ICAR PQS
rev8 may18
47 / 86
21.2
Alarm properties
Various properties can be assigned to each alarm, including user alarms (
User Alarms
, UAx):
Alarm enabled
- General enabling of the alarm. If the alarm isn't enabled, it's as if it doesn't exist.
Retained alarm
- Remains in the memory even if the cause of the alarm has been eliminated.
Operating mode
– Operating modes where the alarm is enabled.
Global alarm 1 -2 -3
- Activates the output assigned to this function.
Step disconnection mode
– Defines whether and how the capacitor steps must be disconnected when the alarm is present.
OFF = no disconnection, SLOW = gradual disconnection, FAST = Immediate disconnection.
Slave disconnection mode
– Defines, for Master-Slave applications, if when this alarm arises, the disconnection is
extended to all the step of the system (GENERAL) or only to the output of the interested panel (LOCAL).
Inhibition
- The alarm can be temporarily disabled by activating an input that can be programmed with the Inhibit function.
Modem call
– The alarm will be signalled remotely by sending a modem call under the conditions and modality defined in
modem parameters.
No LCD
- The alarm is managed normally, but not shown on the display.
Delay time – Time delay in minutes or seconds before the alarm is generated.
21.3
Alarm properties table
C
O
D
DEFAULT ALARM PROPERTIES
en
ab
le
re
te
n
ti
ve
o
n
ly
in
a
u
t
m
o
d
e
g
lo
b
al
a
lr
am
1
g
lo
b
al
a
la
rm
2
g
lo
b
al
a
la
rm
3
st
ed
d
is
co
n
n
ec
ti
o
n
m
o
d
e
sl
av
e
d
is
co
n
n
ec
ti
o
n
m
o
d
e
in
h
ib
it
io
n
m
o
d
em
n
o
lc
d
d
el
ay
t
im
e
m
in
se
c
A01
ON
OFF
A/M
GLB1
OFF
OFF
OFF
GEN
OFF
OFF
OFF
15
●
A02
OFF
OFF
AUT
GLB1
OFF
OFF
OFF
GEN
OFF
OFF
OFF
5
●
A03
ON
OFF
AUT
GLB1
OFF
OFF
IMM
GEN
OFF
OFF
OFF
30
●
A04
ON
OFF
A/M
GLB1
OFF
OFF
OFF
GEN
OFF
OFF
OFF
60
●
A05
ON
OFF
AUT
GLB1
OFF
OFF
IMM
GEN
OFF
OFF
OFF
60
●
A06
ON
OFF
AUT
GLB1
OFF
OFF
IMM
GEN
OFF
OFF
OFF
15
●
A07
ON
RIT
AUT
GLB1
OFF
OFF
IMM
LOC
OFF
OFF
OFF
60
●
A08
ON
OFF
AUT
GLB1
OFF
OFF
SLOW
GEN
OFF
OFF
OFF
3
●
A09
ON
OFF
AUT
GLB1
OFF
OFF
IMM
GEN
OFF
OFF
OFF
OFF
A10
NOT USED
A11
ON
OFF
A/M
GLB1
OFF
OFF
IMM
LOC
OFF
OFF
OFF
3
●
A12
ON
OFF
A/M
GLB1
OFF
OFF
SLOW
LOC
OFF
OFF
OFF
3
●
A13
OFF
OFF
A/M
GLB1
OFF
OFF
IMM
LOC
OFF
OFF
OFF
3
●
A14
OFF
OFF
A/M
GLB1
OFF
OFF
IMM
LOC
OFF
OFF
OFF
3
●
A15
OFF
OFF
A/M
GLB1
OFF
OFF
IMM
LOC
OFF
OFF
OFF
3
●
A16
OFF
OFF
A/M
GLB1
OFF
OFF
IMM
LOC
OFF
OFF
OFF
3
●
A17
OFF
RIT
A/M
GLB1
OFF
OFF
IMM
LOC
OFF
OFF
OFF
60
●
A18
OFF
RIT
AUT
GLB1
OFF
OFF
IMM
LOC
OFF
OFF
OFF
60
●
A19
ON
RIT
AUT
GLB1
OFF
OFF
IMM
GEN
OFF
OFF
OFF
30
●
A20
ON
RIT
A/M
GLB1
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
A21
ON
RIT
A/M
GLB1
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
A22
ON
RIT
A/M
GLB1
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
A23
OFF
OFF
A/M
GLB1
OFF
OFF
OFF
GEN
OFF MDM OFF
OFF
UAx
OFF
OFF
A/M
OFF
OFF
OFF
OFF
GEN
OFF
OFF
OFF
OFF
22
INPUT FUNCTION TABLE
The following table shows all the functions that can be attributed to the INPn programmable digital inputs.
Each input can be set for an reverse function (NA - NC), delayed energizing or de-energizing at independently set times.
Some functions require another numeric parameter, defined in the index (x) specified by parameter P14.n.02.
See menu
M14 Programmable inputs
for more details.
FUNCITON
DESCRIPTION
OFF
Disabled input
Configurable
Free user configurable input INPx. Used for instance to generate a user alarm UA or to count on a CNT counter.
Automatic mode
When active, switches system to AUT mode
Manual mode
When active, switches system to MAN mode
Select cosphi setpoint x
When active, selects the cosphi setpoint x (x=1…3).
Keyboard lock
Locks front keyboard.
Settings lock
Locks access to setup menu and command menu.
Alarm Inhibition
Selectively disables alarms that have
inhibit
property set to ON.