background image

Figure 145. Installing the service access cover

3. Complete the following steps to place the system node in the operating position.

Note: Slide the system node slowly into the rack to ensure that your fingers do not get caught in the

side rails.

a) Unlock the blue rail safety latches (A) by pushing them towards the front as shown in the following

figure.

b) Push the system node back into the rack as shown in the following figure until both system node

release latches lock into position.

Memory modules  167

Содержание 9080-M9S

Страница 1: ...Power Systems Removing and replacing parts in the 9080 M9S system IBM ...

Страница 2: ...2020 08 24 Copyright International Business Machines Corporation US Government Users Restricted Rights Use duplication or disclosure restricted by GSA ADP Schedule Contract with IBM Corp ...

Страница 3: ...USB cable 57 Replacing a USB cable 59 Preparing the system for operation 61 Clock and control card 65 Preparing the system to remove and replace a clock and control card 65 Removing the clock and control card from the 9080 M9S system 69 Replacing the clock and control card in the 9080 M9S system 70 Preparing the system for operation 71 Concurrent maintenance circuit card 77 Removing the concurrent...

Страница 4: ...mory VRMs 241 Preparing the system 241 Removing a memory voltage regulator module 257 Replacing a memory voltage regulator module 258 Preparing the system for operation 259 Miscellaneous VRMs 289 Preparing the system 289 Removing a miscellaneous A voltage regulator module 305 Replacing a miscellaneous A voltage regulator module 306 Preparing the system for operation 307 Preparing the system 335 Re...

Страница 5: ...sted platform module card 495 Replacing the Power APSS and trusted platform module card 496 Power interface card 499 Removing the power interface card 499 Replacing the power interface card 501 Power supplies 505 Preparing the system 505 Removing a power supply 510 Replacing a power supply 512 Preparing the system for operation 514 Processor VRM 519 Preparing the system 519 Removing a processor vo...

Страница 6: ...y 691 Removing the time of day battery 692 Replacing the time of day battery 694 Preparing the system for operation 696 USB card 699 Removing and replacing 699 Preparing the system 699 Removing the USB card from the 9080 M9S system 702 Replacing the USB card in the 9080 M9S system 703 Preparing the system for operation 704 Installing 706 Preparing the system 706 Installing the USB card in the 9080...

Страница 7: ...at you want to power off 3 In the content pane click System Actions Operations Power Off 4 Click OK 2 Attach the electrostatic discharge ESD wrist strap The ESD wrist strap must be connected to an unpainted metal surface until the service procedure is completed and if applicable until the service access cover is replaced Attention Attach an electrostatic discharge ESD wrist strap to the front ESD ...

Страница 8: ...charge ESD wrist strap on and that the ESD clip is plugged into a ground jack or connected to an unpainted metal surface If not do so now b Disconnect the power cables that are plugged into the rear of the line cord conduit that you are removing Figure 1 Removing the rear power cords c Loosen the retaining screw A and pull out the latch B Refer to the following figure 2 Power Systems Removing and ...

Страница 9: ...the front of the system a Ensure that you have the electrostatic discharge ESD wrist strap on and that the ESD clip is plugged into a ground jack or connected to an unpainted metal surface If not do so now b Place your fingers on the indentations located on both sides of the cover A and pull the cover away from the system as shown in the following figure Cables 3 ...

Страница 10: ...s that connect to the line cord conduit you are replacing d Label and disconnect the cords that are connected to the power supplies for the line cord conduit you are replacing Refer to the following figure 4 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 11: ...connecting a cord from a power supply e Loosen the retaining screw A of the line cord conduit you are replacing and pull the line cord conduit out from the front of the system Refer to the following figure Cables 5 ...

Страница 12: ...ing steps at the front of the system a Ensure that you have the electrostatic discharge ESD wrist strap on and that the ESD clip is plugged into a ground jack or connected to an unpainted metal surface If not do so now b Slide the line cord conduit into the front of the system Tighten the screw A to secure the line cord conduit Refer to the following figure 6 Power Systems Removing and replacing p...

Страница 13: ...igure 6 Replacing the line cord conduit in the front of the system c Using your labels reconnect the cords to the power supplies as shown in the following figure Tuck the cords into the chassis Cables 7 ...

Страница 14: ...he cover A on the front of the system unit as shown in the following figure so that the four pins B on the system match the four holes at the rear of the cover Press the front cover into position 8 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 15: ...e the electrostatic discharge ESD wrist strap on and that the ESD clip is plugged into a ground jack or connected to an unpainted metal surface If not do so now b Push the line cord conduit into the rear of the system Push the locking latch A in and tighten the securing screw B Refer to the following image Cables 9 ...

Страница 16: ...e line cord conduit in the rear of the system c Reconnect the power cables that are plugged into the rear of the line cord conduit that you are replacing 10 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 17: ...he repair have the customer perform the following steps If the customer did not require the system to be powered off no additional steps are necessary a To power on the system from the Operation list select System Level Activate Then click OK to confirm the operation b To restart the logical partitions complete the following steps 1 In the navigation area click the Resources icon and then click Al...

Страница 18: ...his action causes the identify LED for the faulty part to turn on and causes the blue system ID LED to turn on 2 Use the blue LED to identify the server Ensure that the serial number of the system matches the serial number to be serviced 3 From the Operation list select FRU Level Deactivate Then click OK to confirm the operation 4 Check that an amber identify LED A is flashing for one of the servi...

Страница 19: ...Figure 11 Identify LEDs for the service processor cables on the system node Cables 13 ...

Страница 20: ...you chose to complete this repair with the power off label and disconnect both UPIC cables from the system control unit UPIC cable locations are P1 C1 T1 and P1 C2 T1 a Remove the white plastic lock A from the plug housing 14 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 21: ...able lock b Push down on the blue cable latch B and pull out the UPIC cable from the system control unit Figure 14 Removing the UPIC cable from the system control unit 6 Attach the electrostatic discharge ESD wrist strap Cables 15 ...

Страница 22: ...painted metal surface of the system for a minimum of 5 seconds If at any point in this service process you move away from the system it is important to again discharge yourself by touching an unpainted metal surface for at least 5 seconds before you continue with the service process Removing a service processor FSP cable from the 9080 M9S system To remove a service processor FSP cable from the sys...

Страница 23: ...e 15 Removing the service processor cable from the system control unit 3 Unplug the service processor FSP cable B being serviced from the system node using the pull tab A attached to the connector Cables 17 ...

Страница 24: ...ctrostatic discharge ESD wrist strap on and that the ESD clip is plugged into a ground jack or connected to an unpainted metal surface If not do so now 2 Reconnect the service processor FSP cables Attention Do not drop or damage the metal connectors on the cable If the metal connectors are bent or damaged they need to be replaced Use the Figure 17 on page 19 and Table 1 on page 20 as needed to det...

Страница 25: ...Figure 17 Service processor FSP cabling Cables 19 ...

Страница 26: ... Plug the service processor cable being serviced into the system control unit by inserting the cable into the connector until it locks into place Service processor cable locations are SC1 P1 T2 T3 T4 T5 T6 T7 T8 and T9 Attention Do not drop or damage the metal connectors on the cable If the metal connectors are bent or damaged they need to be replaced Figure 18 Replacing the service processor cabl...

Страница 27: ...removing or replacing a service processor FSP cable complete the steps in this procedure Procedure 1 Ensure that you have the electrostatic discharge ESD wrist strap on and that the ESD clip is plugged into a ground jack or connected to an unpainted metal surface If not do so now 2 If you chose to complete this repair with the power off using your labels reconnect the UPIC cables to the system con...

Страница 28: ...ched to the system 3 If you powered off the system to complete this repair wait for the service processor comes up to the Flexible Service Processor FSP standby state the power on LED on the control panel is flashing slowly then continue to the next step to validate all of the cables If you did not power off the system skip the next step and continue to the step to validate only the UPIC cables 4 ...

Страница 29: ...powered off the system to complete this repair you validated the UPIC cables in the previous step You can skip this step a If you are already connected to the ASMI go to the next step Otherwise click All Systems then select system being serviced Then click Actions View All Actions Launch Advanced Systems Management ASM b In the navigation area expand System Service Aids Cable Plugging Validation T...

Страница 30: ...rial number to be serviced 3 If you powered off the system from the Operation list select FRU Level Deactivate Then click OK to confirm the operation 4 Check that an amber identify LED is flashing for one of the SMP cables as shown in the following figures Figure 22 Identify LEDs for the SMP cables on the system node 5 If you chose to complete this repair with the power off label and disconnect bo...

Страница 31: ...igure 23 Removing the UPIC cable lock b Push down on the blue cable latch B and pull out the UPIC cable from the system control unit Figure 24 Removing the UPIC cable from the system control unit 6 Attach the electrostatic discharge ESD wrist strap Cables 25 ...

Страница 32: ...und jack or connected to an unpainted metal surface If not do so now 2 Is the system power off Yes Continue with step 7 on page 26 No Continue with the next step 3 Access the Advanced System Management Interface ASMI a In the navigation pane click Resources All Systems to view all the systems that are associated with your Hardware Management Console HMC b Select the server that you want to work wi...

Страница 33: ...e cable If the metal connectors are bent or damaged they need to be replaced a Slightly push in the cable bundle A as shown in the following figure to relieve the spring pressure of the cable connector b Pull the blue latch B as shown in the following figure to release the inner cable latch c Remove the SMP cable C from the system node Cables 27 ...

Страница 34: ...le in the system complete the steps in this procedure Procedure 1 Ensure that you have the electrostatic discharge ESD wrist strap on and that the ESD clip is plugged into a ground jack or connected to an unpainted metal surface If not do so now 2 If you are replacing a faulty cable complete the following steps a Remove the faulty cable from the side of the rack unclipping and removing the hook an...

Страница 35: ...node system configuration use Figure 27 on page 29 and Table 2 on page 29 to determine the point to point cabling for SMP cables Figure 27 Cabling a Two Node Configuration Table 2 Cabling a Two Node Configuration Each connection that is shown in the diagram represents a pair of SMP cables Cable Cable type and length From To 5C 880 mm 2 9 ft ND1 P1 T1 ND2 P1 T1 5D 880 mm 2 9 ft ND1 P1 T2 ND2 P1 T2 ...

Страница 36: ...6 ND2 P1 T16 6W 1225 mm 4 01 ft ND1 P1 T17 ND2 P1 T17 6X 1225 mm 4 01 ft ND1 P1 T18 ND2 P1 T18 5W 1005 mm 3 3 ft ND1 P1 T23 ND2 P1 T23 5X 1005 mm 3 3 ft ND1 P1 T24 ND2 P1 T24 6Y 1005 mm 3 3 ft ND1 P1 T25 ND2 P1 T25 6Z 1005 mm 3 3 ft ND1 P1 T26 ND2 P1 T26 5Y 880 mm 2 9 ft ND1 P1 T31 ND2 P1 T31 5Z 880 mm 2 9 ft ND1 P1 T32 ND2 P1 T32 If you have a three node system configuration use Figure 28 on page...

Страница 37: ...Figure 28 Cabling a Three Node Configuration Table 3 Cabling a Three Node Configuration Cable Cable type and length From To 5C 880 mm 2 9 ft ND3 P1 T1 ND2 P1 T1 Cables 31 ...

Страница 38: ...1 P1 T9 3B 1225 mm 4 01 ft ND3 P1 T16 ND1 P1 T10 3W 1225 mm 4 01 ft ND3 P1 T17 ND1 P1 T23 3X 1225 mm 4 01 ft ND3 P1 T18 ND1 P1 T24 5W 1005 mm 3 3 ft ND3 P1 T23 ND2 P1 T23 5X 1005 mm 3 3 ft ND3 P1 T24 ND2 P1 T24 3Y 1225 mm 4 01 ft ND3 P1 T25 ND1 P1 T31 3Z 1225 mm 4 01 ft ND3 P1 T26 ND1 P1 T32 5Y 880 mm 2 9 ft ND3 P1 T31 ND2 P1 T31 5Z 880 mm 2 9 ft ND3 P1 T32 ND2 P1 T32 6C 1005 mm 3 3 ft ND2 P1 T7 N...

Страница 39: ...1 ft ND2 P1 T16 ND1 P1 T16 6W 1225 mm 4 01 ft ND2 P1 T17 ND1 P1 T17 6X 1225 mm 4 01 ft ND2 P1 T18 ND1 P1 T18 6Y 1005 mm 3 3 ft ND2 P1 T25 ND1 P1 T25 6Z 1005 mm 3 3 ft ND2 P1 T26 ND1 P1 T26 If you have a four node system configuration use Figure 29 on page 34 and Table 4 on page 35 to determine the point to point cabling for SMP cables Cables 33 ...

Страница 40: ...Figure 29 Cabling a Four Node Configuration 34 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 41: ...T3 1D 1425 mm 4 7 ft ND4 P1 T8 ND1 P1 T4 2A 1225 mm 4 01 ft ND4 P1 T9 ND2 P1 T11 2B 1225 mm 4 01 ft ND4 P1 T10 ND2 P1 T12 4A 1005 mm 3 3 ft ND4 P1 T11 ND3 P1 T11 4B 1005 mm 3 3 ft ND4 P1 T12 ND3 P1 T12 1A 1625 mm 5 3 ft ND4 P1 T15 ND1 P1 T11 1B 1625 mm 5 3 ft ND4 P1 T16 ND1 P1 T12 1W 1625 mm 5 3 ft ND4 P1 T17 ND1 P1 T21 1X 1625 mm 5 3 ft ND4 P1 T18 ND1 P1 T22 4W 1005 mm 3 3 ft ND4 P1 T21 ND3 P1 T2...

Страница 42: ...D4 P1 T31 ND2 P1 T29 2Z 1225 mm 4 01 ft ND4 P1 T32 ND2 P1 T30 Cables originating on ND3 5C 880 mm 2 9 ft ND3 P1 T1 ND2 P1 T1 5D 880 mm 2 9 ft ND3 P1 T2 ND2 P1 T2 3C 1225 mm 4 01 ft ND3 P1 T7 ND1 P1 T1 3D 1225 mm 4 01 ft ND3 P1 T8 ND1 P1 T2 5A 1005 mm 3 3 ft ND3 P1 T9 ND2 P1 T9 5B 1005 mm 3 3 ft ND3 P1 T10 ND2 P1 T10 3A 1225 mm 4 01 ft ND3 P1 T15 ND1 P1 T9 3B 1225 mm 4 01 ft ND3 P1 T16 ND1 P1 T10 3...

Страница 43: ...1 T8 ND1 P1 T8 6A 1225 mm 4 01 ft ND2 P1 T15 ND1 P1 T15 6B 1225 mm 4 01 ft ND2 P1 T16 ND1 P1 T16 6W 1225 mm 4 01 ft ND2 P1 T17 ND1 P1 T17 6X 1225 mm 4 01 ft ND2 P1 T18 ND1 P1 T18 6Y 1005 mm 3 3 ft ND2 P1 T25 ND1 P1 T25 6Z 1005 mm 3 3 ft ND2 P1 T26 ND1 P1 T26 4 Press the SMP cable and the blue tab together with your fingers and thumb to hold the SMP cable Plug the SMP cable into the previously iden...

Страница 44: ...hat you previously identified are reconnected 6 Route the cable to the cable management bracket and to the sides of the system nodes 7 If you removed any SMP cable clips from the side of the rack using your labels reattach the cable bundle to the side of the cable management bracket as shown in the following figure 38 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 45: ...ble bundles refer to the information card inserted into the rear of the system control unit You can also refer to the following figures The number in the cable label indicates the bundle for that cable Two system node configuration The two system node configuration has four cable bundles Cables 39 ...

Страница 46: ...aches to the clip C Three system node configuration The three system node configuration has four cable bundles Figure 33 Bundling and connecting SMP cables for three system nodes Two bundles named B3 with the 3 cables The left B3 bundle contains 3A 3B 3C and 3D This bundle attaches to the clip A The right B3 bundle contains 3W 3X 3Y and 3Z This bundle attaches to the clip F Two bundles named B5 wi...

Страница 47: ...dles named B3 with the 3 cables The left B3 bundle contains 3A 3B 3C and 3D This bundle attaches to the clips C The right B3 bundle contains 3W 3X 3Y and 3Z This bundle attaches to the clips J Two bundles named B4 with the 4 cables The left B4 bundle contains 4A 4B 4C and 4D This bundle attaches to the clip D The right B4 bundle contains 4W 4X 4Y and 4Z This bundle attaches to the clip G Two bundl...

Страница 48: ... If you chose to complete this repair with the power off using your labels reconnect the UPIC cables to the system control unit UPIC cable locations are P1 C1 T1 and P1 C2 T1 a Ensure that the white plastic lock is pulled back from the plug housing b Plug the UPIC cable A into the previously identified location in the system control unit by inserting the cable into the connector until it locks int...

Страница 49: ...nt c If your configuration includes two or more nodes expand System Service Aids Cable Plugging Validation Then click Verify Node Position Otherwise if your configuration includes only one node continue to the next step If the system is cabled correctly the blue identify LED on each system node will light up in sequence from the top node to the bottom node If the LEDs do not light up in sequence t...

Страница 50: ...oblems and repeat steps b and c as needed until the status is OK for all cables d Exit the ASMI and continue to the next step 6 If you powered off the system from the Operation list select FRU Level Activate Then click OK to confirm the operation 7 From the Operation list select Reset Identify LED Then click OK to confirm the operation UPIC cables Preparing the 9080 M9S system to remove and replac...

Страница 51: ...Figure 37 Identify LEDs for the UPIC cables on the system node Cables 45 ...

Страница 52: ...ou use an ESD wrist strap follow all electrical safety procedures An ESD wrist strap is used for static control It does not increase or decrease your risk of receiving electric shock when using or working on electrical equipment If you do not have an ESD wrist strap just prior to removing the product from ESD packaging and installing or replacing hardware touch an unpainted metal surface of the sy...

Страница 53: ...nted metal surface If not do so now 2 Identify and label where each end of a UPIC cable is connected to the system node and system control unit 3 To remove the UPIC cable from the system node complete the following steps a Remove the white plastic lock A from the plug housing as shown in the following figure Figure 39 Removing the UPIC cable lock b Push down on the blue cable latch B and pull out ...

Страница 54: ...4 To remove the UPIC cable from the system control unit complete the following steps UPIC cable locations are P1 C1 T1 and P1 C2 T1 a Remove the white plastic lock A from the plug housing 48 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 55: ... latch B and pull out the UPIC cable from the system control unit Figure 42 Removing the UPIC cable from the system control unit 5 If the system is powered off repeat steps 3 on page 47 4 on page 48 until all the UPIC cables previously identified are unplugged Cables 49 ...

Страница 56: ...nformation to determine the point to point cabling for UPIC cables If you have a single node system configuration use Figure 43 on page 50 and Table 5 on page 50 to determine the point to point cabling for UPIC cables Figure 43 Single Node Configuration UPIC Cabling Table 5 Single Node Configuration UPIC Cabling Cable number From To 1 SC1 P1 C1 T1 ND1 P1 C9 T1 2 SC1 P1 C2 T1 ND1 P1 C10 T1 If you h...

Страница 57: ... P1 C2 T1 ND2 P1 C10 T1 3 To replace the UPIC cable in the system node complete the following steps a Ensure that the white plastic lock is pulled back from the plug housing b Plug the UPIC cable A into the previously identified location in the system node by inserting the cable into the connector until it locks into place as shown in the following figure Cables 51 ...

Страница 58: ...e 45 Replacing the UPIC cable into the system node c Push the white plastic lock B onto the plug housing as shown in the following figure 52 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 59: ...should be firmly attached to the system 4 To replace the UPIC cable in the system control unit complete the following steps UPIC cable locations are P1 C1 T1 and P1 C2 T1 a Ensure that the white plastic lock is pulled back from the plug housing b Plug the UPIC cable A into the previously identified location in the system control unit by inserting the cable into the connector until it locks into pl...

Страница 60: ...nt points to ensure it is locked into place Pull the cable connector do not pull on the wire The cables should be firmly attached to the system 5 If the system is powered off repeat steps 3 on page 51 4 on page 53 until all the UPIC cables previously identified are reconnected 6 If applicable secure the cable to the side of the rack with the hook and loop fastener 54 Power Systems Removing and rep...

Страница 61: ... The system validates that the cables are installed in the correct locations Expand System Service Aids Cable Plugging Validation to display a table with the results Ensure that the plugging status is OK for each cable in the displayed table If the status is OK no further action is required If the status is not OK review the error logs correct the problems and repeat steps b c and d as needed unti...

Страница 62: ... the serial number to be serviced 3 If you powered off the system from the Operation list select FRU Level Deactivate Then click OK to confirm the operation 4 If you chose to complete this repair with the power off label and disconnect both UPIC cables from the system control unit as shown in the following figure UPIC cable locations are P1 C1 T1 and P1 C2 T1 a Remove the white plastic lock A from...

