10.
Reconnect the SAN Volume Controller signal cable to the communication port (
2
in Figure 320).
11.
Reconnect the 2145 UPS-1U main power cable, from either the power distribution unit or from the
redundant ac-power switch, into the input connector (
1
in Figure 320).
The 2145 UPS-1U is now in standby mode with the SAN Volume Controller offline. All indicators
that are shown in Figure 320 are off.
12.
To turn on the 2145 UPS-1U, press and hold the on/off button (
2
in Figure 321). On some versions
of the 2145 UPS-1U, you need a pointed device, such as a screwdriver, to press the on/off button.
The 2145 UPS-1U undergoes a self-test, taking approximately five seconds, before the power-on
indicator
1
and the load indicators (
7
and
8
) light up permanently to indicate that the 2145
UPS-1U is supplying power to the SAN Volume Controller. The 2145 UPS-1U begins to charge its
battery while in normal mode.
Note:
If the 2145 UPS-1U battery is not sufficiently charged, the SAN Volume Controller node will
not be able to join the cluster. The node will display
Charging
on its front panel until the 2145
UPS-1U battery has reached sufficient charge, which could take an hour. When the SAN Volume
Controller node rejoins the cluster, it might display
Recovering
on its front panel while the 2145
UPS-1U battery finalizes its charge.
svc00200
Figure 319. The 2145 UPS-1U cable retention bracket connected to the 2145 UPS-1U
1yz09b
1
2
3
Figure 320. 2145 UPS-1U (rear view)
+ -
LOAD 1
LOAD 2
1yyzvm
6
7
8
1
2
3
4
5
Figure 321. 2145 UPS-1U front-panel assembly
Chapter 2. Removing and replacing parts
313
Содержание SAN Volume Controller 2145-CG8
Страница 1: ...System Storage SAN Volume Controller Hardware Maintenance Guide Version 6 2 0 GC27 2283 00...
Страница 2: ......
Страница 3: ...System Storage SAN Volume Controller Hardware Maintenance Guide Version 6 2 0 GC27 2283 00...
Страница 14: ...xii IBM SAN Volume Controller Hardware Maintenance Guide...
Страница 24: ...xxii IBM SAN Volume Controller Hardware Maintenance Guide...
Страница 30: ...xxviii IBM SAN Volume Controller Hardware Maintenance Guide...
Страница 54: ...24 IBM SAN Volume Controller Hardware Maintenance Guide...
Страница 362: ...332 IBM SAN Volume Controller Hardware Maintenance Guide...
Страница 364: ...334 IBM SAN Volume Controller Hardware Maintenance Guide...
Страница 371: ......
Страница 372: ...Part Number 31P1584 Printed in USA GC27 2283 00 1P P N 31P1584...