7.
Connect the internal battery connector (circled in Figure 318).
Note:
A small amount of arcing may occur when connecting the batteries. This is normal and does
not damage the unit or present any safety concerns.
8.
Reinstall the front panel.
9.
At the back of the 2145 UPS-1U, connect the SAN Volume Controller power cable to load segment 2
receptacle (
3
in Figure 320 on page 313). If applicable, install the power cable-retention bracket
(shown in Figure 319 on page 313).
Note:
The 2145 UPS-1U is intended to maintain power on a single SAN Volume Controller node
until data can be saved to the local hard disk drive. Only SAN Volume Controller nodes can be
plugged in to the 2145 UPS-1U or else the SAN Volume Controller cluster malfunctions. You must
attach only one SAN Volume Controller to the 2145 UPS-1U, and nothing else.
svc00062
Figure 317. The 2145 UPS-1U internal battery connector with protective tape
svc00061
Figure 318. The 2145 UPS-1U with internal battery connectors in place
312
IBM SAN Volume Controller Hardware Maintenance Guide
Содержание SAN Volume Controller 2145-CG8
Страница 1: ...System Storage SAN Volume Controller Hardware Maintenance Guide Version 6 2 0 GC27 2283 00...
Страница 2: ......
Страница 3: ...System Storage SAN Volume Controller Hardware Maintenance Guide Version 6 2 0 GC27 2283 00...
Страница 14: ...xii IBM SAN Volume Controller Hardware Maintenance Guide...
Страница 24: ...xxii IBM SAN Volume Controller Hardware Maintenance Guide...
Страница 30: ...xxviii IBM SAN Volume Controller Hardware Maintenance Guide...
Страница 54: ...24 IBM SAN Volume Controller Hardware Maintenance Guide...
Страница 362: ...332 IBM SAN Volume Controller Hardware Maintenance Guide...
Страница 364: ...334 IBM SAN Volume Controller Hardware Maintenance Guide...
Страница 371: ......
Страница 372: ...Part Number 31P1584 Printed in USA GC27 2283 00 1P P N 31P1584...