Страница 63: ...se or decrease your risk of receiving electric shock when using or working on electrical equipment If you do not have an ESD wrist strap just prior to removing the product from ESD packaging and installing or replacing hardware touch an unpainted metal surface of the system for a minimum of 5 seconds If at any point in this service process you move away from the system it is important to again dis...

Страница 64: ...ontrol unit 3 Remove the USB cable from the system node as shown in the following figure Figure 51 Removing the USB cable from the system node 4 Remove the USB cable from the system control unit as shown in the following figure 58 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 65: ...e the steps in this procedure Procedure 1 Ensure that you have the electrostatic discharge ESD wrist strap on and that the ESD clip is plugged into a ground jack or connected to an unpainted metal surface If not do so now 2 Refer to the following figure and table to determine the point to point cabling for the USB cable Figure 53 USB Cabling Cables 59 ...

Страница 66: ...ng the cable into the connector as shown in the following figure Figure 54 Replacing the USB cable into the system node 4 Plug the USB cable into the previously identified location in the system control unit by inserting the cable into the connector as shown in the following figure 60 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 67: ...ap on and that the ESD clip is plugged into a ground jack or connected to an unpainted metal surface If not do so now 2 If you chose to complete this repair with the power off using your labels reconnect the UPIC cables to the system control unit UPIC cable locations are P1 C1 T1 and P1 C2 T1 a Ensure that the white plastic lock is pulled back from the plug housing b Plug the UPIC cable A into the...

Страница 68: ...ched to the system 3 If you powered off the system to complete this repair wait for the service processor comes up to the Flexible Service Processor FSP standby state the power on LED on the control panel is flashing slowly then continue to the next step to validate all of the cables If you did not power off the system skip the next step and continue to the step to validate only the UPIC cables 4 ...

Страница 69: ... e Exit the ASMI and skip the following step 5 Access the ASMI and run the Cable Plugging Validation utility to validate only the UPIC cables Note If you powered off the system to complete this repair you validated the UPIC cables in the previous step You can skip this step a If you are already connected to the ASMI go to the next step Otherwise click All Systems then select system being serviced ...

Страница 70: ...64 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 71: ...Set Identify LED Then click OK to confirm the operation This action causes the identify LED for the faulty part to turn on and causes the blue system ID LED to turn on 2 Open the rear rack door if necessary 3 Use the blue LED to identify the server Ensure that the serial number of the system matches the serial number to be serviced 4 Check that an amber identify LED is flashing for one of the cloc...

Страница 72: ...for static control It does not increase or decrease your risk of receiving electric shock when using or working on electrical equipment If you do not have an ESD wrist strap just prior to removing the product from ESD packaging and installing or replacing hardware touch an unpainted metal surface of the system for a minimum of 5 seconds If at any point in this service process you move away from th...

Страница 73: ...blue cable latch B and pull out the UPIC cable from the system control unit Figure 60 Removing the UPIC cable from the system control unit 7 Place your fingers on the indentations located on both sides of the cover A and pull the cover away from the system as shown in the following figure Clock and control card 67 ...

Страница 74: ...be removed with the system operating ensure that all such loose material is secured away from the fan area to prevent any loose material from being pulled into the fan Figure 61 Removing the front cover 8 Disconnect all of the front power cords that plug into the power supplies of the system node that is being serviced 68 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 75: ... jack or connected to an unpainted metal surface If not do so now 2 To remove a clock and control card complete the following steps a For the clock and control card that has the amber LED on pull the blue clock and control card handle latch A to the right as shown in the following figure b Hold on to the clock and control card handle and by using your hand to support the bottom of the clock and co...

Страница 76: ...rface If not do so now 2 To replace a clock and control card complete the following steps a Ensure that the clock and control card handle A is open as shown in the following figure b Hold on to the clock and control card handle and by using your hand to support the bottom of the clock and control card push the clock and control card into its slot as shown in the following figure c Rotate the handl...

Страница 77: ...replacing the clock and control card complete the steps in this procedure Procedure 1 Ensure that you have the electrostatic discharge ESD wrist strap on and that the ESD clip is plugged into a ground jack or connected to an unpainted metal surface If not do so now 2 Connect all of the front power cords that plug into the power supplies of the system node Tuck the cords into the chassis Clock and ...

Страница 78: ...over A on the front of the system unit as shown in the following figure so that the four pins B on the system match the four holes at the rear of the cover Press the front cover into position 72 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 79: ...les to the system control unit UPIC cable locations are P1 C1 T1 and P1 C2 T1 a Ensure that the white plastic lock is pulled back from the plug housing b Plug the UPIC cable A into the previously identified location in the system control unit by inserting the cable into the connector until it locks into place Clock and control card 73 ...

Страница 80: ...ched to the system 5 If you powered off the system to complete this repair wait for the service processor comes up to the Flexible Service Processor FSP standby state the power on LED on the control panel is flashing slowly then continue to the next step to validate all of the cables If you did not power off the system skip the next step and continue to the step to validate only the UPIC cables 6 ...

Страница 81: ...and d as needed until the status is OK for all cables e Exit the ASMI and skip the following step 7 Access the ASMI and run the Cable Plugging Validation utility to validate only the UPIC cables Note If you powered off the system to complete this repair you validated the UPIC cables in the previous step You can skip this step a If you are already connected to the ASMI go to the next step Otherwise...

Страница 82: ...76 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 83: ...ge ESD wrist strap on and that the ESD clip is plugged into a ground jack or connected to an unpainted metal surface If not do so now 2 Remove the concurrent maintenance circuit card a Unlock the levers A to release the concurrent maintenance circuit card from its connector Refer to the following image b Rotate the levers in the direction shown c While holding the concurrent maintenance circuit ca...

Страница 84: ...a ground jack or connected to an unpainted metal surface If not do so now 2 Replace the concurrent maintenance circuit card a With the levers A in the open position hold the concurrent maintenance circuit card by the levers and lower the card into its slot in the system Refer to the following image b Gently push the concurrent maintenance circuit card into its connector c Rotate the levers in the ...

Страница 85: ...Figure 70 Replacing the concurrent maintenance circuit card Concurrent maintenance circuit card 79 ...

Страница 86: ...80 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 87: ...conds If at any point in this service process you move away from the system it is important to again discharge yourself by touching an unpainted metal surface for at least 5 seconds before you continue with the service process Removing the control panel from the 9080 M9S system To remove a control panel complete the steps in this procedure Procedure 1 Ensure that you have the electrostatic dischar...

Страница 88: ...eps in this procedure Procedure 1 Ensure that you have the electrostatic discharge ESD wrist strap on and that the ESD clip is plugged into a ground jack or connected to an unpainted metal surface If not do so now 2 Access the Advanced System Management Interface ASMI Attention During this procedure Do not reset the service processor do not remove the service processor card and do not power off an...

Страница 89: ...then slightly pull the latch at C with your index finger This action opens the latch e Continue to push in the lever with your thumb until the latch is fully seated at C Figure 72 Replacing the control panel 4 In the navigation area select Concurrent maintenance Control Panel 5 In the ASMI Control Panel window select the Install action and press Continue 6 Verify that the location code C5 for the ...

Страница 90: ...the front of the system control unit as shown in the following figure and press the cover into position Note Use care to not touch the power button when replacing the cover Figure 73 Installing the front cover 3 If you unplugged a USB cable from the control panel using your label replace the USB cable in the control panel 4 Check that the power indicator is on 5 If you powered off the system to co...

Страница 91: ...atus is OK for each cable in the displayed table If the status is OK no further action is required If the status is not OK review the error logs correct the problems and repeat steps b c and d as needed until the status is OK for all cables e Exit the ASMI and skip the following step 7 Access the ASMI and run the Cable Plugging Validation utility to validate only the UPIC cables Note If you powere...

Страница 92: ...86 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 93: ...hat you are working on For instructions see Identifying a part www ibm com support knowledgecenter POWER9 p9haj sal htm Use the blue identify LED on the enclosure to locate the system Ensure that the serial number of the system matches the serial number to be serviced 2 If applicable open the rack front door 3 Pull the cover A away from the system control unit as shown in the following figure Figu...

Страница 94: ...p 7 b on page 88 Otherwise prepare to power off the system Attention Ensure that you shut down the running logical partitions on the managed system before you power off the managed system Powering off the managed system without shutting down the logical partitions first causes the logical partitions to shut down abnormally and can cause data loss If you use a Virtual I O Server VIOS logical partit...

Страница 95: ...nted metal surface for at least 5 seconds before you continue with the service process Removing a fan from the 9080 M9S system control unit To remove a fan from the system control unit complete the steps in this procedure Procedure 1 Ensure that you have the electrostatic discharge ESD wrist strap on and that the ESD clip is plugged into a ground jack or connected to an unpainted metal surface If ...

Страница 96: ...wn in the following figure b Hold on to the fan handle and by using your hand to support the bottom of the fan push the fan into its slot as shown in the following figure Ensure that the fan is kept level with the enclosure and that you push the fan straight in to the enclosure c Push the fan handle in the direction shown in the following figure d Push against the front of the latch B with your th...

Страница 97: ... that you are servicing 3 If you powered off the system to complete this repair wait for the service processor comes up to the Flexible Service Processor FSP standby state the power on LED on the control panel is flashing slowly then continue to the next step to validate all of the cables If you did not power off the system skip the next step and continue to the step to validate only the UPIC cabl...

Страница 98: ... step Otherwise click All Systems then select system being serviced Then click Actions View All Actions Launch Advanced Systems Management ASM b In the navigation area expand System Service Aids Cable Plugging Validation Then click Validate UPIC Cables The system verifies that the UPIC cables are present Note Older firmware levels do not support validating the UPIC cables while the system is at FS...

Страница 99: ...t knowledgecenter POWER9 p9haj sal htm Use the blue identify LED on the enclosure to locate the system Ensure that the serial number of the system matches the serial number to be serviced 2 If applicable open the rack front door 3 Place your fingers on the indentations located on both sides of the cover A and pull the cover away from the system as shown in the following figure CAUTION The fans can...

Страница 100: ...ue the repair operation when the system power is turned on the following conditions must be true Fans must be installed in all five slots Each of the five fans has a green LED and an amber LED as shown in Figure 80 on page 95 The green LED is lit solid for all five fans but the fan with the failure has the flashing amber fault LED If only one amber fault LED is On the repair operation can be compl...

Страница 101: ...er turned on continue with step 9 on page 96 7 If you need to power off the server to complete the repair operation complete the following steps 8 If you chose to complete this repair with the power off label and disconnect both UPIC cables from the system control unit UPIC cable locations are P1 C1 T1 and P1 C2 T1 a Remove the white plastic lock A from the plug housing Fans 95 ...

Страница 102: ...blue cable latch B and pull out the UPIC cable from the system control unit Figure 82 Removing the UPIC cable from the system control unit 9 Attach the electrostatic discharge ESD wrist strap 96 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 103: ...ocess you move away from the system it is important to again discharge yourself by touching an unpainted metal surface for at least 5 seconds before you continue with the service process Removing a fan from the 9080 M9S system node To remove a fan from the system complete the steps in this procedure Procedure 1 Ensure that you have the electrostatic discharge ESD wrist strap on and that the ESD cl...

Страница 104: ... in the following figure b Hold on to the fan handle and by using your hand to support the bottom of the fan push the fan into its slot as shown in the following figure Ensure that the fan is kept level with the enclosure and that you push the fan straight in to the enclosure c Push the fan handle in the direction shown in the following figure d Push against the front of the latch B with your thum...

Страница 105: ...t the ESD clip is plugged into a ground jack or connected to an unpainted metal surface If not do so now 2 If you chose to complete this repair with the power off using your labels reconnect the UPIC cables to the system control unit UPIC cable locations are P1 C1 T1 and P1 C2 T1 a Ensure that the white plastic lock is pulled back from the plug housing b Plug the UPIC cable A into the previously i...

Страница 106: ...ssor comes up to the Flexible Service Processor FSP standby state the power on LED on the control panel is flashing slowly then continue to the next step to validate all of the cables If you did not power off the system skip the next step and continue to the step to validate only the UPIC cables 4 Access the ASMI and run the Cable Plugging Validation utility to validate all of the cables a If you ...

Страница 107: ...to the ASMI go to the next step Otherwise click All Systems then select system being serviced Then click Actions View All Actions Launch Advanced Systems Management ASM b In the navigation area expand System Service Aids Cable Plugging Validation Then click Validate UPIC Cables The system verifies that the UPIC cables are present Note Older firmware levels do not support validating the UPIC cables...

Страница 108: ...Figure 87 Installing the front cover 10 If applicable close the rack front door 102 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 109: ... proper cooling a memory module or a memory module filler is required in all locations Table 8 on page 103 shows the base memory plugging rules Table 9 on page 103 shows the plugging rules for adding memory Quads must be added next to a processor The quads can be added in any order Table 8 Base memory plugging rules Memory module location CPU socket P1 C22 P1 C23 P1 C28 P1 C29 P1 P1 C30 P1 C31 P1 ...

Страница 110: ...t UPIC cable locations are P1 C1 T1 and P1 C2 T1 a Remove the white plastic lock A from the plug housing Figure 88 Removing the UPIC cable lock b Push down on the blue cable latch B and pull out the UPIC cable from the system control unit 104 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 111: ...out more than one drawer at a time The rack might become unstable if you pull out more than one drawer at a time a Label and disconnect the rear power cords from the system node being serviced as shown in the following figure Notes This system node might be equipped with two or more power supplies If the removing and replacing procedures require the system power to be turned off ensure that all po...

Страница 112: ...Figure 90 Removing the rear power cords L003 or or 106 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 113: ...wer cables To remove all hazardous voltages disconnect all power cords and power cables L003 b Label and disconnect all of the PCIe cables or transceivers that are attached to the PCIe adapters for the system node you are servicing Use hook and loop fasteners to hold the PCIe cables in place Memory modules 107 ...

Страница 114: ... connector Figure 91 Removing the service processor cable from the system node d Label and unplug the UPIC cables for the system node that you are servicing if applicable 1 Remove the white plastic lock A from the plug housing as shown in the following figure 108 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 115: ...Figure 92 Removing the UPIC cable lock 2 Push down on the blue cable latch B and pull out the UPIC cable from the system node as shown in the following figure Memory modules 109 ...

Страница 116: ...r more slack in the SMP cables label and unclip the SMP cable bundle from the side of the cable management bracket as shown in the following figure and move the SMP cables to near the center of the system node 110 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 117: ... on the cable If the metal connectors are bent or damaged they need to be replaced 1 Slightly push in the cable bundle A as shown in the following figure to relieve the spring pressure of the cable connector 2 Pull the blue latch B as shown in the following figure to release the inner cable latch 3 Remove the SMP cable C from the system node Memory modules 111 ...

Страница 118: ...em node use hook and loop fasteners to connect the cables to the cable management bracket so the cables do not hang loosely h If you are servicing system node ND1 or ND2 label and unplug the USB cable as shown in the following figure 112 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 119: ...Figure 96 Removing the USB cable from the system node i If present remove the two screws A at the rear of the system as shown in the following figure Memory modules 113 ...

Страница 120: ...Figure 97 Removing the rear screws j If present remove the four screws A at the front of the system as shown in the following figure 114 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 121: ...ront screws k Release the side latches B for the system node by pressing them downward and then pulling outward as shown in the following figure l Pull out the system node C as shown in the following figure Memory modules 115 ...

Страница 122: ...does not increase or decrease your risk of receiving electric shock when using or working on electrical equipment If you do not have an ESD wrist strap just prior to removing the product from ESD packaging and installing or replacing hardware touch an unpainted metal surface of the system for a minimum of 5 seconds If at any point in this service process you move away from the system it is importa...

Страница 123: ...unit Figure 100 Removing the service access cover 7 To activate the identify LED for the locations for installing the memory modules press and hold either push button on the trusted platform module card as shown in the following figure Verify that the LED A is lit which indicates that sufficient power exists for the identify LED If the LED is not lit use the location code to find the physical loca...

Страница 124: ... a note of which locations are flashing they indicate the memory modules to install Figure 102 on page 119 shows the locations of the memory module The LEDs are next to the memory module Record the location of the identifying LED 118 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 125: ... metal surface If not do so now 2 Use the slot information that you recorded to determine the slot location to place the memory module 3 If a memory module filler is present remove the memory module filler a Push the tab A down and outward as shown in the following figure The lever action of the tabs forces the memory module filler out of the connector b Grasp the top plastic portion and remove th...

Страница 126: ...event a memory module from being installed incorrectly Note the location of the key tab within the memory module connector before you attempt to install the memory module 5 Install the memory module by pushing it into slot until the tabs A lock into place as shown in the following figure 120 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 127: ...D wrist strap on and that the ESD clip is plugged into a ground jack or connected to an unpainted metal surface If not do so now 2 Replace the service access cover by completing the following steps a Slide the cover A onto the system unit as shown in the following figure b Close the release latch B by pushing it in the direction shown in the following figure Memory modules 121 ...

Страница 128: ...ck to ensure that your fingers do not get caught in the side rails a Unlock the blue rail safety latches A by pushing them towards the front as shown in the following figure b Push the system node back into the rack as shown in the following figure until both system node release latches lock into position 122 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 129: ...Figure 106 Placing the system node into the operating position c Replace the two screws A at the rear of the system if you removed them earlier as shown in the following figure Memory modules 123 ...

Страница 130: ...Figure 107 Replacing the rear screws d Replace the four screws A at the front of the system node as shown in the following figure 124 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 131: ...system node that you are servicing Then refer to your labels and the following steps to reconnect the SMP cables that you removed from the system node you are servicing If you have a two node system configuration use Figure 109 on page 126 and Table 10 on page 126 to determine the point to point cabling for SMP cables Memory modules 125 ...

Страница 132: ...ram represents a pair of SMP cables Cable Cable type and length From To 5C 880 mm 2 9 ft ND1 P1 T1 ND2 P1 T1 5D 880 mm 2 9 ft ND1 P1 T2 ND2 P1 T2 6C 1005 mm 3 3 ft ND1 P1 T7 ND2 P1 T7 6D 1005 mm 3 3 ft ND1 P1 T8 ND2 P1 T8 5A 1005 mm 3 3 ft ND1 P1 T9 ND2 P1 T9 126 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 133: ...W 1225 mm 4 01 ft ND1 P1 T17 ND2 P1 T17 6X 1225 mm 4 01 ft ND1 P1 T18 ND2 P1 T18 5W 1005 mm 3 3 ft ND1 P1 T23 ND2 P1 T23 5X 1005 mm 3 3 ft ND1 P1 T24 ND2 P1 T24 6Y 1005 mm 3 3 ft ND1 P1 T25 ND2 P1 T25 6Z 1005 mm 3 3 ft ND1 P1 T26 ND2 P1 T26 5Y 880 mm 2 9 ft ND1 P1 T31 ND2 P1 T31 5Z 880 mm 2 9 ft ND1 P1 T32 ND2 P1 T32 If you have a three node system configuration use Figure 110 on page 128 and Tabl...

Страница 134: ...ing a Three Node Configuration Table 11 Cabling a Three Node Configuration Cable Cable type and length From To 5C 880 mm 2 9 ft ND3 P1 T1 ND2 P1 T1 128 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 135: ...5 mm 4 01 ft ND3 P1 T15 ND1 P1 T9 3B 1225 mm 4 01 ft ND3 P1 T16 ND1 P1 T10 3W 1225 mm 4 01 ft ND3 P1 T17 ND1 P1 T23 3X 1225 mm 4 01 ft ND3 P1 T18 ND1 P1 T24 5W 1005 mm 3 3 ft ND3 P1 T23 ND2 P1 T23 5X 1005 mm 3 3 ft ND3 P1 T24 ND2 P1 T24 3Y 1225 mm 4 01 ft ND3 P1 T25 ND1 P1 T31 3Z 1225 mm 4 01 ft ND3 P1 T26 ND1 P1 T32 5Y 880 mm 2 9 ft ND3 P1 T31 ND2 P1 T31 5Z 880 mm 2 9 ft ND3 P1 T32 ND2 P1 T32 6C ...

Страница 136: ...25 mm 4 01 ft ND2 P1 T17 ND1 P1 T17 6X 1225 mm 4 01 ft ND2 P1 T18 ND1 P1 T18 6Y 1005 mm 3 3 ft ND2 P1 T25 ND1 P1 T25 6Z 1005 mm 3 3 ft ND2 P1 T26 ND1 P1 T26 If you have a four node system configuration use Figure 111 on page 131 and Table 12 on page 132 to determine the point to point cabling for SMP cables 130 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 137: ...Figure 111 Cabling a Four Node Configuration Memory modules 131 ...

