panel/plant data
M03
STEP
Capacitor step configuration
M04
MASTER OUTPUTS
Programmable outputs of master device
M05
MASTER / SLAVE
Device role (master or slave)
M06
SLAVE 01 OUTPUTS
Programmable outputs of slave device 01
…
…
M13
SLAVE 08 OUTPUTS
Programmable outputs of slave device 08
M14
PROG. INPUTS
Programmable digital inputs
M15
PASSWORD
Password access management
M16
COMMUNICATION
Communication channels parameters
M17
BASE PROTECTIONS
Base protections of the panel
M18
HARMONIC PROT.
Harmonic protections (MCP5 module)
M19
MISCELLANEOUS
Various settings
M20
LIMIT THRESHOLDS
Limit thresholds on measurements
M21
COUNTERS
Generic programmable counters
M22
ANALOG INPUTS
Programmable analog inputs
M23
ANALOG OUTPUTS
Programmable analog outputs
M24
ENERGY PULSES
Pulses for energy meters increment
M25
USER ALARMS
Programmable user alarms
M26
ALARM PROPERTIES
Action caused by alarms
Select the sub-menu and press
to show the parameters. Each parameter is shown with code, description and actual
setting value.
Set-up: parameter selection
To modify the setting of one parameter, select it and then press
.
If the Advanced level access code has not been entered, it
will not be possible to enter editing page and an access denied message will be shown. If instead the access rights are confirmed,
then the editing screen will be shown.
Parameter
code
Parameter
description
Present setting
value
Selected
parameter