Страница 138: ...8 ND1 P1 T4 2A 1225 mm 4 01 ft ND4 P1 T9 ND2 P1 T11 2B 1225 mm 4 01 ft ND4 P1 T10 ND2 P1 T12 4A 1005 mm 3 3 ft ND4 P1 T11 ND3 P1 T11 4B 1005 mm 3 3 ft ND4 P1 T12 ND3 P1 T12 1A 1625 mm 5 3 ft ND4 P1 T15 ND1 P1 T11 1B 1625 mm 5 3 ft ND4 P1 T16 ND1 P1 T12 1W 1625 mm 5 3 ft ND4 P1 T17 ND1 P1 T21 1X 1625 mm 5 3 ft ND4 P1 T18 ND1 P1 T22 4W 1005 mm 3 3 ft ND4 P1 T21 ND3 P1 T21 4X 1005 mm 3 3 ft ND4 P1 T2...

Страница 139: ...1 T30 2Y 1225 mm 4 01 ft ND4 P1 T31 ND2 P1 T29 2Z 1225 mm 4 01 ft ND4 P1 T32 ND2 P1 T30 Cables originating on ND3 5C 880 mm 2 9 ft ND3 P1 T1 ND2 P1 T1 5D 880 mm 2 9 ft ND3 P1 T2 ND2 P1 T2 3C 1225 mm 4 01 ft ND3 P1 T7 ND1 P1 T1 3D 1225 mm 4 01 ft ND3 P1 T8 ND1 P1 T2 5A 1005 mm 3 3 ft ND3 P1 T9 ND2 P1 T9 5B 1005 mm 3 3 ft ND3 P1 T10 ND2 P1 T10 3A 1225 mm 4 01 ft ND3 P1 T15 ND1 P1 T9 3B 1225 mm 4 01 ...

Страница 140: ...1 ft ND2 P1 T15 ND1 P1 T15 6B 1225 mm 4 01 ft ND2 P1 T16 ND1 P1 T16 6W 1225 mm 4 01 ft ND2 P1 T17 ND1 P1 T17 6X 1225 mm 4 01 ft ND2 P1 T18 ND1 P1 T18 6Y 1005 mm 3 3 ft ND2 P1 T25 ND1 P1 T25 6Z 1005 mm 3 3 ft ND2 P1 T26 ND1 P1 T26 a Press the SMP cable and the blue tab together with your fingers and thumb to hold the SMP cable Plug the SMP cable into the previously identified location in the system...

Страница 141: ...ll the SMP cables previously identified are reconnected to the system node you are servicing c If you removed any SMP cable clips from the side of the rack using your labels reattach the cable bundle to the side of the cable management bracket as shown in the following figure Memory modules 135 ...

Страница 142: ...rmation card inserted into the rear of the system control unit You can also refer to the following figures The number in the cable label indicates the bundle for that cable Two system node configuration The two system node configuration has four cable bundles 136 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 143: ...e attaches to the clip C Three system node configuration The three system node configuration has four cable bundles Figure 115 Bundling and connecting SMP cables for three system nodes Two bundles named B3 with the 3 cables The left B3 bundle contains 3A 3B 3C and 3D This bundle attaches to the clip A The right B3 bundle contains 3W 3X 3Y and 3Z This bundle attaches to the clip F Two bundles named...

Страница 144: ... This bundle attaches to the clips J Two bundles named B4 with the 4 cables The left B4 bundle contains 4A 4B 4C and 4D This bundle attaches to the clip D The right B4 bundle contains 4W 4X 4Y and 4Z This bundle attaches to the clip G Two bundles named B5 with the 5 cables The left B5 bundle contains 5A 5B 5C and 5D This bundle attaches to the clip E The right B5 bundle contains 5W 5X 5Y and 5Z Th...

Страница 145: ...igure 117 Single Node Configuration UPIC Cabling Table 13 Single Node Configuration UPIC Cabling Cable number From To 1 SC1 P1 C1 T1 ND1 P1 C9 T1 2 SC1 P1 C2 T1 ND1 P1 C10 T1 If you have a two three or four node system configuration use Figure 118 on page 140 and Table 14 on page 140 to determine the point to point cabling for UPIC cables Memory modules 139 ...

Страница 146: ...replace the UPIC cable in the system node complete the following steps 1 Ensure that the white plastic lock is pulled back from the plug housing 2 Plug the UPIC cable A into the previously identified location in the system node by inserting the cable into the connector until it locks into place as shown in the following figure 140 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 147: ...Figure 119 Replacing the UPIC cable into the system node 3 Push the white plastic lock B onto the plug housing as shown in the following figure Memory modules 141 ...

Страница 148: ...attached to the system b Repeat step 5 a on page 140 until all the UPIC cables previously identified are reconnected to the system node you are servicing c If applicable secure the cable to the side of the rack with the hook and loop fastener 6 Using your labels reconnect the service processor FSP cables that you removed from the system node you are servicing 142 Power Systems Removing and replaci...

Страница 149: ...Figure 121 Service processor FSP cabling Memory modules 143 ...

Страница 150: ... P1 T3 ND1 P1 C9 T2 B 355 mm 1 16 ft SC1 P1 T5 ND1 P1 C10 T2 7 Review the following information to identify the locations where the USB cable connects to the system node that you are servicing and to the system control unit Then reconnect the USB cable that you removed Figure 122 USB Cabling Table 16 USB Cabling From To ND1 or ND2 P1 C13 T3 SC1 P1 T1 a Plug the USB cable into the previously identi...

Страница 151: ...ng the USB cable into the system node b Plug the USB cable into the previously identified location in the system control unit by inserting the cable into the connector as shown in the following figure Memory modules 145 ...

Страница 152: ...of the PCIe cables or transceivers that you removed from the PCIe adapters for the system node you are servicing 9 Using your labels reconnect the rear power cords to the system node being serviced as shown in the following figure 146 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 153: ...trol unit UPIC cable locations are P1 C1 T1 and P1 C2 T1 a Ensure that the white plastic lock is pulled back from the plug housing b Plug the UPIC cable A into the previously identified location in the system control unit by inserting the cable into the connector until it locks into place Memory modules 147 ...

Страница 154: ...tached to the system 11 When the service processor comes up to the Flexible Service Processor FSP standby state the power on LED on the control panel is flashing slowly continue to the next step 12 Access the ASMI and run the Cable Plugging Validation utility to validate all of the cables a If you are already connected to the ASMI go to the next step Otherwise click All Systems then select system ...

Страница 155: ...nue The system validates that the cables are installed in the correct locations Expand System Service Aids Cable Plugging Validation to display a table with the results Ensure that the plugging status is OK for each cable in the displayed table If the status is OK no further action is required If the status is not OK review the error logs correct the problems and repeat steps b c and d as needed u...

Страница 156: ...at a time The rack might become unstable if you pull out more than one drawer at a time a Label and disconnect the rear power cords from the system node being serviced as shown in the following figure Notes This system node might be equipped with two or more power supplies If the removing and replacing procedures require the system power to be turned off ensure that all power sources to the system...

Страница 157: ...Figure 130 Removing the rear power cords L003 or or Memory modules 151 ...

Страница 158: ...hazardous voltages disconnect all power cords and power cables L003 b Label and disconnect all of the PCIe cables or transceivers that are attached to the PCIe adapters for the system node you are servicing Use hook and loop fasteners to hold the PCIe cables in place 152 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 159: ...ull tab A attached to the connector Figure 131 Removing the service processor cable from the system node d Label and unplug the UPIC cables for the system node that you are servicing if applicable 1 Remove the white plastic lock A from the plug housing as shown in the following figure Memory modules 153 ...

Страница 160: ...oving the UPIC cable lock 2 Push down on the blue cable latch B and pull out the UPIC cable from the system node as shown in the following figure 154 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 161: ...de e If needed to allow for more slack in the SMP cables label and unclip the SMP cable bundle from the side of the cable management bracket as shown in the following figure and move the SMP cables to near the center of the system node Memory modules 155 ...

Страница 162: ...l connectors are bent or damaged they need to be replaced 1 Slightly push in the cable bundle A as shown in the following figure to relieve the spring pressure of the cable connector 2 Pull the blue latch B as shown in the following figure to release the inner cable latch 3 Remove the SMP cable C from the system node 156 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 163: ... the SMP cables for a system node use hook and loop fasteners to connect the cables to the cable management bracket so the cables do not hang loosely h If you are servicing system node ND1 or ND2 label and unplug the USB cable as shown in the following figure Memory modules 157 ...

Страница 164: ...6 Removing the USB cable from the system node i If present remove the two screws A at the rear of the system as shown in the following figure 158 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 165: ...Figure 137 Removing the rear screws j If present remove the four screws A at the front of the system as shown in the following figure Memory modules 159 ...

Страница 166: ... side latches B for the system node by pressing them downward and then pulling outward as shown in the following figure l Pull out the system node C as shown in the following figure 160 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 167: ...sed for static control It does not increase or decrease your risk of receiving electric shock when using or working on electrical equipment If you do not have an ESD wrist strap just prior to removing the product from ESD packaging and installing or replacing hardware touch an unpainted metal surface of the system for a minimum of 5 seconds If at any point in this service process you move away fro...

Страница 168: ...ess cover 6 To activate the identify LED for the faulty part press and hold either blue push button on the trusted platform module card as shown in the following figure Verify that the green LED A is lit which indicates that sufficient power exists to light the identify LED on the faulty part If the green LED A does not light use the location code on the service label to find the physical location...

Страница 169: ... for the failed memory module Make a note of which location is flashing that indicates the memory module to replace Figure 142 on page 164 shows the locations of the memory module The LEDs are next to the memory module Record the location of the identifying LED Memory modules 163 ...

Страница 170: ...is plugged into a ground jack or connected to an unpainted metal surface If not do so now 2 Note the location of the memory module that you are replacing 3 Remove the memory module by pushing the tabs A down and outward as shown in the following figure The lever action of the tabs forces the memory module out of the connector 164 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 171: ...onnected to an unpainted metal surface If not do so now 2 Use the slot information that you recorded to determine the slot location to place the memory module 3 Grasp the new memory module along its edges and align it with the slot Attention Memory modules are keyed to prevent a memory module from being installed incorrectly Note the location of the key tab within the memory module connector befor...

Страница 172: ... that the ESD clip is plugged into a ground jack or connected to an unpainted metal surface If not do so now 2 Replace the service access cover by completing the following steps a Slide the cover A onto the system unit as shown in the following figure b Close the release latch B by pushing it in the direction shown in the following figure 166 Power Systems Removing and replacing parts in the 9080 ...

Страница 173: ...m node slowly into the rack to ensure that your fingers do not get caught in the side rails a Unlock the blue rail safety latches A by pushing them towards the front as shown in the following figure b Push the system node back into the rack as shown in the following figure until both system node release latches lock into position Memory modules 167 ...

Страница 174: ... system node into the operating position c Replace the two screws A at the rear of the system if you removed them earlier as shown in the following figure 168 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 175: ...Figure 147 Replacing the rear screws d Replace the four screws A at the front of the system node as shown in the following figure Memory modules 169 ...

Страница 176: ...ervicing Then refer to your labels and the following steps to reconnect the SMP cables that you removed from the system node you are servicing If you have a two node system configuration use Figure 149 on page 171 and Table 17 on page 171 to determine the point to point cabling for SMP cables 170 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 177: ...that is shown in the diagram represents a pair of SMP cables Cable Cable type and length From To 5C 880 mm 2 9 ft ND1 P1 T1 ND2 P1 T1 5D 880 mm 2 9 ft ND1 P1 T2 ND2 P1 T2 6C 1005 mm 3 3 ft ND1 P1 T7 ND2 P1 T7 6D 1005 mm 3 3 ft ND1 P1 T8 ND2 P1 T8 5A 1005 mm 3 3 ft ND1 P1 T9 ND2 P1 T9 Memory modules 171 ...

Страница 178: ...17 ND2 P1 T17 6X 1225 mm 4 01 ft ND1 P1 T18 ND2 P1 T18 5W 1005 mm 3 3 ft ND1 P1 T23 ND2 P1 T23 5X 1005 mm 3 3 ft ND1 P1 T24 ND2 P1 T24 6Y 1005 mm 3 3 ft ND1 P1 T25 ND2 P1 T25 6Z 1005 mm 3 3 ft ND1 P1 T26 ND2 P1 T26 5Y 880 mm 2 9 ft ND1 P1 T31 ND2 P1 T31 5Z 880 mm 2 9 ft ND1 P1 T32 ND2 P1 T32 If you have a three node system configuration use Figure 150 on page 173 and Table 18 on page 173 to determ...

Страница 179: ...Figure 150 Cabling a Three Node Configuration Table 18 Cabling a Three Node Configuration Cable Cable type and length From To 5C 880 mm 2 9 ft ND3 P1 T1 ND2 P1 T1 Memory modules 173 ...

Страница 180: ...1 P1 T9 3B 1225 mm 4 01 ft ND3 P1 T16 ND1 P1 T10 3W 1225 mm 4 01 ft ND3 P1 T17 ND1 P1 T23 3X 1225 mm 4 01 ft ND3 P1 T18 ND1 P1 T24 5W 1005 mm 3 3 ft ND3 P1 T23 ND2 P1 T23 5X 1005 mm 3 3 ft ND3 P1 T24 ND2 P1 T24 3Y 1225 mm 4 01 ft ND3 P1 T25 ND1 P1 T31 3Z 1225 mm 4 01 ft ND3 P1 T26 ND1 P1 T32 5Y 880 mm 2 9 ft ND3 P1 T31 ND2 P1 T31 5Z 880 mm 2 9 ft ND3 P1 T32 ND2 P1 T32 6C 1005 mm 3 3 ft ND2 P1 T7 N...

Страница 181: ...D2 P1 T16 ND1 P1 T16 6W 1225 mm 4 01 ft ND2 P1 T17 ND1 P1 T17 6X 1225 mm 4 01 ft ND2 P1 T18 ND1 P1 T18 6Y 1005 mm 3 3 ft ND2 P1 T25 ND1 P1 T25 6Z 1005 mm 3 3 ft ND2 P1 T26 ND1 P1 T26 If you have a four node system configuration use Figure 151 on page 176 and Table 19 on page 177 to determine the point to point cabling for SMP cables Memory modules 175 ...

Страница 182: ...Figure 151 Cabling a Four Node Configuration 176 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 183: ...D 1425 mm 4 7 ft ND4 P1 T8 ND1 P1 T4 2A 1225 mm 4 01 ft ND4 P1 T9 ND2 P1 T11 2B 1225 mm 4 01 ft ND4 P1 T10 ND2 P1 T12 4A 1005 mm 3 3 ft ND4 P1 T11 ND3 P1 T11 4B 1005 mm 3 3 ft ND4 P1 T12 ND3 P1 T12 1A 1625 mm 5 3 ft ND4 P1 T15 ND1 P1 T11 1B 1625 mm 5 3 ft ND4 P1 T16 ND1 P1 T12 1W 1625 mm 5 3 ft ND4 P1 T17 ND1 P1 T21 1X 1625 mm 5 3 ft ND4 P1 T18 ND1 P1 T22 4W 1005 mm 3 3 ft ND4 P1 T21 ND3 P1 T21 4X...

Страница 184: ...D4 P1 T31 ND2 P1 T29 2Z 1225 mm 4 01 ft ND4 P1 T32 ND2 P1 T30 Cables originating on ND3 5C 880 mm 2 9 ft ND3 P1 T1 ND2 P1 T1 5D 880 mm 2 9 ft ND3 P1 T2 ND2 P1 T2 3C 1225 mm 4 01 ft ND3 P1 T7 ND1 P1 T1 3D 1225 mm 4 01 ft ND3 P1 T8 ND1 P1 T2 5A 1005 mm 3 3 ft ND3 P1 T9 ND2 P1 T9 5B 1005 mm 3 3 ft ND3 P1 T10 ND2 P1 T10 3A 1225 mm 4 01 ft ND3 P1 T15 ND1 P1 T9 3B 1225 mm 4 01 ft ND3 P1 T16 ND1 P1 T10 3...

Страница 185: ... ND1 P1 T8 6A 1225 mm 4 01 ft ND2 P1 T15 ND1 P1 T15 6B 1225 mm 4 01 ft ND2 P1 T16 ND1 P1 T16 6W 1225 mm 4 01 ft ND2 P1 T17 ND1 P1 T17 6X 1225 mm 4 01 ft ND2 P1 T18 ND1 P1 T18 6Y 1005 mm 3 3 ft ND2 P1 T25 ND1 P1 T25 6Z 1005 mm 3 3 ft ND2 P1 T26 ND1 P1 T26 a Press the SMP cable and the blue tab together with your fingers and thumb to hold the SMP cable Plug the SMP cable into the previously identifi...

Страница 186: ...ly identified are reconnected to the system node you are servicing c If you removed any SMP cable clips from the side of the rack using your labels reattach the cable bundle to the side of the cable management bracket as shown in the following figure 180 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 187: ...bundles refer to the information card inserted into the rear of the system control unit You can also refer to the following figures The number in the cable label indicates the bundle for that cable Two system node configuration The two system node configuration has four cable bundles Memory modules 181 ...

Страница 188: ...Three system node configuration The three system node configuration has four cable bundles Figure 155 Bundling and connecting SMP cables for three system nodes Two bundles named B3 with the 3 cables The left B3 bundle contains 3A 3B 3C and 3D This bundle attaches to the clip A The right B3 bundle contains 3W 3X 3Y and 3Z This bundle attaches to the clip F Two bundles named B5 with the 5 cables The...

Страница 189: ...e contains 3W 3X 3Y and 3Z This bundle attaches to the clips J Two bundles named B4 with the 4 cables The left B4 bundle contains 4A 4B 4C and 4D This bundle attaches to the clip D The right B4 bundle contains 4W 4X 4Y and 4Z This bundle attaches to the clip G Two bundles named B5 with the 5 cables The left B5 bundle contains 5A 5B 5C and 5D This bundle attaches to the clip E The right B5 bundle c...

Страница 190: ...iguration UPIC Cabling Table 20 Single Node Configuration UPIC Cabling Cable number From To 1 SC1 P1 C1 T1 ND1 P1 C9 T1 2 SC1 P1 C2 T1 ND1 P1 C10 T1 If you have a two three or four node system configuration use Figure 158 on page 185 and Table 21 on page 185 to determine the point to point cabling for UPIC cables 184 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 191: ...C2 T1 ND2 P1 C10 T1 a To replace the UPIC cable in the system node complete the following steps 1 Ensure that the white plastic lock is pulled back from the plug housing 2 Plug the UPIC cable A into the previously identified location in the system node by inserting the cable into the connector until it locks into place as shown in the following figure Memory modules 185 ...

Страница 192: ... 159 Replacing the UPIC cable into the system node 3 Push the white plastic lock B onto the plug housing as shown in the following figure 186 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 193: ... cables should be firmly attached to the system b Repeat step 5 a on page 185 until all the UPIC cables previously identified are reconnected to the system node you are servicing c If applicable secure the cable to the side of the rack with the hook and loop fastener 6 Using your labels reconnect the service processor FSP cables that you removed from the system node you are servicing Memory module...

Страница 194: ...Figure 161 Service processor FSP cabling 188 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 195: ...ttom A 355 mm 1 16 ft SC1 P1 T3 ND1 P1 C9 T2 B 355 mm 1 16 ft SC1 P1 T5 ND1 P1 C10 T2 7 Review the following information to identify the locations where the USB cable connects to the system node that you are servicing and to the system control unit Then reconnect the USB cable that you removed Figure 162 USB Cabling Table 23 USB Cabling From To ND1 or ND2 P1 C13 T3 SC1 P1 T1 a Plug the USB cable i...

Страница 196: ... system node b Plug the USB cable into the previously identified location in the system control unit by inserting the cable into the connector as shown in the following figure 190 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 197: ...our labels reconnect all of the PCIe cables or transceivers that you removed from the PCIe adapters for the system node you are servicing 9 Using your labels reconnect the rear power cords to the system node being serviced as shown in the following figure Memory modules 191 ...

Страница 198: ...tions are P1 C1 T1 and P1 C2 T1 a Ensure that the white plastic lock is pulled back from the plug housing b Plug the UPIC cable A into the previously identified location in the system control unit by inserting the cable into the connector until it locks into place 192 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 199: ...cables should be firmly attached to the system 11 When the service processor comes up to the Flexible Service Processor FSP standby state the power on LED on the control panel is flashing slowly continue to the next step 12 Access the ASMI and run the Cable Plugging Validation utility to validate all of the cables a If you are already connected to the ASMI go to the next step Otherwise click All S...

Страница 200: ...ll cables e Exit the ASMI Permanently removing memory modules Preparing the 9080 M9S system to permanently remove memory modules About this task The following memory configurations are available for the systems The system nodes use DDR4 memory modules DDR3 memory modules are also supported Mixing of DDR3 and DDR4 memory modules are not supported in the same system node For each processor socket a ...

Страница 201: ...fy LED Then click OK to confirm the operation This action causes causes the blue system ID LED to turn on You can also identify the locations for the memory to be installed 2 Open the rear rack door if necessary 3 Label and disconnect both UPIC cables from the system control unit UPIC cable locations are P1 C1 T1 and P1 C2 T1 a Remove the white plastic lock A from the plug housing Figure 168 Remov...

Страница 202: ...at a time The rack might become unstable if you pull out more than one drawer at a time a Label and disconnect the rear power cords from the system node being serviced as shown in the following figure Notes This system node might be equipped with two or more power supplies If the removing and replacing procedures require the system power to be turned off ensure that all power sources to the system...

Страница 203: ...Figure 170 Removing the rear power cords L003 or or Memory modules 197 ...

Страница 204: ...hazardous voltages disconnect all power cords and power cables L003 b Label and disconnect all of the PCIe cables or transceivers that are attached to the PCIe adapters for the system node you are servicing Use hook and loop fasteners to hold the PCIe cables in place 198 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 205: ...ull tab A attached to the connector Figure 171 Removing the service processor cable from the system node d Label and unplug the UPIC cables for the system node that you are servicing if applicable 1 Remove the white plastic lock A from the plug housing as shown in the following figure Memory modules 199 ...

Страница 206: ...oving the UPIC cable lock 2 Push down on the blue cable latch B and pull out the UPIC cable from the system node as shown in the following figure 200 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 207: ...de e If needed to allow for more slack in the SMP cables label and unclip the SMP cable bundle from the side of the cable management bracket as shown in the following figure and move the SMP cables to near the center of the system node Memory modules 201 ...

Страница 208: ...l connectors are bent or damaged they need to be replaced 1 Slightly push in the cable bundle A as shown in the following figure to relieve the spring pressure of the cable connector 2 Pull the blue latch B as shown in the following figure to release the inner cable latch 3 Remove the SMP cable C from the system node 202 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 209: ... the SMP cables for a system node use hook and loop fasteners to connect the cables to the cable management bracket so the cables do not hang loosely h If you are servicing system node ND1 or ND2 label and unplug the USB cable as shown in the following figure Memory modules 203 ...

Страница 210: ...6 Removing the USB cable from the system node i If present remove the two screws A at the rear of the system as shown in the following figure 204 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 211: ...Figure 177 Removing the rear screws j If present remove the four screws A at the front of the system as shown in the following figure Memory modules 205 ...

Страница 212: ... side latches B for the system node by pressing them downward and then pulling outward as shown in the following figure l Pull out the system node C as shown in the following figure 206 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 213: ...sed for static control It does not increase or decrease your risk of receiving electric shock when using or working on electrical equipment If you do not have an ESD wrist strap just prior to removing the product from ESD packaging and installing or replacing hardware touch an unpainted metal surface of the system for a minimum of 5 seconds If at any point in this service process you move away fro...

Страница 214: ...he service access cover 7 To activate the identify LED for the locations for installing the memory modules press and hold either push button on the trusted platform module card as shown in the following figure Verify that the LED A is lit which indicates that sufficient power exists for the identify LED If the LED is not lit use the location code to find the physical location by using the service ...

Страница 215: ...stallation locations Make a note of which locations are flashing they indicate the memory modules to install Figure 182 on page 210 shows the locations of the memory module The LEDs are next to the memory module Record the location of the identifying LED Memory modules 209 ...

Страница 216: ...o a ground jack or connected to an unpainted metal surface If not do so now 2 Use the slot information that you recorded to determine the slot location to remove the memory module 3 Remove the memory module by pushing the tabs A down and outward as shown in the following figure The lever action of the tabs forces the memory module out of the connector 210 Power Systems Removing and replacing parts...

Страница 217: ... pull it out of the system 5 If the removed part is used again place the part on an electrostatic discharge ESD mat 6 Install a memory module filler into the empty slot by pushing it into slot until the tabs A lock into place as shown in the following figure Memory modules 211 ...

Страница 218: ...and that the ESD clip is plugged into a ground jack or connected to an unpainted metal surface If not do so now 2 Replace the service access cover by completing the following steps a Slide the cover A onto the system unit as shown in the following figure b Close the release latch B by pushing it in the direction shown in the following figure 212 Power Systems Removing and replacing parts in the 90...

Страница 219: ...m node slowly into the rack to ensure that your fingers do not get caught in the side rails a Unlock the blue rail safety latches A by pushing them towards the front as shown in the following figure b Push the system node back into the rack as shown in the following figure until both system node release latches lock into position Memory modules 213 ...

Страница 220: ... system node into the operating position c Replace the two screws A at the rear of the system if you removed them earlier as shown in the following figure 214 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 221: ...Figure 187 Replacing the rear screws d Replace the four screws A at the front of the system node as shown in the following figure Memory modules 215 ...

Страница 222: ...ervicing Then refer to your labels and the following steps to reconnect the SMP cables that you removed from the system node you are servicing If you have a two node system configuration use Figure 189 on page 217 and Table 26 on page 217 to determine the point to point cabling for SMP cables 216 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 223: ...that is shown in the diagram represents a pair of SMP cables Cable Cable type and length From To 5C 880 mm 2 9 ft ND1 P1 T1 ND2 P1 T1 5D 880 mm 2 9 ft ND1 P1 T2 ND2 P1 T2 6C 1005 mm 3 3 ft ND1 P1 T7 ND2 P1 T7 6D 1005 mm 3 3 ft ND1 P1 T8 ND2 P1 T8 5A 1005 mm 3 3 ft ND1 P1 T9 ND2 P1 T9 Memory modules 217 ...

Страница 224: ...17 ND2 P1 T17 6X 1225 mm 4 01 ft ND1 P1 T18 ND2 P1 T18 5W 1005 mm 3 3 ft ND1 P1 T23 ND2 P1 T23 5X 1005 mm 3 3 ft ND1 P1 T24 ND2 P1 T24 6Y 1005 mm 3 3 ft ND1 P1 T25 ND2 P1 T25 6Z 1005 mm 3 3 ft ND1 P1 T26 ND2 P1 T26 5Y 880 mm 2 9 ft ND1 P1 T31 ND2 P1 T31 5Z 880 mm 2 9 ft ND1 P1 T32 ND2 P1 T32 If you have a three node system configuration use Figure 190 on page 219 and Table 27 on page 219 to determ...

Страница 225: ...Figure 190 Cabling a Three Node Configuration Table 27 Cabling a Three Node Configuration Cable Cable type and length From To 5C 880 mm 2 9 ft ND3 P1 T1 ND2 P1 T1 Memory modules 219 ...

Страница 226: ...1 P1 T9 3B 1225 mm 4 01 ft ND3 P1 T16 ND1 P1 T10 3W 1225 mm 4 01 ft ND3 P1 T17 ND1 P1 T23 3X 1225 mm 4 01 ft ND3 P1 T18 ND1 P1 T24 5W 1005 mm 3 3 ft ND3 P1 T23 ND2 P1 T23 5X 1005 mm 3 3 ft ND3 P1 T24 ND2 P1 T24 3Y 1225 mm 4 01 ft ND3 P1 T25 ND1 P1 T31 3Z 1225 mm 4 01 ft ND3 P1 T26 ND1 P1 T32 5Y 880 mm 2 9 ft ND3 P1 T31 ND2 P1 T31 5Z 880 mm 2 9 ft ND3 P1 T32 ND2 P1 T32 6C 1005 mm 3 3 ft ND2 P1 T7 N...

Страница 227: ...D2 P1 T16 ND1 P1 T16 6W 1225 mm 4 01 ft ND2 P1 T17 ND1 P1 T17 6X 1225 mm 4 01 ft ND2 P1 T18 ND1 P1 T18 6Y 1005 mm 3 3 ft ND2 P1 T25 ND1 P1 T25 6Z 1005 mm 3 3 ft ND2 P1 T26 ND1 P1 T26 If you have a four node system configuration use Figure 191 on page 222 and Table 28 on page 223 to determine the point to point cabling for SMP cables Memory modules 221 ...

Страница 228: ...Figure 191 Cabling a Four Node Configuration 222 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 229: ...D 1425 mm 4 7 ft ND4 P1 T8 ND1 P1 T4 2A 1225 mm 4 01 ft ND4 P1 T9 ND2 P1 T11 2B 1225 mm 4 01 ft ND4 P1 T10 ND2 P1 T12 4A 1005 mm 3 3 ft ND4 P1 T11 ND3 P1 T11 4B 1005 mm 3 3 ft ND4 P1 T12 ND3 P1 T12 1A 1625 mm 5 3 ft ND4 P1 T15 ND1 P1 T11 1B 1625 mm 5 3 ft ND4 P1 T16 ND1 P1 T12 1W 1625 mm 5 3 ft ND4 P1 T17 ND1 P1 T21 1X 1625 mm 5 3 ft ND4 P1 T18 ND1 P1 T22 4W 1005 mm 3 3 ft ND4 P1 T21 ND3 P1 T21 4X...

Страница 230: ...D4 P1 T31 ND2 P1 T29 2Z 1225 mm 4 01 ft ND4 P1 T32 ND2 P1 T30 Cables originating on ND3 5C 880 mm 2 9 ft ND3 P1 T1 ND2 P1 T1 5D 880 mm 2 9 ft ND3 P1 T2 ND2 P1 T2 3C 1225 mm 4 01 ft ND3 P1 T7 ND1 P1 T1 3D 1225 mm 4 01 ft ND3 P1 T8 ND1 P1 T2 5A 1005 mm 3 3 ft ND3 P1 T9 ND2 P1 T9 5B 1005 mm 3 3 ft ND3 P1 T10 ND2 P1 T10 3A 1225 mm 4 01 ft ND3 P1 T15 ND1 P1 T9 3B 1225 mm 4 01 ft ND3 P1 T16 ND1 P1 T10 3...

Страница 231: ... ND1 P1 T8 6A 1225 mm 4 01 ft ND2 P1 T15 ND1 P1 T15 6B 1225 mm 4 01 ft ND2 P1 T16 ND1 P1 T16 6W 1225 mm 4 01 ft ND2 P1 T17 ND1 P1 T17 6X 1225 mm 4 01 ft ND2 P1 T18 ND1 P1 T18 6Y 1005 mm 3 3 ft ND2 P1 T25 ND1 P1 T25 6Z 1005 mm 3 3 ft ND2 P1 T26 ND1 P1 T26 a Press the SMP cable and the blue tab together with your fingers and thumb to hold the SMP cable Plug the SMP cable into the previously identifi...

Страница 232: ...ly identified are reconnected to the system node you are servicing c If you removed any SMP cable clips from the side of the rack using your labels reattach the cable bundle to the side of the cable management bracket as shown in the following figure 226 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 233: ...bundles refer to the information card inserted into the rear of the system control unit You can also refer to the following figures The number in the cable label indicates the bundle for that cable Two system node configuration The two system node configuration has four cable bundles Memory modules 227 ...

Страница 234: ...Three system node configuration The three system node configuration has four cable bundles Figure 195 Bundling and connecting SMP cables for three system nodes Two bundles named B3 with the 3 cables The left B3 bundle contains 3A 3B 3C and 3D This bundle attaches to the clip A The right B3 bundle contains 3W 3X 3Y and 3Z This bundle attaches to the clip F Two bundles named B5 with the 5 cables The...

Страница 235: ...e contains 3W 3X 3Y and 3Z This bundle attaches to the clips J Two bundles named B4 with the 4 cables The left B4 bundle contains 4A 4B 4C and 4D This bundle attaches to the clip D The right B4 bundle contains 4W 4X 4Y and 4Z This bundle attaches to the clip G Two bundles named B5 with the 5 cables The left B5 bundle contains 5A 5B 5C and 5D This bundle attaches to the clip E The right B5 bundle c...

Страница 236: ...iguration UPIC Cabling Table 29 Single Node Configuration UPIC Cabling Cable number From To 1 SC1 P1 C1 T1 ND1 P1 C9 T1 2 SC1 P1 C2 T1 ND1 P1 C10 T1 If you have a two three or four node system configuration use Figure 198 on page 231 and Table 30 on page 231 to determine the point to point cabling for UPIC cables 230 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 237: ...C2 T1 ND2 P1 C10 T1 a To replace the UPIC cable in the system node complete the following steps 1 Ensure that the white plastic lock is pulled back from the plug housing 2 Plug the UPIC cable A into the previously identified location in the system node by inserting the cable into the connector until it locks into place as shown in the following figure Memory modules 231 ...

Страница 238: ... 199 Replacing the UPIC cable into the system node 3 Push the white plastic lock B onto the plug housing as shown in the following figure 232 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 239: ... cables should be firmly attached to the system b Repeat step 5 a on page 231 until all the UPIC cables previously identified are reconnected to the system node you are servicing c If applicable secure the cable to the side of the rack with the hook and loop fastener 6 Using your labels reconnect the service processor FSP cables that you removed from the system node you are servicing Memory module...

Страница 240: ...Figure 201 Service processor FSP cabling 234 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 241: ...ttom A 355 mm 1 16 ft SC1 P1 T3 ND1 P1 C9 T2 B 355 mm 1 16 ft SC1 P1 T5 ND1 P1 C10 T2 7 Review the following information to identify the locations where the USB cable connects to the system node that you are servicing and to the system control unit Then reconnect the USB cable that you removed Figure 202 USB Cabling Table 32 USB Cabling From To ND1 or ND2 P1 C13 T3 SC1 P1 T1 a Plug the USB cable i...

Страница 242: ... system node b Plug the USB cable into the previously identified location in the system control unit by inserting the cable into the connector as shown in the following figure 236 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 243: ...our labels reconnect all of the PCIe cables or transceivers that you removed from the PCIe adapters for the system node you are servicing 9 Using your labels reconnect the rear power cords to the system node being serviced as shown in the following figure Memory modules 237 ...

Страница 244: ...tions are P1 C1 T1 and P1 C2 T1 a Ensure that the white plastic lock is pulled back from the plug housing b Plug the UPIC cable A into the previously identified location in the system control unit by inserting the cable into the connector until it locks into place 238 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 245: ...cables should be firmly attached to the system 11 When the service processor comes up to the Flexible Service Processor FSP standby state the power on LED on the control panel is flashing slowly continue to the next step 12 Access the ASMI and run the Cable Plugging Validation utility to validate all of the cables a If you are already connected to the ASMI go to the next step Otherwise click All S...

Страница 246: ...EDs do not light up in sequence the FSP cables need to be re installed d Expand System Service Aids Cable Plugging Validation Then select All of the above in the Display Cable Status section and click Continue The system validates that the cables are installed in the correct locations Expand System Service Aids Cable Plugging Validation to display a table with the results Ensure that the plugging ...

Страница 247: ...LED on the enclosure to locate the system Ensure that the serial number of the system matches the serial number to be serviced 2 Stop the system For instructions see Stopping a system www ibm com support knowledgecenter POWER9 p9haj crustopsys htm 3 Open the rear rack door if necessary 4 Label and disconnect both UPIC cables from the system control unit UPIC cable locations are P1 C1 T1 and P1 C2 ...

Страница 248: ...eiving electric shock when using or working on electrical equipment If you do not have an ESD wrist strap just prior to removing the product from ESD packaging and installing or replacing hardware touch an unpainted metal surface of the system for a minimum of 5 seconds If at any point in this service process you move away from the system it is important to again discharge yourself by touching an ...

Страница 249: ... following figure Notes This system node might be equipped with two or more power supplies If the removing and replacing procedures require the system power to be turned off ensure that all power sources to the system node are disconnected Figure 210 Removing the rear power cords Memory VRMs 243 ...

Страница 250: ... L003 or or or or 244 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 251: ... and power cables L003 b Label and disconnect all of the PCIe cables or transceivers that are attached to the PCIe adapters for the system node you are servicing Use hook and loop fasteners to hold the PCIe cables in place c Label and unplug both service processor FSP cables B from the system node being serviced using the pull tab A attached to the connector Memory VRMs 245 ...

Страница 252: ...stem node d Label and unplug the UPIC cables for the system node that you are servicing if applicable 1 Remove the white plastic lock A from the plug housing as shown in the following figure 246 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 253: ...Figure 212 Removing the UPIC cable lock 2 Push down on the blue cable latch B and pull out the UPIC cable from the system node as shown in the following figure Memory VRMs 247 ...

Страница 254: ...or more slack in the SMP cables label and unclip the SMP cable bundle from the side of the cable management bracket as shown in the following figure and move the SMP cables to near the center of the system node 248 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 255: ...rs on the cable If the metal connectors are bent or damaged they need to be replaced 1 Slightly push in the cable bundle A as shown in the following figure to relieve the spring pressure of the cable connector 2 Pull the blue latch B as shown in the following figure to release the inner cable latch 3 Remove the SMP cable C from the system node Memory VRMs 249 ...

Страница 256: ...tem node use hook and loop fasteners to connect the cables to the cable management bracket so the cables do not hang loosely h If you are servicing system node ND1 or ND2 label and unplug the USB cable as shown in the following figure 250 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 257: ...Figure 216 Removing the USB cable from the system node i If present remove the two screws A at the rear of the system as shown in the following figure Memory VRMs 251 ...

Страница 258: ...igure 217 Removing the rear screws j If present remove the four screws A at the front of the system as shown in the following figure 252 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 259: ... front screws k Release the side latches B for the system node by pressing them downward and then pulling outward as shown in the following figure l Pull out the system node C as shown in the following figure Memory VRMs 253 ...

Страница 260: ...For proper cooling and airflow replace the cover before turning on the system a Push the release latch A in the direction shown in the following figure b Slide the cover B off the system unit as shown in the following figure When the service access cover has cleared the upper frame ledge lift the cover up and off the system unit 254 Power Systems Removing and replacing parts in the 9080 M9S system...

Страница 261: ... on the trusted platform module card as shown in the following figure Verify that the green LED A is lit which indicates that sufficient power exists to light the identify LED on the faulty part If the green LED A does not light use the location code on the service label to find the physical location of the faulty part Memory VRMs 255 ...

Страница 262: ...lashing amber LED of the faulty or failed memory voltage regulator module Memory voltage regulator module are in locations P1 C54 P1 C55 P1 C57 P1 C58 P1 C64 P1 C67 and P1 C68 Refer to the following image 256 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 263: ...rostatic discharge ESD wrist strap on and that the ESD clip is plugged into a ground jack or connected to an unpainted metal surface If not do so now 2 Remove a memory voltage regulator module by completing the following steps a Unlock the levers A to release the voltage regulator module from its connector Refer to the following image b Rotate the levers in the direction shown c While holding the ...

Страница 264: ...n unpainted metal surface If not do so now 2 To replace a memory voltage regulator module complete the following steps a With the levers A in the open position hold the voltage regulator module by its levers and lower the voltage regulator module into its slot in the system Refer to the following image b Gently push the voltage regulator module into its connector c Rotate the levers in the directi...

Страница 265: ...e steps in this procedure Procedure 1 Ensure that you have the electrostatic discharge ESD wrist strap on and that the ESD clip is plugged into a ground jack or connected to an unpainted metal surface If not do so now 2 Replace the service access cover by completing the following steps a Slide the cover A onto the system unit as shown in the following figure b Close the release latch B by pushing ...

Страница 266: ...ck to ensure that your fingers do not get caught in the side rails a Unlock the blue rail safety latches A by pushing them towards the front as shown in the following figure b Push the system node back into the rack as shown in the following figure until both system node release latches lock into position 260 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 267: ...Figure 226 Placing the system node into the operating position c Replace the two screws A at the rear of the system if you removed them earlier as shown in the following figure Memory VRMs 261 ...

Страница 268: ...Figure 227 Replacing the rear screws d Replace the four screws A at the front of the system node as shown in the following figure 262 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 269: ... system node that you are servicing Then refer to your labels and the following steps to reconnect the SMP cables that you removed from the system node you are servicing If you have a two node system configuration use Figure 229 on page 264 and Table 33 on page 264 to determine the point to point cabling for SMP cables Memory VRMs 263 ...

Страница 270: ...ram represents a pair of SMP cables Cable Cable type and length From To 5C 880 mm 2 9 ft ND1 P1 T1 ND2 P1 T1 5D 880 mm 2 9 ft ND1 P1 T2 ND2 P1 T2 6C 1005 mm 3 3 ft ND1 P1 T7 ND2 P1 T7 6D 1005 mm 3 3 ft ND1 P1 T8 ND2 P1 T8 5A 1005 mm 3 3 ft ND1 P1 T9 ND2 P1 T9 264 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 271: ...6W 1225 mm 4 01 ft ND1 P1 T17 ND2 P1 T17 6X 1225 mm 4 01 ft ND1 P1 T18 ND2 P1 T18 5W 1005 mm 3 3 ft ND1 P1 T23 ND2 P1 T23 5X 1005 mm 3 3 ft ND1 P1 T24 ND2 P1 T24 6Y 1005 mm 3 3 ft ND1 P1 T25 ND2 P1 T25 6Z 1005 mm 3 3 ft ND1 P1 T26 ND2 P1 T26 5Y 880 mm 2 9 ft ND1 P1 T31 ND2 P1 T31 5Z 880 mm 2 9 ft ND1 P1 T32 ND2 P1 T32 If you have a three node system configuration use Figure 230 on page 266 and Tab...

Страница 272: ...ing a Three Node Configuration Table 34 Cabling a Three Node Configuration Cable Cable type and length From To 5C 880 mm 2 9 ft ND3 P1 T1 ND2 P1 T1 266 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 273: ...25 mm 4 01 ft ND3 P1 T15 ND1 P1 T9 3B 1225 mm 4 01 ft ND3 P1 T16 ND1 P1 T10 3W 1225 mm 4 01 ft ND3 P1 T17 ND1 P1 T23 3X 1225 mm 4 01 ft ND3 P1 T18 ND1 P1 T24 5W 1005 mm 3 3 ft ND3 P1 T23 ND2 P1 T23 5X 1005 mm 3 3 ft ND3 P1 T24 ND2 P1 T24 3Y 1225 mm 4 01 ft ND3 P1 T25 ND1 P1 T31 3Z 1225 mm 4 01 ft ND3 P1 T26 ND1 P1 T32 5Y 880 mm 2 9 ft ND3 P1 T31 ND2 P1 T31 5Z 880 mm 2 9 ft ND3 P1 T32 ND2 P1 T32 6C...

Страница 274: ...25 mm 4 01 ft ND2 P1 T17 ND1 P1 T17 6X 1225 mm 4 01 ft ND2 P1 T18 ND1 P1 T18 6Y 1005 mm 3 3 ft ND2 P1 T25 ND1 P1 T25 6Z 1005 mm 3 3 ft ND2 P1 T26 ND1 P1 T26 If you have a four node system configuration use Figure 231 on page 269 and Table 35 on page 270 to determine the point to point cabling for SMP cables 268 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 275: ...Figure 231 Cabling a Four Node Configuration Memory VRMs 269 ...

Страница 276: ...8 ND1 P1 T4 2A 1225 mm 4 01 ft ND4 P1 T9 ND2 P1 T11 2B 1225 mm 4 01 ft ND4 P1 T10 ND2 P1 T12 4A 1005 mm 3 3 ft ND4 P1 T11 ND3 P1 T11 4B 1005 mm 3 3 ft ND4 P1 T12 ND3 P1 T12 1A 1625 mm 5 3 ft ND4 P1 T15 ND1 P1 T11 1B 1625 mm 5 3 ft ND4 P1 T16 ND1 P1 T12 1W 1625 mm 5 3 ft ND4 P1 T17 ND1 P1 T21 1X 1625 mm 5 3 ft ND4 P1 T18 ND1 P1 T22 4W 1005 mm 3 3 ft ND4 P1 T21 ND3 P1 T21 4X 1005 mm 3 3 ft ND4 P1 T2...

Страница 277: ...P1 T30 2Y 1225 mm 4 01 ft ND4 P1 T31 ND2 P1 T29 2Z 1225 mm 4 01 ft ND4 P1 T32 ND2 P1 T30 Cables originating on ND3 5C 880 mm 2 9 ft ND3 P1 T1 ND2 P1 T1 5D 880 mm 2 9 ft ND3 P1 T2 ND2 P1 T2 3C 1225 mm 4 01 ft ND3 P1 T7 ND1 P1 T1 3D 1225 mm 4 01 ft ND3 P1 T8 ND1 P1 T2 5A 1005 mm 3 3 ft ND3 P1 T9 ND2 P1 T9 5B 1005 mm 3 3 ft ND3 P1 T10 ND2 P1 T10 3A 1225 mm 4 01 ft ND3 P1 T15 ND1 P1 T9 3B 1225 mm 4 01...

Страница 278: ...1 ft ND2 P1 T15 ND1 P1 T15 6B 1225 mm 4 01 ft ND2 P1 T16 ND1 P1 T16 6W 1225 mm 4 01 ft ND2 P1 T17 ND1 P1 T17 6X 1225 mm 4 01 ft ND2 P1 T18 ND1 P1 T18 6Y 1005 mm 3 3 ft ND2 P1 T25 ND1 P1 T25 6Z 1005 mm 3 3 ft ND2 P1 T26 ND1 P1 T26 a Press the SMP cable and the blue tab together with your fingers and thumb to hold the SMP cable Plug the SMP cable into the previously identified location in the system...

Страница 279: ...all the SMP cables previously identified are reconnected to the system node you are servicing c If you removed any SMP cable clips from the side of the rack using your labels reattach the cable bundle to the side of the cable management bracket as shown in the following figure Memory VRMs 273 ...

Страница 280: ...rmation card inserted into the rear of the system control unit You can also refer to the following figures The number in the cable label indicates the bundle for that cable Two system node configuration The two system node configuration has four cable bundles 274 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 281: ...dle attaches to the clip C Three system node configuration The three system node configuration has four cable bundles Figure 235 Bundling and connecting SMP cables for three system nodes Two bundles named B3 with the 3 cables The left B3 bundle contains 3A 3B 3C and 3D This bundle attaches to the clip A The right B3 bundle contains 3W 3X 3Y and 3Z This bundle attaches to the clip F Two bundles nam...

Страница 282: ... This bundle attaches to the clips J Two bundles named B4 with the 4 cables The left B4 bundle contains 4A 4B 4C and 4D This bundle attaches to the clip D The right B4 bundle contains 4W 4X 4Y and 4Z This bundle attaches to the clip G Two bundles named B5 with the 5 cables The left B5 bundle contains 5A 5B 5C and 5D This bundle attaches to the clip E The right B5 bundle contains 5W 5X 5Y and 5Z Th...

Страница 283: ...Figure 237 Single Node Configuration UPIC Cabling Table 36 Single Node Configuration UPIC Cabling Cable number From To 1 SC1 P1 C1 T1 ND1 P1 C9 T1 2 SC1 P1 C2 T1 ND1 P1 C10 T1 If you have a two three or four node system configuration use Figure 238 on page 278 and Table 37 on page 278 to determine the point to point cabling for UPIC cables Memory VRMs 277 ...

Страница 284: ...replace the UPIC cable in the system node complete the following steps 1 Ensure that the white plastic lock is pulled back from the plug housing 2 Plug the UPIC cable A into the previously identified location in the system node by inserting the cable into the connector until it locks into place as shown in the following figure 278 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 285: ...Figure 239 Replacing the UPIC cable into the system node 3 Push the white plastic lock B onto the plug housing as shown in the following figure Memory VRMs 279 ...

Страница 286: ...attached to the system b Repeat step 5 a on page 278 until all the UPIC cables previously identified are reconnected to the system node you are servicing c If applicable secure the cable to the side of the rack with the hook and loop fastener 6 Using your labels reconnect the service processor FSP cables that you removed from the system node you are servicing 280 Power Systems Removing and replaci...

Страница 287: ...Figure 241 Service processor FSP cabling Memory VRMs 281 ...

Страница 288: ... P1 T3 ND1 P1 C9 T2 B 355 mm 1 16 ft SC1 P1 T5 ND1 P1 C10 T2 7 Review the following information to identify the locations where the USB cable connects to the system node that you are servicing and to the system control unit Then reconnect the USB cable that you removed Figure 242 USB Cabling Table 39 USB Cabling From To ND1 or ND2 P1 C13 T3 SC1 P1 T1 a Plug the USB cable into the previously identi...

Страница 289: ...cing the USB cable into the system node b Plug the USB cable into the previously identified location in the system control unit by inserting the cable into the connector as shown in the following figure Memory VRMs 283 ...

Страница 290: ...USB cable into the system control unit 8 Using your labels reconnect the rear power cords to the system node being serviced as shown in the following figure 284 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 291: ...ntrol unit UPIC cable locations are P1 C1 T1 and P1 C2 T1 a Ensure that the white plastic lock is pulled back from the plug housing b Plug the UPIC cable A into the previously identified location in the system control unit by inserting the cable into the connector until it locks into place Memory VRMs 285 ...

Страница 292: ...tached to the system 10 When the service processor comes up to the Flexible Service Processor FSP standby state the power on LED on the control panel is flashing slowly continue to the next step 11 Access the ASMI and run the Cable Plugging Validation utility to validate all of the cables a If you are already connected to the ASMI go to the next step Otherwise click All Systems then select system ...

Страница 293: ...Validation Then select All of the above in the Display Cable Status section and click Continue The system validates that the cables are installed in the correct locations Expand System Service Aids Cable Plugging Validation to display a table with the results Ensure that the plugging status is OK for each cable in the displayed table If the status is OK no further action is required If the status ...

Страница 294: ...288 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 295: ...lue identify LED on the enclosure to locate the system Ensure that the serial number of the system matches the serial number to be serviced 2 Stop the system For instructions see Stopping a system www ibm com support knowledgecenter POWER9 p9haj crustopsys htm 3 Open the rear rack door if necessary 4 Label and disconnect both UPIC cables from the system control unit UPIC cable locations are P1 C1 ...

Страница 296: ...eiving electric shock when using or working on electrical equipment If you do not have an ESD wrist strap just prior to removing the product from ESD packaging and installing or replacing hardware touch an unpainted metal surface of the system for a minimum of 5 seconds If at any point in this service process you move away from the system it is important to again discharge yourself by touching an ...

Страница 297: ...llowing figure Notes This system node might be equipped with two or more power supplies If the removing and replacing procedures require the system power to be turned off ensure that all power sources to the system node are disconnected Figure 250 Removing the rear power cords Miscellaneous VRMs 291 ...

Страница 298: ... L003 or or or or 292 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 299: ... power cables L003 b Label and disconnect all of the PCIe cables or transceivers that are attached to the PCIe adapters for the system node you are servicing Use hook and loop fasteners to hold the PCIe cables in place c Label and unplug both service processor FSP cables B from the system node being serviced using the pull tab A attached to the connector Miscellaneous VRMs 293 ...

Страница 300: ...stem node d Label and unplug the UPIC cables for the system node that you are servicing if applicable 1 Remove the white plastic lock A from the plug housing as shown in the following figure 294 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 301: ...Figure 252 Removing the UPIC cable lock 2 Push down on the blue cable latch B and pull out the UPIC cable from the system node as shown in the following figure Miscellaneous VRMs 295 ...

Страница 302: ...or more slack in the SMP cables label and unclip the SMP cable bundle from the side of the cable management bracket as shown in the following figure and move the SMP cables to near the center of the system node 296 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 303: ...on the cable If the metal connectors are bent or damaged they need to be replaced 1 Slightly push in the cable bundle A as shown in the following figure to relieve the spring pressure of the cable connector 2 Pull the blue latch B as shown in the following figure to release the inner cable latch 3 Remove the SMP cable C from the system node Miscellaneous VRMs 297 ...

Страница 304: ...tem node use hook and loop fasteners to connect the cables to the cable management bracket so the cables do not hang loosely h If you are servicing system node ND1 or ND2 label and unplug the USB cable as shown in the following figure 298 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 305: ...Figure 256 Removing the USB cable from the system node i If present remove the two screws A at the rear of the system as shown in the following figure Miscellaneous VRMs 299 ...

Страница 306: ...igure 257 Removing the rear screws j If present remove the four screws A at the front of the system as shown in the following figure 300 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 307: ...ont screws k Release the side latches B for the system node by pressing them downward and then pulling outward as shown in the following figure l Pull out the system node C as shown in the following figure Miscellaneous VRMs 301 ...

Страница 308: ...For proper cooling and airflow replace the cover before turning on the system a Push the release latch A in the direction shown in the following figure b Slide the cover B off the system unit as shown in the following figure When the service access cover has cleared the upper frame ledge lift the cover up and off the system unit 302 Power Systems Removing and replacing parts in the 9080 M9S system...

Страница 309: ...the trusted platform module card as shown in the following figure Verify that the green LED A is lit which indicates that sufficient power exists to light the identify LED on the faulty part If the green LED A does not light use the location code on the service label to find the physical location of the faulty part Miscellaneous VRMs 303 ...

Страница 310: ...flashing amber LED of the faulty or failed miscellaneous A voltage regulator module Miscellaneous A voltage regulator modules are in locations P1 C56 P1 C60 P1 C65 and P1 C66 Refer to the following image 304 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 311: ... electrostatic discharge ESD wrist strap on and that the ESD clip is plugged into a ground jack or connected to an unpainted metal surface If not do so now 2 Remove a miscellaneous A voltage regulator module by completing the following steps a Unlock the levers A to release the voltage regulator module from its connector Refer to the following image b Rotate the levers in the direction shown c Whi...

Страница 312: ...cted to an unpainted metal surface If not do so now 2 To replace a miscellaneous A voltage regulator module complete the following steps a With the levers A in the open position hold the voltage regulator module by its levers and lower the voltage regulator module into its slot in the system Refer to the following image b Gently push the voltage regulator module into its connector c Rotate the lev...

Страница 313: ...omplete the steps in this procedure Procedure 1 Ensure that you have the electrostatic discharge ESD wrist strap on and that the ESD clip is plugged into a ground jack or connected to an unpainted metal surface If not do so now 2 Replace the service access cover by completing the following steps a Slide the cover A onto the system unit as shown in the following figure b Close the release latch B b...

Страница 314: ...ck to ensure that your fingers do not get caught in the side rails a Unlock the blue rail safety latches A by pushing them towards the front as shown in the following figure b Push the system node back into the rack as shown in the following figure until both system node release latches lock into position 308 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 315: ...Figure 266 Placing the system node into the operating position c Replace the two screws A at the rear of the system if you removed them earlier as shown in the following figure Miscellaneous VRMs 309 ...

Страница 316: ...Figure 267 Replacing the rear screws d Replace the four screws A at the front of the system node as shown in the following figure 310 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 317: ...stem node that you are servicing Then refer to your labels and the following steps to reconnect the SMP cables that you removed from the system node you are servicing If you have a two node system configuration use Figure 269 on page 312 and Table 40 on page 312 to determine the point to point cabling for SMP cables Miscellaneous VRMs 311 ...

Страница 318: ...ram represents a pair of SMP cables Cable Cable type and length From To 5C 880 mm 2 9 ft ND1 P1 T1 ND2 P1 T1 5D 880 mm 2 9 ft ND1 P1 T2 ND2 P1 T2 6C 1005 mm 3 3 ft ND1 P1 T7 ND2 P1 T7 6D 1005 mm 3 3 ft ND1 P1 T8 ND2 P1 T8 5A 1005 mm 3 3 ft ND1 P1 T9 ND2 P1 T9 312 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 319: ...1225 mm 4 01 ft ND1 P1 T17 ND2 P1 T17 6X 1225 mm 4 01 ft ND1 P1 T18 ND2 P1 T18 5W 1005 mm 3 3 ft ND1 P1 T23 ND2 P1 T23 5X 1005 mm 3 3 ft ND1 P1 T24 ND2 P1 T24 6Y 1005 mm 3 3 ft ND1 P1 T25 ND2 P1 T25 6Z 1005 mm 3 3 ft ND1 P1 T26 ND2 P1 T26 5Y 880 mm 2 9 ft ND1 P1 T31 ND2 P1 T31 5Z 880 mm 2 9 ft ND1 P1 T32 ND2 P1 T32 If you have a three node system configuration use Figure 270 on page 314 and Table ...

Страница 320: ...ing a Three Node Configuration Table 41 Cabling a Three Node Configuration Cable Cable type and length From To 5C 880 mm 2 9 ft ND3 P1 T1 ND2 P1 T1 314 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 321: ...mm 4 01 ft ND3 P1 T15 ND1 P1 T9 3B 1225 mm 4 01 ft ND3 P1 T16 ND1 P1 T10 3W 1225 mm 4 01 ft ND3 P1 T17 ND1 P1 T23 3X 1225 mm 4 01 ft ND3 P1 T18 ND1 P1 T24 5W 1005 mm 3 3 ft ND3 P1 T23 ND2 P1 T23 5X 1005 mm 3 3 ft ND3 P1 T24 ND2 P1 T24 3Y 1225 mm 4 01 ft ND3 P1 T25 ND1 P1 T31 3Z 1225 mm 4 01 ft ND3 P1 T26 ND1 P1 T32 5Y 880 mm 2 9 ft ND3 P1 T31 ND2 P1 T31 5Z 880 mm 2 9 ft ND3 P1 T32 ND2 P1 T32 6C 10...

Страница 322: ...25 mm 4 01 ft ND2 P1 T17 ND1 P1 T17 6X 1225 mm 4 01 ft ND2 P1 T18 ND1 P1 T18 6Y 1005 mm 3 3 ft ND2 P1 T25 ND1 P1 T25 6Z 1005 mm 3 3 ft ND2 P1 T26 ND1 P1 T26 If you have a four node system configuration use Figure 271 on page 317 and Table 42 on page 318 to determine the point to point cabling for SMP cables 316 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 323: ...Figure 271 Cabling a Four Node Configuration Miscellaneous VRMs 317 ...

Страница 324: ...8 ND1 P1 T4 2A 1225 mm 4 01 ft ND4 P1 T9 ND2 P1 T11 2B 1225 mm 4 01 ft ND4 P1 T10 ND2 P1 T12 4A 1005 mm 3 3 ft ND4 P1 T11 ND3 P1 T11 4B 1005 mm 3 3 ft ND4 P1 T12 ND3 P1 T12 1A 1625 mm 5 3 ft ND4 P1 T15 ND1 P1 T11 1B 1625 mm 5 3 ft ND4 P1 T16 ND1 P1 T12 1W 1625 mm 5 3 ft ND4 P1 T17 ND1 P1 T21 1X 1625 mm 5 3 ft ND4 P1 T18 ND1 P1 T22 4W 1005 mm 3 3 ft ND4 P1 T21 ND3 P1 T21 4X 1005 mm 3 3 ft ND4 P1 T2...

Страница 325: ...T30 2Y 1225 mm 4 01 ft ND4 P1 T31 ND2 P1 T29 2Z 1225 mm 4 01 ft ND4 P1 T32 ND2 P1 T30 Cables originating on ND3 5C 880 mm 2 9 ft ND3 P1 T1 ND2 P1 T1 5D 880 mm 2 9 ft ND3 P1 T2 ND2 P1 T2 3C 1225 mm 4 01 ft ND3 P1 T7 ND1 P1 T1 3D 1225 mm 4 01 ft ND3 P1 T8 ND1 P1 T2 5A 1005 mm 3 3 ft ND3 P1 T9 ND2 P1 T9 5B 1005 mm 3 3 ft ND3 P1 T10 ND2 P1 T10 3A 1225 mm 4 01 ft ND3 P1 T15 ND1 P1 T9 3B 1225 mm 4 01 ft...

Страница 326: ...1 ft ND2 P1 T15 ND1 P1 T15 6B 1225 mm 4 01 ft ND2 P1 T16 ND1 P1 T16 6W 1225 mm 4 01 ft ND2 P1 T17 ND1 P1 T17 6X 1225 mm 4 01 ft ND2 P1 T18 ND1 P1 T18 6Y 1005 mm 3 3 ft ND2 P1 T25 ND1 P1 T25 6Z 1005 mm 3 3 ft ND2 P1 T26 ND1 P1 T26 a Press the SMP cable and the blue tab together with your fingers and thumb to hold the SMP cable Plug the SMP cable into the previously identified location in the system...

Страница 327: ... the SMP cables previously identified are reconnected to the system node you are servicing c If you removed any SMP cable clips from the side of the rack using your labels reattach the cable bundle to the side of the cable management bracket as shown in the following figure Miscellaneous VRMs 321 ...

Страница 328: ...rmation card inserted into the rear of the system control unit You can also refer to the following figures The number in the cable label indicates the bundle for that cable Two system node configuration The two system node configuration has four cable bundles 322 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 329: ...attaches to the clip C Three system node configuration The three system node configuration has four cable bundles Figure 275 Bundling and connecting SMP cables for three system nodes Two bundles named B3 with the 3 cables The left B3 bundle contains 3A 3B 3C and 3D This bundle attaches to the clip A The right B3 bundle contains 3W 3X 3Y and 3Z This bundle attaches to the clip F Two bundles named B...

Страница 330: ... This bundle attaches to the clips J Two bundles named B4 with the 4 cables The left B4 bundle contains 4A 4B 4C and 4D This bundle attaches to the clip D The right B4 bundle contains 4W 4X 4Y and 4Z This bundle attaches to the clip G Two bundles named B5 with the 5 cables The left B5 bundle contains 5A 5B 5C and 5D This bundle attaches to the clip E The right B5 bundle contains 5W 5X 5Y and 5Z Th...

Страница 331: ...ure 277 Single Node Configuration UPIC Cabling Table 43 Single Node Configuration UPIC Cabling Cable number From To 1 SC1 P1 C1 T1 ND1 P1 C9 T1 2 SC1 P1 C2 T1 ND1 P1 C10 T1 If you have a two three or four node system configuration use Figure 278 on page 326 and Table 44 on page 326 to determine the point to point cabling for UPIC cables Miscellaneous VRMs 325 ...

Страница 332: ...replace the UPIC cable in the system node complete the following steps 1 Ensure that the white plastic lock is pulled back from the plug housing 2 Plug the UPIC cable A into the previously identified location in the system node by inserting the cable into the connector until it locks into place as shown in the following figure 326 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 333: ...Figure 279 Replacing the UPIC cable into the system node 3 Push the white plastic lock B onto the plug housing as shown in the following figure Miscellaneous VRMs 327 ...

Страница 334: ...attached to the system b Repeat step 5 a on page 326 until all the UPIC cables previously identified are reconnected to the system node you are servicing c If applicable secure the cable to the side of the rack with the hook and loop fastener 6 Using your labels reconnect the service processor FSP cables that you removed from the system node you are servicing 328 Power Systems Removing and replaci...

Страница 335: ...Figure 281 Service processor FSP cabling Miscellaneous VRMs 329 ...

Страница 336: ... P1 T3 ND1 P1 C9 T2 B 355 mm 1 16 ft SC1 P1 T5 ND1 P1 C10 T2 7 Review the following information to identify the locations where the USB cable connects to the system node that you are servicing and to the system control unit Then reconnect the USB cable that you removed Figure 282 USB Cabling Table 46 USB Cabling From To ND1 or ND2 P1 C13 T3 SC1 P1 T1 a Plug the USB cable into the previously identi...

Страница 337: ... the USB cable into the system node b Plug the USB cable into the previously identified location in the system control unit by inserting the cable into the connector as shown in the following figure Miscellaneous VRMs 331 ...

Страница 338: ...USB cable into the system control unit 8 Using your labels reconnect the rear power cords to the system node being serviced as shown in the following figure 332 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 339: ...ol unit UPIC cable locations are P1 C1 T1 and P1 C2 T1 a Ensure that the white plastic lock is pulled back from the plug housing b Plug the UPIC cable A into the previously identified location in the system control unit by inserting the cable into the connector until it locks into place Miscellaneous VRMs 333 ...

Страница 340: ...tached to the system 10 When the service processor comes up to the Flexible Service Processor FSP standby state the power on LED on the control panel is flashing slowly continue to the next step 11 Access the ASMI and run the Cable Plugging Validation utility to validate all of the cables a If you are already connected to the ASMI go to the next step Otherwise click All Systems then select system ...

Страница 341: ...correct the problems and repeat steps b c and d as needed until the status is OK for all cables e Exit the ASMI 12 Turn off the identify LED For instructions see Deactivating an identify LED www ibm com support knowledgecenter POWER9 p9haj p9haj_turn_off_identify_led htm 13 Start the system For instructions see Starting a system www ibm com support knowledgecenter POWER9 p9haj crustartsys htm Prep...

Страница 342: ...lue cable latch B and pull out the UPIC cable from the system control unit Figure 289 Removing the UPIC cable from the system control unit 5 Attach the electrostatic discharge ESD wrist strap 336 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 343: ...an unpainted metal surface of the system for a minimum of 5 seconds If at any point in this service process you move away from the system it is important to again discharge yourself by touching an unpainted metal surface for at least 5 seconds before you continue with the service process 6 Complete the following steps to place the system node in the service position Do not pull out or install any ...

Страница 344: ...Figure 290 Removing the rear power cords L003 or or 338 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 345: ...r cables To remove all hazardous voltages disconnect all power cords and power cables L003 b Label and disconnect all of the PCIe cables or transceivers that are attached to the PCIe adapters for the system node you are servicing Use hook and loop fasteners to hold the PCIe cables in place Miscellaneous VRMs 339 ...

Страница 346: ...connector Figure 291 Removing the service processor cable from the system node d Label and unplug the UPIC cables for the system node that you are servicing if applicable 1 Remove the white plastic lock A from the plug housing as shown in the following figure 340 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 347: ...Figure 292 Removing the UPIC cable lock 2 Push down on the blue cable latch B and pull out the UPIC cable from the system node as shown in the following figure Miscellaneous VRMs 341 ...

Страница 348: ...or more slack in the SMP cables label and unclip the SMP cable bundle from the side of the cable management bracket as shown in the following figure and move the SMP cables to near the center of the system node 342 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 349: ...on the cable If the metal connectors are bent or damaged they need to be replaced 1 Slightly push in the cable bundle A as shown in the following figure to relieve the spring pressure of the cable connector 2 Pull the blue latch B as shown in the following figure to release the inner cable latch 3 Remove the SMP cable C from the system node Miscellaneous VRMs 343 ...

Страница 350: ...tem node use hook and loop fasteners to connect the cables to the cable management bracket so the cables do not hang loosely h If you are servicing system node ND1 or ND2 label and unplug the USB cable as shown in the following figure 344 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 351: ...Figure 296 Removing the USB cable from the system node i If present remove the two screws A at the rear of the system as shown in the following figure Miscellaneous VRMs 345 ...

Страница 352: ...igure 297 Removing the rear screws j If present remove the four screws A at the front of the system as shown in the following figure 346 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 353: ...ont screws k Release the side latches B for the system node by pressing them downward and then pulling outward as shown in the following figure l Pull out the system node C as shown in the following figure Miscellaneous VRMs 347 ...

Страница 354: ...tes when the system power is turned on might damage the system components a Push the release latch A in the direction shown in the following figure b Slide the cover B off the system unit as shown in the following figure When the service access cover has cleared the upper frame ledge lift the cover up and off the system unit 348 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 355: ...the trusted platform module card as shown in the following figure Verify that the green LED A is lit which indicates that sufficient power exists to light the identify LED on the faulty part If the green LED A does not light use the location code on the service label to find the physical location of the faulty part Miscellaneous VRMs 349 ...

Страница 356: ...ook for the flashing amber LED of the faulty or failed miscellaneous B voltage regulator module The miscellaneous B voltage regulator module is in location P1 C59 Refer to the following image 350 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 357: ...electrostatic discharge ESD wrist strap on and that the ESD clip is plugged into a ground jack or connected to an unpainted metal surface If not do so now 2 Remove a miscellaneous B voltage regulator module by completing the following steps a Unlock the levers A to release the voltage regulator module from its connector Refer to the following image b Rotate the levers in the direction shown c Whil...

Страница 358: ...cted to an unpainted metal surface If not do so now 2 To replace a miscellaneous B voltage regulator module complete the following steps a With the levers A in the open position hold the voltage regulator module by its levers and lower the voltage regulator module into its slot in the system Refer to the following image b Gently push the voltage regulator module into its connector c Rotate the lev...

Страница 359: ...omplete the steps in this procedure Procedure 1 Ensure that you have the electrostatic discharge ESD wrist strap on and that the ESD clip is plugged into a ground jack or connected to an unpainted metal surface If not do so now 2 Replace the service access cover by completing the following steps a Slide the cover A onto the system unit as shown in the following figure b Close the release latch B b...

Страница 360: ...ck to ensure that your fingers do not get caught in the side rails a Unlock the blue rail safety latches A by pushing them towards the front as shown in the following figure b Push the system node back into the rack as shown in the following figure until both system node release latches lock into position 354 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 361: ...Figure 306 Placing the system node into the operating position c Replace the two screws A at the rear of the system if you removed them earlier as shown in the following figure Miscellaneous VRMs 355 ...

Страница 362: ...Figure 307 Replacing the rear screws d Replace the four screws A at the front of the system node as shown in the following figure 356 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 363: ...stem node that you are servicing Then refer to your labels and the following steps to reconnect the SMP cables that you removed from the system node you are servicing If you have a two node system configuration use Figure 309 on page 358 and Table 47 on page 358 to determine the point to point cabling for SMP cables Miscellaneous VRMs 357 ...

Страница 364: ...ram represents a pair of SMP cables Cable Cable type and length From To 5C 880 mm 2 9 ft ND1 P1 T1 ND2 P1 T1 5D 880 mm 2 9 ft ND1 P1 T2 ND2 P1 T2 6C 1005 mm 3 3 ft ND1 P1 T7 ND2 P1 T7 6D 1005 mm 3 3 ft ND1 P1 T8 ND2 P1 T8 5A 1005 mm 3 3 ft ND1 P1 T9 ND2 P1 T9 358 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 365: ...1225 mm 4 01 ft ND1 P1 T17 ND2 P1 T17 6X 1225 mm 4 01 ft ND1 P1 T18 ND2 P1 T18 5W 1005 mm 3 3 ft ND1 P1 T23 ND2 P1 T23 5X 1005 mm 3 3 ft ND1 P1 T24 ND2 P1 T24 6Y 1005 mm 3 3 ft ND1 P1 T25 ND2 P1 T25 6Z 1005 mm 3 3 ft ND1 P1 T26 ND2 P1 T26 5Y 880 mm 2 9 ft ND1 P1 T31 ND2 P1 T31 5Z 880 mm 2 9 ft ND1 P1 T32 ND2 P1 T32 If you have a three node system configuration use Figure 310 on page 360 and Table ...

Страница 366: ...ing a Three Node Configuration Table 48 Cabling a Three Node Configuration Cable Cable type and length From To 5C 880 mm 2 9 ft ND3 P1 T1 ND2 P1 T1 360 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 367: ...mm 4 01 ft ND3 P1 T15 ND1 P1 T9 3B 1225 mm 4 01 ft ND3 P1 T16 ND1 P1 T10 3W 1225 mm 4 01 ft ND3 P1 T17 ND1 P1 T23 3X 1225 mm 4 01 ft ND3 P1 T18 ND1 P1 T24 5W 1005 mm 3 3 ft ND3 P1 T23 ND2 P1 T23 5X 1005 mm 3 3 ft ND3 P1 T24 ND2 P1 T24 3Y 1225 mm 4 01 ft ND3 P1 T25 ND1 P1 T31 3Z 1225 mm 4 01 ft ND3 P1 T26 ND1 P1 T32 5Y 880 mm 2 9 ft ND3 P1 T31 ND2 P1 T31 5Z 880 mm 2 9 ft ND3 P1 T32 ND2 P1 T32 6C 10...

Страница 368: ...25 mm 4 01 ft ND2 P1 T17 ND1 P1 T17 6X 1225 mm 4 01 ft ND2 P1 T18 ND1 P1 T18 6Y 1005 mm 3 3 ft ND2 P1 T25 ND1 P1 T25 6Z 1005 mm 3 3 ft ND2 P1 T26 ND1 P1 T26 If you have a four node system configuration use Figure 311 on page 363 and Table 49 on page 364 to determine the point to point cabling for SMP cables 362 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 369: ...Figure 311 Cabling a Four Node Configuration Miscellaneous VRMs 363 ...

Страница 370: ...8 ND1 P1 T4 2A 1225 mm 4 01 ft ND4 P1 T9 ND2 P1 T11 2B 1225 mm 4 01 ft ND4 P1 T10 ND2 P1 T12 4A 1005 mm 3 3 ft ND4 P1 T11 ND3 P1 T11 4B 1005 mm 3 3 ft ND4 P1 T12 ND3 P1 T12 1A 1625 mm 5 3 ft ND4 P1 T15 ND1 P1 T11 1B 1625 mm 5 3 ft ND4 P1 T16 ND1 P1 T12 1W 1625 mm 5 3 ft ND4 P1 T17 ND1 P1 T21 1X 1625 mm 5 3 ft ND4 P1 T18 ND1 P1 T22 4W 1005 mm 3 3 ft ND4 P1 T21 ND3 P1 T21 4X 1005 mm 3 3 ft ND4 P1 T2...

Страница 371: ...T30 2Y 1225 mm 4 01 ft ND4 P1 T31 ND2 P1 T29 2Z 1225 mm 4 01 ft ND4 P1 T32 ND2 P1 T30 Cables originating on ND3 5C 880 mm 2 9 ft ND3 P1 T1 ND2 P1 T1 5D 880 mm 2 9 ft ND3 P1 T2 ND2 P1 T2 3C 1225 mm 4 01 ft ND3 P1 T7 ND1 P1 T1 3D 1225 mm 4 01 ft ND3 P1 T8 ND1 P1 T2 5A 1005 mm 3 3 ft ND3 P1 T9 ND2 P1 T9 5B 1005 mm 3 3 ft ND3 P1 T10 ND2 P1 T10 3A 1225 mm 4 01 ft ND3 P1 T15 ND1 P1 T9 3B 1225 mm 4 01 ft...

Страница 372: ...1 ft ND2 P1 T15 ND1 P1 T15 6B 1225 mm 4 01 ft ND2 P1 T16 ND1 P1 T16 6W 1225 mm 4 01 ft ND2 P1 T17 ND1 P1 T17 6X 1225 mm 4 01 ft ND2 P1 T18 ND1 P1 T18 6Y 1005 mm 3 3 ft ND2 P1 T25 ND1 P1 T25 6Z 1005 mm 3 3 ft ND2 P1 T26 ND1 P1 T26 a Press the SMP cable and the blue tab together with your fingers and thumb to hold the SMP cable Plug the SMP cable into the previously identified location in the system...

Страница 373: ... the SMP cables previously identified are reconnected to the system node you are servicing c If you removed any SMP cable clips from the side of the rack using your labels reattach the cable bundle to the side of the cable management bracket as shown in the following figure Miscellaneous VRMs 367 ...

Страница 374: ...rmation card inserted into the rear of the system control unit You can also refer to the following figures The number in the cable label indicates the bundle for that cable Two system node configuration The two system node configuration has four cable bundles 368 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 375: ...attaches to the clip C Three system node configuration The three system node configuration has four cable bundles Figure 315 Bundling and connecting SMP cables for three system nodes Two bundles named B3 with the 3 cables The left B3 bundle contains 3A 3B 3C and 3D This bundle attaches to the clip A The right B3 bundle contains 3W 3X 3Y and 3Z This bundle attaches to the clip F Two bundles named B...

Страница 376: ... This bundle attaches to the clips J Two bundles named B4 with the 4 cables The left B4 bundle contains 4A 4B 4C and 4D This bundle attaches to the clip D The right B4 bundle contains 4W 4X 4Y and 4Z This bundle attaches to the clip G Two bundles named B5 with the 5 cables The left B5 bundle contains 5A 5B 5C and 5D This bundle attaches to the clip E The right B5 bundle contains 5W 5X 5Y and 5Z Th...

Страница 377: ...ure 317 Single Node Configuration UPIC Cabling Table 50 Single Node Configuration UPIC Cabling Cable number From To 1 SC1 P1 C1 T1 ND1 P1 C9 T1 2 SC1 P1 C2 T1 ND1 P1 C10 T1 If you have a two three or four node system configuration use Figure 318 on page 372 and Table 51 on page 372 to determine the point to point cabling for UPIC cables Miscellaneous VRMs 371 ...

Страница 378: ...replace the UPIC cable in the system node complete the following steps 1 Ensure that the white plastic lock is pulled back from the plug housing 2 Plug the UPIC cable A into the previously identified location in the system node by inserting the cable into the connector until it locks into place as shown in the following figure 372 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 379: ...Figure 319 Replacing the UPIC cable into the system node 3 Push the white plastic lock B onto the plug housing as shown in the following figure Miscellaneous VRMs 373 ...

Страница 380: ...attached to the system b Repeat step 5 a on page 372 until all the UPIC cables previously identified are reconnected to the system node you are servicing c If applicable secure the cable to the side of the rack with the hook and loop fastener 6 Using your labels reconnect the service processor FSP cables that you removed from the system node you are servicing 374 Power Systems Removing and replaci...

Страница 381: ...Figure 321 Service processor FSP cabling Miscellaneous VRMs 375 ...

Страница 382: ... P1 T3 ND1 P1 C9 T2 B 355 mm 1 16 ft SC1 P1 T5 ND1 P1 C10 T2 7 Review the following information to identify the locations where the USB cable connects to the system node that you are servicing and to the system control unit Then reconnect the USB cable that you removed Figure 322 USB Cabling Table 53 USB Cabling From To ND1 or ND2 P1 C13 T3 SC1 P1 T1 a Plug the USB cable into the previously identi...

Страница 383: ... the USB cable into the system node b Plug the USB cable into the previously identified location in the system control unit by inserting the cable into the connector as shown in the following figure Miscellaneous VRMs 377 ...

Страница 384: ...USB cable into the system control unit 8 Using your labels reconnect the rear power cords to the system node being serviced as shown in the following figure 378 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 385: ...ol unit UPIC cable locations are P1 C1 T1 and P1 C2 T1 a Ensure that the white plastic lock is pulled back from the plug housing b Plug the UPIC cable A into the previously identified location in the system control unit by inserting the cable into the connector until it locks into place Miscellaneous VRMs 379 ...

Страница 386: ...tached to the system 10 When the service processor comes up to the Flexible Service Processor FSP standby state the power on LED on the control panel is flashing slowly continue to the next step 11 Access the ASMI and run the Cable Plugging Validation utility to validate all of the cables a If you are already connected to the ASMI go to the next step Otherwise click All Systems then select system ...

Страница 387: ...dation Then select All of the above in the Display Cable Status section and click Continue The system validates that the cables are installed in the correct locations Expand System Service Aids Cable Plugging Validation to display a table with the results Ensure that the plugging status is OK for each cable in the displayed table If the status is OK no further action is required If the status is n...

Страница 388: ...382 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 389: ...door if necessary 2 Label and disconnect both UPIC cables from the system control unit UPIC cable locations are P1 C1 T1 and P1 C2 T1 a Remove the white plastic lock A from the plug housing Figure 328 Removing the UPIC cable lock b Push down on the blue cable latch B and pull out the UPIC cable from the system control unit ...

Страница 390: ...n in the following figure CAUTION The fans can pull in hair jewelry loose clothing and so forth and cause injury or damage Operate the system with the bezel installed For service operations if the front cover must be removed with the system operating ensure that all such loose material is secured away from the fan area to prevent any loose material from being pulled into the fan 384 Power Systems ...

Страница 391: ...Figure 330 Removing the front cover 4 Disconnect all of the front power cords that plug into the power supplies of the system node that is being serviced NVMe backplane 385 ...

Страница 392: ... bracket in the service position as shown in the following figure a Pull out the quarter turn fasteners B and turn them to disengage them while you lift the cable management bracket A to its raised position b Turn the quarter turn fasteners B to engage and lock the bracket into position 386 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 393: ...damaging your hardware When you use an ESD wrist strap follow all electrical safety procedures An ESD wrist strap is used for static control It does not increase or decrease your risk of receiving electric shock when using or working on electrical equipment If you do not have an ESD wrist strap just prior to removing the product from ESD packaging and installing or replacing hardware touch an unpa...

Страница 394: ...an unpainted metal surface If not do so now 2 To remove any NVMe U 2 drives from the failed backplane complete the following steps a Press the release latch A in the direction that is shown to release the drive handle B L007 CAUTION A hot surface nearby L007 b Support the bottom of the NVMe U 2 drive as you slide the drive out of the system holding the drive by its sides Note Do not pull the drive...

Страница 395: ...b Put your thumb on the front side of the latch B and put your index finger against the rear of the latch C as shown in the following figure c Push against the latch with your thumb and then pull the latch out with your index finger This action releases the latch d Rotate the backplane handle in the direction that is shown in the following figure to unlock the backplane from its slot e Hold on to ...

Страница 396: ...lugged into a ground jack or connected to an unpainted metal surface If not do so now 2 If necessary remove the NVMe drive backplane from the antistatic package 3 Place the NVMe drive backplane on an appropriate ESD surface 4 To install the NVMe drive backplane complete the following steps a Slide the NVMe drive backplane A into the system until it is seated b Press the NVMe backplane latch B in t...

Страница 397: ...ive backplane complete the following steps Note Using your labels ensure that you put the NVMe U 2 drives into the same slot in the replacement backplane a Press the release latch A in the direction that is shown to release the drive handle B b Slide the NVMe U 2 drive into the slot until it s fully seated NVMe backplane 391 ...

Страница 398: ...e the electrostatic discharge ESD wrist strap on and that the ESD clip is plugged into a ground jack or connected to an unpainted metal surface If not do so now 2 Put the cable management bracket in the operating position as shown in the following figure a Pull out the quarter turn fasteners B and turn them to disengage them while moving the cable management bracket A to its lower position b Turn ...

Страница 399: ...Placing the cable management bracket in the lowered operating position 3 Connect all of the front power cords that plug into the power supplies of the system node Tuck the cords into the chassis NVMe backplane 393 ...

Страница 400: ...over A on the front of the system unit as shown in the following figure so that the four pins B on the system match the four holes at the rear of the cover Press the front cover into position 394 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 401: ...l unit UPIC cable locations are P1 C1 T1 and P1 C2 T1 a Ensure that the white plastic lock is pulled back from the plug housing b Plug the UPIC cable A into the previously identified location in the system control unit by inserting the cable into the connector until it locks into place NVMe backplane 395 ...

Страница 402: ...ttached to the system 6 When the service processor comes up to the Flexible Service Processor FSP standby state the power on LED on the control panel is flashing slowly continue to the next step 7 Access the ASMI and run the Cable Plugging Validation utility to validate all of the cables a If you are already connected to the ASMI go to the next step Otherwise click All Systems then select system b...

Страница 403: ... the bottom node If the LEDs do not light up in sequence the FSP cables need to be re installed d Expand System Service Aids Cable Plugging Validation Then select All of the above in the Display Cable Status section and click Continue The system validates that the cables are installed in the correct locations Expand System Service Aids Cable Plugging Validation to display a table with the results ...

Страница 404: ...398 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 405: ...e See the Power Systems Prerequisites website 2 If applicable open the rack door at the rear of the system 3 Review the NVMe U 2 drive slot locations The NVMe U 2 drive slots are located in the rear of the system Figure 342 Location of the NVMe U 2 drives in the 9080 M9S system 4 Review the NVMe U 2 drive LED locations The NVMe U 2 drive has two LEDs that indicate the following status A power acti...

Страница 406: ...m com support knowledgecenter POWER9 p9haj sal htm b Physically verify that the slot you identified is where you want to install or replace the NVMe U 2 drive Use the blue identify LED on the enclosure to locate the system Ensure that the serial number of the system matches the serial number to be serviced Look for a flashing amber LED which identifies the slot that was selected by using the ident...

Страница 407: ...d pull out the UPIC cable from the system control unit Figure 345 Removing the UPIC cable from the system control unit 8 Continue with step 12 on page 403 9 To identify the available NVMe U 2 drive slots by using the AIX operating system complete the following steps NVMe drives 401 ...

Страница 408: ...ve when you are instructed to do so later in this procedure 10 Continue with step 12 on page 403 11 To identify the available NVMe U 2 drive slots by using the Linux operating system complete the following steps Note The NVMe U 2 drives are based on PCI technology a Log in to the system console as the root user b Run the following command to list the available slots lsslot c pci a The following sc...

Страница 409: ...able management bracket A to its raised position b Turn the quarter turn fasteners B to engage and lock the bracket into position Figure 346 Placing the cable management bracket in the raised service position 13 Attach the electrostatic discharge ESD wrist strap The ESD wrist strap must be connected to an unpainted metal surface until the service procedure is completed and if applicable until the ...

Страница 410: ... an unpainted metal surface for at least 5 seconds before you continue with the service process Installing an NVMe U 2 drive in the 9080 M9S system To install an NVMe U 2 drive into the system complete the steps in this procedure Procedure 1 Ensure that you have the electrostatic discharge ESD wrist strap on and that the ESD clip is plugged into a ground jack or connected to an unpainted metal sur...

Страница 411: ...operation after installing an NVMe U 2 drive To prepare the system for operation after installing an NVMe U 2 drive complete the steps in this procedure Procedure 1 Ensure that you have the electrostatic discharge ESD wrist strap on and that the ESD clip is plugged into a ground jack or connected to an unpainted metal surface If not do so now 2 Put the cable management bracket in the operating pos...

Страница 412: ...irmware levels do not support validating the UPIC cables while the system is at FSP standby You can skip this step if it is not available c Expand System Service Aids Cable Plugging Validation In the Display Cable Status section select UPIC Cables and click Continue The system validates that the UPIC cables are installed in the correct locations and displays a table with the results Ensure that th...

Страница 413: ...IC cables to the system control unit UPIC cable locations are P1 C1 T1 and P1 C2 T1 a Ensure that the white plastic lock is pulled back from the plug housing b Plug the UPIC cable A into the previously identified location in the system control unit by inserting the cable into the connector until it locks into place Figure 350 Replacing the UPIC cable into the system control unit c Push the white p...

Страница 414: ...y a table with the results Ensure that the plugging status is OK for each cable in the displayed table If the status is OK no further action is required If the status is not OK review the error logs correct the problems and repeat steps b c and d as needed until the status is OK for all cables e Exit the ASMI 8 Start the system For instructions see Starting a system www ibm com support knowledgece...

Страница 415: ...replacing Preparing the 9080 M9S system to remove and replace an NVMe U 2 drive To prepare the system to remove and replace an NVMe U 2 drive complete the steps in this procedure Procedure 1 If you chose to complete this repair with the power off label and disconnect both UPIC cables from the system control unit UPIC cable locations are P1 C1 T1 and P1 C2 T1 a Remove the white plastic lock A from ...

Страница 416: ...ice position as shown in the following figure a Pull out the quarter turn fasteners B and turn them to disengage them while you lift the cable management bracket A to its raised position b Turn the quarter turn fasteners B to engage and lock the bracket into position 410 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 417: ...m damaging your hardware When you use an ESD wrist strap follow all electrical safety procedures An ESD wrist strap is used for static control It does not increase or decrease your risk of receiving electric shock when using or working on electrical equipment If you do not have an ESD wrist strap just prior to removing the product from ESD packaging and installing or replacing hardware touch an un...

Страница 418: ...cted to an unpainted metal surface If not do so now 2 To remove an NVMe U 2 drive complete the following steps a Press the release latch A in the direction that is shown to release the drive handle B L007 CAUTION A hot surface nearby L007 b Support the bottom of the NVMe U 2 drive as you slide the drive out of the system holding the drive by its sides Note Do not pull the drive out by using the ha...

Страница 419: ... have the electrostatic discharge ESD wrist strap on and that the ESD clip is plugged into a ground jack or connected to an unpainted metal surface If not do so now 2 If necessary remove the NVMe U 2 drive from the antistatic package 3 To install or replace an NVMe U 2 drive complete the following steps a Press the handle release latch A in the direction that is shown to release the latch handle b...

Страница 420: ... Ensure that you have the electrostatic discharge ESD wrist strap on and that the ESD clip is plugged into a ground jack or connected to an unpainted metal surface If not do so now 2 Put the cable management bracket in the operating position as shown in the following figure a Pull out the quarter turn fasteners B and turn them to disengage them while moving the cable management bracket A to its lo...

Страница 421: ... Management ASM b In the navigation area expand System Service Aids Cable Plugging Validation Then click Validate UPIC Cables The system verifies that the UPIC cables are present Note Older firmware levels do not support validating the UPIC cables while the system is at FSP standby You can skip this step if it is not available c Expand System Service Aids Cable Plugging Validation In the Display C...

Страница 422: ...ock is pulled back from the plug housing b Plug the UPIC cable A into the previously identified location in the system control unit by inserting the cable into the connector until it locks into place Figure 358 Replacing the UPIC cable into the system control unit c Push the white plastic lock B onto the plug housing Figure 359 Replacing the UPIC cable into the system control unit 416 Power System...

Страница 423: ... continue to the next step If the system is cabled correctly the blue identify LED on each system node will light up in sequence from the top node to the bottom node If the LEDs do not light up in sequence the FSP cables need to be re installed d Expand System Service Aids Cable Plugging Validation Then select All of the above in the Display Cable Status section and click Continue The system valid...

Страница 424: ...drive LED locations The NVMe U 2 drive has two LEDs that indicate the following status A power activity LED green An error and identify function LED amber Figure 361 Locations of the NVMe U 2 LEDs in the 9080 M9S system 418 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 425: ...the system matches the serial number to be serviced Look for a flashing amber LED which identifies the slot that was selected by using the identify function c Stop the system For instructions see Stopping a system www ibm com support knowledgecenter POWER9 p9haj crustopsys htm 5 If you chose to complete this repair with the power off label and disconnect both UPIC cables from the system control un...

Страница 426: ...ice position as shown in the following figure a Pull out the quarter turn fasteners B and turn them to disengage them while you lift the cable management bracket A to its raised position b Turn the quarter turn fasteners B to engage and lock the bracket into position 420 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 427: ...m damaging your hardware When you use an ESD wrist strap follow all electrical safety procedures An ESD wrist strap is used for static control It does not increase or decrease your risk of receiving electric shock when using or working on electrical equipment If you do not have an ESD wrist strap just prior to removing the product from ESD packaging and installing or replacing hardware touch an un...

Страница 428: ...ack or connected to an unpainted metal surface If not do so now 2 To remove an NVMe U 2 drive complete the following steps a Press the release latch A in the direction that is shown to release the drive handle B L007 CAUTION A hot surface nearby L007 b Support the bottom of the NVMe U 2 drive as you slide the drive out of the system holding the drive by its sides Note Do not pull the drive out by ...

Страница 429: ...n appropriate ESD surface 4 Install an NVMe drive filler a With the drive filler handle A in the open position slide the filler into the slot where you permanently removed the NVMe U 2 drive b Close the drive filler handle A in the direction that is shown until it locks in place NVMe drives 423 ...

Страница 430: ... discharge ESD wrist strap on and that the ESD clip is plugged into a ground jack or connected to an unpainted metal surface If not do so now 2 Put the cable management bracket in the operating position as shown in the following figure a Pull out the quarter turn fasteners B and turn them to disengage them while moving the cable management bracket A to its lower position b Turn the quarter turn fa...

Страница 431: ...ot support validating the UPIC cables while the system is at FSP standby You can skip this step if it is not available c Expand System Service Aids Cable Plugging Validation In the Display Cable Status section select UPIC Cables and click Continue The system validates that the UPIC cables are installed in the correct locations and displays a table with the results Ensure that the plugging status i...

Страница 432: ...g Figure 369 Replacing the UPIC cable into the system control unit d Lightly pull on the UPIC cable from both attachment points to ensure it is locked into place Pull the cable connector do not pull on the wire The cables should be firmly attached to the system 5 When the service processor comes up to the Flexible Service Processor FSP standby state the power on LED on the control panel is flashin...

Страница 433: ...led correctly the blue identify LED on each system node will light up in sequence from the top node to the bottom node If the LEDs do not light up in sequence the FSP cables need to be re installed d Expand System Service Aids Cable Plugging Validation Then select All of the above in the Display Cable Status section and click Continue The system validates that the cables are installed in the corre...

Страница 434: ...428 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 435: ...equired software is installed to support the new feature See the Power Systems Prerequisites website Important If you are installing a PCIe3 cable adapter and want to connect a EMX0 PCIe3 expansion drawer via the HMC you must have the HMC driver 9 1 921 0 or later installed 2 Take appropriate precautions for avoiding electric shock and for handling static sensitive devices For more information see...

Страница 436: ...r has three LEDs that indicate the following status A power activity LED green An identify function LED amber for the adapter labeled C1 An identify function LED amber for the cassette labeled with an exclamation mark 430 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 437: ...x operating system controls the slot continue with step 12 on page 434 7 To prepare the system to install an adapter when the system is powered off complete the following steps a Activate the identify function For instructions see Identifying a part www ibm com support knowledgecenter POWER9 p9haj sal htm b Physically verify that the slot you identified is where you want to install the adapter Use...

Страница 438: ...ff label and disconnect both UPIC cables from the system control unit UPIC cable locations are P1 C1 T1 and P1 C2 T1 a Remove the white plastic lock A from the plug housing Figure 372 Removing the UPIC cable lock b Push down on the blue cable latch B and pull out the UPIC cable from the system control unit 432 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 439: ...ger menu select Add a PCI Hot Plug Adapter and then press Enter e Select the appropriate slot from the list that is displayed on the screen and then press Enter f Physically verify that the slot you identified is where you want to install the adapter Use the blue identify LED on the enclosure to locate the system Ensure that the serial number of the system matches the serial number to be serviced ...

Страница 440: ...em complete the following steps a Log in to the system console as the root user b Run the following command to list the available slots lsslot c pci a The following screen is an example of the information that is displayed by this command Slot Description Device s U7879 001 DQD014E P1 C1 PCI X capable 64 bit 133MHz slot Empty U7879 001 DQD014E P1 C4 PCI X capable 64 bit 133MHz slot Empty U7879 001...

Страница 441: ...he cable management bracket A to its raised position b Turn the quarter turn fasteners B to engage and lock the bracket into position Figure 374 Placing the cable management bracket in the raised service position 14 Attach the electrostatic discharge ESD wrist strap The ESD wrist strap must be connected to an unpainted metal surface until the service procedure is completed and if applicable until ...

Страница 442: ...r in the system complete the steps in this procedure Procedure 1 Ensure that you have the electrostatic discharge ESD wrist strap on and that the ESD clip is plugged into a ground jack or connected to an unpainted metal surface If not do so now 2 If necessary remove the adapter from the antistatic package Attention Avoid touching the components and gold connectors on the adapter 3 Place the adapte...

Страница 443: ...er cassette from the 9080 M9S system 5 Remove the side cover from the cassette a Press the release button on the side cover and slide the cover in the direction that is shown b Lift the side cover off the cassette PCIe adapters 437 ...

Страница 444: ...r the 9080 M9S system 6 Remove the top cover from the cassette a Press the release button on the top cover and slide the cover in the direction that is shown b Lift the top cover off the cassette 438 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 445: ... 7 Remove the tailstock filler from the cassette a Pull the tailstock filler away from the cassette in the direction that is shown b Save the tailstock filler for a future use You must have a tailstock filler in an empty cassette in a system to ensure proper airflow PCIe adapters 439 ...

Страница 446: ...ainers continue with the next step If you have adapter retainers complete the following steps 1 Ensure that the retainer latches A are in the open position by pushing up on the latch in the direction that is shown in the following figure 2 Slide up the retainers and remove them from the cassette and then discard them 440 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 447: ...ners for the 9080 M9S system so you can slide them off and discard them Note The adapter retainers are not needed b Press the adapter firmly into its connector as shown in the following figure ensuring that it is seated PCIe adapters 441 ...

Страница 448: ...s secured in the adapter retainer channel 9 Replace the top cover on the cassette a Lower the top cover on the top of the cassette b Slide the top cover in the direction that is shown in the following figure until it latches securely 442 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 449: ...r cassette for the 9080 M9S system 10 Replace the side cover on the cassette a Place the side cover on the side of the cassette b Slide the side cover in the direction that is shown in the following figure until it latches securely PCIe adapters 443 ...

Страница 450: ...er alignment when you insert a adapter cassette into the system a Align the cassette on the cassette rail in the cassette slot b Slide the cassette forward until the cassette is fully seated c To lock the adapter in its slot rotate the adapter latch A in the direction that is shown in the following figure 444 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 451: ... your system http www ibm com support knowledgecenter POWER9 p9egp p9egp_connect_kickoff htm If you have an HMC managed 9040 MR9 or 9080 M9S system you can connect and activate the expansion drawer cable when the system power is turned on Otherwise you must connect the cable with the system power turned off The cable is activated when you start the system 3 Connect any cables or transceivers to th...

Страница 452: ... UPIC cables are present Note Older firmware levels do not support validating the UPIC cables while the system is at FSP standby You can skip this step if it is not available c Expand System Service Aids Cable Plugging Validation In the Display Cable Status section select UPIC Cables and click Continue The system validates that the UPIC cables are installed in the correct locations and displays a ...

Страница 453: ...s are installed in the correct locations Expand System Service Aids Cable Plugging Validation to display a table with the results Ensure that the plugging status is OK for each cable in the displayed table If the status is OK no further action is required If the status is not OK review the error logs correct the problems and repeat steps b c and d as needed until the status is OK for all cables e ...

Страница 454: ...the wire The cables should be firmly attached to the system b Start the system For instructions see Starting a system www ibm com support knowledgecenter POWER9 p9haj crustartsys htm c Continue with step 18 on page 449 12 If you are using the AIX operating system you must configure the adapter by completing the following steps a Install the AIX device drivers for the installed adapter For instruct...

Страница 455: ... the deletion of the namespaces 3 Press F12 to return to the SST main menu e On the System Service Tools SST display select Work with disk units Work with disk configuration Work with NVM Devices Create NVM Namespaces f Select the NVMe device that you installed g On the Create NVM Namespaces display select the quantity and capacity of the namespaces disk units that you want to create on the newly ...

Страница 456: ...tm Removing and replacing a cassette Preparing the 9080 M9S system to remove and replace an adapter cassette Procedure 1 If you chose to complete this repair with the power off label and disconnect both UPIC cables from the system control unit UPIC cable locations are P1 C1 T1 and P1 C2 T1 a Remove the white plastic lock A from the plug housing Figure 387 Removing the UPIC cable lock b Push down o...

Страница 457: ...f the system put the cable management bracket in the service position as shown in the following figure a Pull out the quarter turn fasteners B and turn them to disengage them while you lift the cable management bracket A to its raised position b Turn the quarter turn fasteners B to engage and lock the bracket into position PCIe adapters 451 ...

Страница 458: ...your hardware to prevent the electrostatic discharge from damaging your hardware When you use an ESD wrist strap follow all electrical safety procedures An ESD wrist strap is used for static control It does not increase or decrease your risk of receiving electric shock when using or working on electrical equipment If you do not have an ESD wrist strap just prior to removing the product from ESD pa...

Страница 459: ...the slot a Press in on the latch release A as shown in the following figure The latch is released b Rotate the latch in the direction shown The cassette is released from the slot c Pull the cassette straight out from the slot Figure 390 Removing the adapter cassette from the 9080 M9S system 3 Remove the side cover from the cassette a Press the release button on the side cover and slide the cover i...

Страница 460: ...r the 9080 M9S system 4 Remove the top cover from the cassette a Press the release button on the top cover and slide the cover in the direction that is shown b Lift the top cover off the cassette 454 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 461: ...not have adapter retainers continue with the next step If you have adapter retainers complete the following steps 1 Ensure that the retainer latches are in the open position by pushing up on the latch in the direction that is shown in the following figure 2 Slide the adapter retainers up and remove them from the cassette and then discard the retainers PCIe adapters 455 ...

Страница 462: ...3 Opening the adapter retainers for the 9040 MR9 system Note The adapter retainers are not needed b Pull the adapter away from the connectors 456 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 463: ...the PCIe adapter so that you can install it into the replacement PCIe adapter cassette 7 Remove the PCIe adapter cassette from the antistatic packaging 8 Remove the side cover from the cassette a Press the release button on the side cover and slide the cover in the direction that is shown b Lift the side cover off the cassette PCIe adapters 457 ...

Страница 464: ...r the 9080 M9S system 9 Remove the top cover from the cassette a Press the release button on the top cover and slide the cover in the direction that is shown b Lift the top cover off the cassette 458 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 465: ...ure 396 Removing the top cover from the adapter cassette for the 9080 M9S system 10 Press the adapter firmly into its connector as shown in the following figure ensuring that it is seated PCIe adapters 459 ...

Страница 466: ...stem 11 Replace the top cover on the cassette a Lower the top cover on the top of the cassette b Slide the top cover in the direction that is shown in the following figure until it latches securely 460 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 467: ...r cassette for the 9080 M9S system 12 Replace the side cover on the cassette a Place the side cover on the side of the cassette b Slide the side cover in the direction that is shown in the following figure until it latches securely PCIe adapters 461 ...

Страница 468: ... connected to an unpainted metal surface If not do so now 2 Ensure that the target slot is empty 3 Slide the cassette into the slot by completing the following steps Attention Ensure proper alignment when you insert a adapter cassette into the system a Align the cassette on the cassette rail in the cassette slot b Slide the cassette forward until the cassette is fully seated c To lock the adapter ...

Страница 469: ...to an unpainted metal surface If not do so now 2 If removed connect the cables or transceivers to the adapter 3 Route the cables through the cable management bracket 4 Put the cable management bracket in the operating position as shown in the following figure a Pull out the quarter turn fasteners B and turn them to disengage them while moving the cable management bracket A to its lower position b ...

Страница 470: ...t the UPIC cables are present Note Older firmware levels do not support validating the UPIC cables while the system is at FSP standby You can skip this step if it is not available c Expand System Service Aids Cable Plugging Validation In the Display Cable Status section select UPIC Cables and click Continue The system validates that the UPIC cables are installed in the correct locations and displa...

Страница 471: ...ed location in the system control unit by inserting the cable into the connector until it locks into place Figure 402 Replacing the UPIC cable into the system control unit c Push the white plastic lock B onto the plug housing Figure 403 Replacing the UPIC cable into the system control unit d Lightly pull on the UPIC cable from both attachment points to ensure it is locked into place Pull the cable...

Страница 472: ...le Plugging Validation to display a table with the results Ensure that the plugging status is OK for each cable in the displayed table If the status is OK no further action is required If the status is not OK review the error logs correct the problems and repeat steps b c and d as needed until the status is OK for all cables e Exit the ASMI Rempving and replacing an adapter Preparing the 9080 M9S ...

Страница 473: ... white plastic lock A from the plug housing Figure 404 Removing the UPIC cable lock b Push down on the blue cable latch B and pull out the UPIC cable from the system control unit Figure 405 Removing the UPIC cable from the system control unit PCIe adapters 467 ...

Страница 474: ...n 4 Label and disconnect all of the cables or transceivers that are attached to the adapter you plan to remove Use a hook and loop fastener to hold the cables in place 5 Attach the electrostatic discharge ESD wrist strap The ESD wrist strap must be connected to an unpainted metal surface until the service procedure is completed and if applicable until the service access cover is replaced Attention...

Страница 475: ...onds before you continue with the service process Removing a PCIe adapter from the 9080 M9S system Procedure 1 Ensure that you have the electrostatic discharge ESD wrist strap on and that the ESD clip is plugged into a ground jack or connected to an unpainted metal surface If not do so now 2 Remove the adapter cassette from the slot a Press in on the latch release A as shown in the following figur...

Страница 476: ...r the 9080 M9S system 4 Remove the top cover from the cassette a Press the release button on the top cover and slide the cover in the direction that is shown b Lift the top cover off the cassette 470 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 477: ...not have adapter retainers continue with the next step If you have adapter retainers complete the following steps 1 Ensure that the retainer latches are in the open position by pushing up on the latch in the direction that is shown in the following figure 2 Slide the adapter retainers up and remove them from the cassette and then discard the retainers PCIe adapters 471 ...

Страница 478: ...0 Opening the adapter retainers for the 9040 MR9 system Note The adapter retainers are not needed b Pull the adapter away from the connectors 472 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 479: ...re that the target slot is empty 3 If necessary remove the adapter from the antistatic package Attention Avoid touching the components and gold connectors on the adapter 4 Place the adapter component side up on a flat antistatic surface Attention A pin on the tailstock of the adapter resembles a removable screw Do not remove this pin It is required for correct alignment and seating 5 If you want p...

Страница 480: ...ystem 7 Replace the top cover on the cassette a Lower the top cover on the top of the cassette b Slide the top cover in the direction that is shown in the following figure until it latches securely 474 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 481: ...er cassette for the 9080 M9S system 8 Replace the side cover on the cassette a Place the side cover on the side of the cassette b Slide the side cover in the direction that is shown in the following figure until it latches securely PCIe adapters 475 ...

Страница 482: ...er alignment when you insert a adapter cassette into the system a Align the cassette on the cassette rail in the cassette slot b Slide the cassette forward until the cassette is fully seated c To lock the adapter in its slot rotate the adapter latch A in the direction that is shown in the following figure 476 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 483: ...ESD clip is plugged into a ground jack or connected to an unpainted metal surface If not do so now 2 If removed connect the cables or transceivers to the adapter 3 Route the cables through the cable management bracket 4 Put the cable management bracket in the operating position as shown in the following figure a Pull out the quarter turn fasteners B and turn them to disengage them while moving the...

Страница 484: ...e UPIC cables are present Note Older firmware levels do not support validating the UPIC cables while the system is at FSP standby You can skip this step if it is not available c Expand System Service Aids Cable Plugging Validation In the Display Cable Status section select UPIC Cables and click Continue The system validates that the UPIC cables are installed in the correct locations and displays a...

Страница 485: ...e error logs correct the problems and repeat steps b c and d as needed until the status is OK for all cables e Exit the ASMI 9 If you replaced a PCIe3 x8 non volatile memory SSD NVMe adapter and the logical partition that controls the adapter is running the IBM i operating system complete the following steps to prepare the NVMe adapter for operation a Start the IBM i System Service Tools STRSST an...

Страница 486: ...ove an adapter Procedure 1 If you chose to complete this repair with the power off label and disconnect both UPIC cables from the system control unit UPIC cable locations are P1 C1 T1 and P1 C2 T1 a Remove the white plastic lock A from the plug housing Figure 417 Removing the UPIC cable lock b Push down on the blue cable latch B and pull out the UPIC cable from the system control unit 480 Power Sy...

Страница 487: ...gement bracket in the service position as shown in the following figure a Pull out the quarter turn fasteners B and turn them to disengage them while you lift the cable management bracket A to its raised position b Turn the quarter turn fasteners B to engage and lock the bracket into position PCIe adapters 481 ...

Страница 488: ...your hardware to prevent the electrostatic discharge from damaging your hardware When you use an ESD wrist strap follow all electrical safety procedures An ESD wrist strap is used for static control It does not increase or decrease your risk of receiving electric shock when using or working on electrical equipment If you do not have an ESD wrist strap just prior to removing the product from ESD pa...

Страница 489: ...do so now 2 Remove the adapter cassette from the slot a Press in on the latch release A as shown in the following figure The latch is released b Rotate the latch in the direction shown The cassette is released from the slot c Pull the cassette straight out from the slot Figure 420 Removing the adapter cassette from the 9080 M9S system 3 Remove the side cover from the cassette a Press the release b...

Страница 490: ...r the 9080 M9S system 4 Remove the top cover from the cassette a Press the release button on the top cover and slide the cover in the direction that is shown b Lift the top cover off the cassette 484 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 491: ...not have adapter retainers continue with the next step If you have adapter retainers complete the following steps 1 Ensure that the retainer latches are in the open position by pushing up on the latch in the direction that is shown in the following figure 2 Slide the adapter retainers up and remove them from the cassette and then discard the retainers PCIe adapters 485 ...

Страница 492: ...3 Opening the adapter retainers for the 9040 MR9 system Note The adapter retainers are not needed b Pull the adapter away from the connectors 486 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 493: ...ponent side up on a flat antistatic surface 6 After permanently removing a PCIe adapter you must install a PCIe filler in the cassette a Carefully grasp the filler and align the filler with the slot and its connector in the cassette b Press the filler firmly into the connectors PCIe adapters 487 ...

Страница 494: ...ystem 7 Replace the top cover on the cassette a Lower the top cover on the top of the cassette b Slide the top cover in the direction that is shown in the following figure until it latches securely 488 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 495: ...pter cassette for the 9080 M9S system 8 Replace the side cover on the cassette a Place the side cover on the side of the cassette b Slide the side cover in the direction that is shown in the following figure until it latches securely PCIe adapters 489 ...

Страница 496: ...oper alignment when you insert a adapter cassette into the system a Align the cassette on the cassette rail in the cassette slot b Slide the cassette forward until the cassette is fully seated c To lock the adapter in its slot rotate the adapter latch A in the direction that is shown in the following figure 490 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 497: ...e ESD clip is plugged into a ground jack or connected to an unpainted metal surface If not do so now 2 Put the cable management bracket in the operating position as shown in the following figure a Pull out the quarter turn fasteners B and turn them to disengage them while moving the cable management bracket A to its lower position b Turn the quarter turn fasteners B to engage and lock the bracket ...

Страница 498: ...UPIC Cables The system verifies that the UPIC cables are present Note Older firmware levels do not support validating the UPIC cables while the system is at FSP standby You can skip this step if it is not available c Expand System Service Aids Cable Plugging Validation In the Display Cable Status section select UPIC Cables and click Continue The system validates that the UPIC cables are installed ...

Страница 499: ...usly identified location in the system control unit by inserting the cable into the connector until it locks into place Figure 430 Replacing the UPIC cable into the system control unit c Push the white plastic lock B onto the plug housing Figure 431 Replacing the UPIC cable into the system control unit d Lightly pull on the UPIC cable from both attachment points to ensure it is locked into place P...

Страница 500: ...tion Otherwise if your configuration includes only one node continue to the next step If the system is cabled correctly the blue identify LED on each system node will light up in sequence from the top node to the bottom node If the LEDs do not light up in sequence the FSP cables need to be re installed d Expand System Service Aids Cable Plugging Validation Then select All of the above in the Displ...

Страница 501: ...hat the ESD clip is plugged into a ground jack or connected to an unpainted metal surface If not do so now 2 Remove the Power APSS and TPM card Note Be careful not to damage the identification LED activation button as you complete these steps a Unlock the levers A to release the Power APSS and TPM card from its connector Refer to the following image b Rotate the levers in the direction shown c Whi...

Страница 502: ...ged into a ground jack or connected to an unpainted metal surface If not do so now 2 Replace the Power APSS and TPM card a With the levers A in the open position hold the Power APSS and TPM card by the levers and lower the card into its slot in the system Refer to the following image b Gently push the Power APSS and TPM card card into its connector c Rotate the levers in the direction shown and pr...

Страница 503: ...Figure 433 Replacing the Power APSS and TPM card Power APSS and trusted platform module card 497 ...

Страница 504: ...498 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 505: ...ou chose to complete this repair with the power off Note If you chose to disconnect power for this procedure you already removed both UPIC cables The following images show both UPIC cables being unplugged so that you are aware of the location for each cable However if you chose to complete this repair with the power on you will only need to unplug the cable from the power interface card that you a...

Страница 506: ...h against the front of the latch A and then pull the latch out from the rear B This action releases the latch c Rotate the power interface card handle in the direction shown in the following figure to unlock the card from its slot d Hold on to the power interface card handle and use your hand to support the bottom of the card as you pull the card out from its slot as shown in the following figure ...

Страница 507: ...rface card a Ensure that the power interface card handle A is open as shown in the following figure b Hold on to the power interface card handle and use your hand to support the bottom of the card as you slide the card into its slot as shown in the following figure c Push the power interface card handle in the direction shown in the following figure d Push against the front of the latch B with you...

Страница 508: ... being unplugged so that you are aware of the location for each cable If you chose to complete this procedure with the power on you only need to reconnect the cable to the power interface card that you are servicing a Ensure that the white plastic lock is pulled back from the plug housing b Inserting the cable into the connector until it locks into place as shown in the following figure 502 Power ...

Страница 509: ...g as shown in the following figure Figure 439 Replacing the UPIC cable into the system control unit d Lightly pull on the UPIC cable from both attachment points to ensure it is locked into place Pull the cable connector do not pull on the wire The cables should be firmly attached to the system Power interface card 503 ...

Страница 510: ...504 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 511: ...plete procedure to remove and replace a system power supply and that you can remove and replace the power supply within this time Procedure 1 If applicable open the rack front door 2 Place your fingers on the indentations located on both sides of the cover A and pull the cover away from the system as shown in the following figure CAUTION The fans can pull in hair jewelry loose clothing and so fort...

Страница 512: ...s are installed in the front of the system The following figure shows the location of the power supplies in a system and the position of the light emitting diodes LEDs on the power supply 506 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 513: ...ble 54 Description of the power supply LED states AC Power LED Green DC Power LED Green Identify LED Amber Power Supply Status On Solid On Solid Off The power supply is operating correctly See B in the following figure On Solid Flashing Off The system is turned off but the power supply is still connected to the power source See C in the following figure On Solid On Solid Flashing The power supply ...

Страница 514: ...owered on 5 Ensure that the amber LED corresponds to the location of the power supply and the lit fault LED 6 If you can complete the procedure with the system power turned on continue with step 8 on page 509 7 If you need to power off the server to complete the repair operation complete the following steps a Label and disconnect both UPIC cables from the system control unit as shown in the follow...

Страница 515: ...em control unit Figure 444 Removing the UPIC cable from the system control unit 8 Attach the electrostatic discharge ESD wrist strap The ESD wrist strap must be connected to an unpainted metal surface until the service procedure is completed and if applicable until the service access cover is replaced Power supplies 509 ...

Страница 516: ...nimum of 5 seconds If at any point in this service process you move away from the system it is important to again discharge yourself by touching an unpainted metal surface for at least 5 seconds before you continue with the service process Removing a power supply from the 9080 M9S system To remove a power supply complete the steps in this procedure Procedure 1 Ensure that you have the electrostati...

Страница 517: ...ecting a cord from a power supply b Push tab A down of the power supply being serviced and pull it towards the direction of the arrow shown Keep pulling until the power supply slides out from the slot Power supplies 511 ...

Страница 518: ...d metal surface If not do so now 2 To replace the power supply complete the following steps a Pull the latch down on the power supply as shown in the following figure b Align the power supply with the bay and slide the power supply into the system as shown in the following figure Ensure that the pins on the latch go into the grooves in the chassis c Push the latch up to lock the power supply in pl...

Страница 519: ...Figure 447 Replacing a power supply d Connect the power cord to the power supply as shown in the following figure e Tuck the power cord into the chassis Power supplies 513 ...

Страница 520: ...lugged into a ground jack or connected to an unpainted metal surface If not do so now 2 If you chose to complete this repair with the power off using your labels reconnect the UPIC cables to the system control unit UPIC cable locations are P1 C1 T1 and P1 C2 T1 a Ensure that the white plastic lock is pulled back from the plug housing b Plug the UPIC cable A into the previously identified location ...

Страница 521: ...bles should be firmly attached to the system 3 If you powered off the system to complete this repair wait for the service processor comes up to the Flexible Service Processor FSP standby state the power on LED on the control panel is flashing slowly then continue to the next step to validate all of the cables If you did not power off the system skip the next step and continue to the step to valida...

Страница 522: ...PIC cables in the previous step You can skip this step a If you are already connected to the ASMI go to the next step Otherwise click All Systems then select system being serviced Then click Actions View All Actions Launch Advanced Systems Management ASM b In the navigation area expand System Service Aids Cable Plugging Validation Then click Validate UPIC Cables The system verifies that the UPIC c...

Страница 523: ...Figure 451 Installing the front cover 9 If applicable close the rack front door Power supplies 517 ...

Страница 524: ...518 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 525: ...ify LED on the enclosure to locate the system Ensure that the serial number of the system matches the serial number to be serviced 2 Stop the system For instructions see Stopping a system www ibm com support knowledgecenter POWER9 p9haj crustopsys htm 3 Open the rear rack door if necessary 4 Label and disconnect both UPIC cables from the system control unit UPIC cable locations are P1 C1 T1 and P1...

Страница 526: ...eiving electric shock when using or working on electrical equipment If you do not have an ESD wrist strap just prior to removing the product from ESD packaging and installing or replacing hardware touch an unpainted metal surface of the system for a minimum of 5 seconds If at any point in this service process you move away from the system it is important to again discharge yourself by touching an ...

Страница 527: ...following figure Notes This system node might be equipped with two or more power supplies If the removing and replacing procedures require the system power to be turned off ensure that all power sources to the system node are disconnected Figure 454 Removing the rear power cords Processor VRM 521 ...

Страница 528: ... L003 or or or or 522 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 529: ...and power cables L003 b Label and disconnect all of the PCIe cables or transceivers that are attached to the PCIe adapters for the system node you are servicing Use hook and loop fasteners to hold the PCIe cables in place c Label and unplug both service processor FSP cables B from the system node being serviced using the pull tab A attached to the connector Processor VRM 523 ...

Страница 530: ...stem node d Label and unplug the UPIC cables for the system node that you are servicing if applicable 1 Remove the white plastic lock A from the plug housing as shown in the following figure 524 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 531: ...Figure 456 Removing the UPIC cable lock 2 Push down on the blue cable latch B and pull out the UPIC cable from the system node as shown in the following figure Processor VRM 525 ...

Страница 532: ...or more slack in the SMP cables label and unclip the SMP cable bundle from the side of the cable management bracket as shown in the following figure and move the SMP cables to near the center of the system node 526 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 533: ...s on the cable If the metal connectors are bent or damaged they need to be replaced 1 Slightly push in the cable bundle A as shown in the following figure to relieve the spring pressure of the cable connector 2 Pull the blue latch B as shown in the following figure to release the inner cable latch 3 Remove the SMP cable C from the system node Processor VRM 527 ...

Страница 534: ...tem node use hook and loop fasteners to connect the cables to the cable management bracket so the cables do not hang loosely h If you are servicing system node ND1 or ND2 label and unplug the USB cable as shown in the following figure 528 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 535: ...Figure 460 Removing the USB cable from the system node i If present remove the two screws A at the rear of the system as shown in the following figure Processor VRM 529 ...

Страница 536: ...igure 461 Removing the rear screws j If present remove the four screws A at the front of the system as shown in the following figure 530 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 537: ...front screws k Release the side latches B for the system node by pressing them downward and then pulling outward as shown in the following figure l Pull out the system node C as shown in the following figure Processor VRM 531 ...

Страница 538: ...For proper cooling and airflow replace the cover before turning on the system a Push the release latch A in the direction shown in the following figure b Slide the cover B off the system unit as shown in the following figure When the service access cover has cleared the upper frame ledge lift the cover up and off the system unit 532 Power Systems Removing and replacing parts in the 9080 M9S system...

Страница 539: ...on the trusted platform module card as shown in the following figure Verify that the green LED A is lit which indicates that sufficient power exists to light the identify LED on the faulty part If the green LED A does not light use the location code on the service label to find the physical location of the faulty part Processor VRM 533 ...

Страница 540: ...r the flashing amber LED of the faulty or failed processor voltage regulator module Processor voltage regulator modules are in locations P1 C14 P1 C17 P1 C18 and P1 C21 Refer to the following image 534 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 541: ...ctrostatic discharge ESD wrist strap on and that the ESD clip is plugged into a ground jack or connected to an unpainted metal surface If not do so now 2 Remove a processor voltage regulator module by completing the following steps a Unlock the levers A to release the voltage regulator module from its connector Refer to the following image b Rotate the levers in the direction shown c While holding...

Страница 542: ...o an unpainted metal surface If not do so now 2 To replace a processor voltage regulator module complete the following steps a With the levers A in the open position hold the voltage regulator module by its levers and lower the voltage regulator module into its slot in the system Refer to the following image b Gently push the voltage regulator module into its connector c Rotate the levers in the d...

Страница 543: ... the steps in this procedure Procedure 1 Ensure that you have the electrostatic discharge ESD wrist strap on and that the ESD clip is plugged into a ground jack or connected to an unpainted metal surface If not do so now 2 Replace the service access cover by completing the following steps a Slide the cover A onto the system unit as shown in the following figure b Close the release latch B by pushi...

Страница 544: ...ck to ensure that your fingers do not get caught in the side rails a Unlock the blue rail safety latches A by pushing them towards the front as shown in the following figure b Push the system node back into the rack as shown in the following figure until both system node release latches lock into position 538 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 545: ...Figure 470 Placing the system node into the operating position c Replace the two screws A at the rear of the system if you removed them earlier as shown in the following figure Processor VRM 539 ...

Страница 546: ...Figure 471 Replacing the rear screws d Replace the four screws A at the front of the system node as shown in the following figure 540 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 547: ...system node that you are servicing Then refer to your labels and the following steps to reconnect the SMP cables that you removed from the system node you are servicing If you have a two node system configuration use Figure 473 on page 542 and Table 55 on page 542 to determine the point to point cabling for SMP cables Processor VRM 541 ...

Страница 548: ...ram represents a pair of SMP cables Cable Cable type and length From To 5C 880 mm 2 9 ft ND1 P1 T1 ND2 P1 T1 5D 880 mm 2 9 ft ND1 P1 T2 ND2 P1 T2 6C 1005 mm 3 3 ft ND1 P1 T7 ND2 P1 T7 6D 1005 mm 3 3 ft ND1 P1 T8 ND2 P1 T8 5A 1005 mm 3 3 ft ND1 P1 T9 ND2 P1 T9 542 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 549: ...W 1225 mm 4 01 ft ND1 P1 T17 ND2 P1 T17 6X 1225 mm 4 01 ft ND1 P1 T18 ND2 P1 T18 5W 1005 mm 3 3 ft ND1 P1 T23 ND2 P1 T23 5X 1005 mm 3 3 ft ND1 P1 T24 ND2 P1 T24 6Y 1005 mm 3 3 ft ND1 P1 T25 ND2 P1 T25 6Z 1005 mm 3 3 ft ND1 P1 T26 ND2 P1 T26 5Y 880 mm 2 9 ft ND1 P1 T31 ND2 P1 T31 5Z 880 mm 2 9 ft ND1 P1 T32 ND2 P1 T32 If you have a three node system configuration use Figure 474 on page 544 and Tabl...

Страница 550: ...ing a Three Node Configuration Table 56 Cabling a Three Node Configuration Cable Cable type and length From To 5C 880 mm 2 9 ft ND3 P1 T1 ND2 P1 T1 544 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 551: ...5 mm 4 01 ft ND3 P1 T15 ND1 P1 T9 3B 1225 mm 4 01 ft ND3 P1 T16 ND1 P1 T10 3W 1225 mm 4 01 ft ND3 P1 T17 ND1 P1 T23 3X 1225 mm 4 01 ft ND3 P1 T18 ND1 P1 T24 5W 1005 mm 3 3 ft ND3 P1 T23 ND2 P1 T23 5X 1005 mm 3 3 ft ND3 P1 T24 ND2 P1 T24 3Y 1225 mm 4 01 ft ND3 P1 T25 ND1 P1 T31 3Z 1225 mm 4 01 ft ND3 P1 T26 ND1 P1 T32 5Y 880 mm 2 9 ft ND3 P1 T31 ND2 P1 T31 5Z 880 mm 2 9 ft ND3 P1 T32 ND2 P1 T32 6C ...

Страница 552: ...25 mm 4 01 ft ND2 P1 T17 ND1 P1 T17 6X 1225 mm 4 01 ft ND2 P1 T18 ND1 P1 T18 6Y 1005 mm 3 3 ft ND2 P1 T25 ND1 P1 T25 6Z 1005 mm 3 3 ft ND2 P1 T26 ND1 P1 T26 If you have a four node system configuration use Figure 475 on page 547 and Table 57 on page 548 to determine the point to point cabling for SMP cables 546 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 553: ...Figure 475 Cabling a Four Node Configuration Processor VRM 547 ...

Страница 554: ...8 ND1 P1 T4 2A 1225 mm 4 01 ft ND4 P1 T9 ND2 P1 T11 2B 1225 mm 4 01 ft ND4 P1 T10 ND2 P1 T12 4A 1005 mm 3 3 ft ND4 P1 T11 ND3 P1 T11 4B 1005 mm 3 3 ft ND4 P1 T12 ND3 P1 T12 1A 1625 mm 5 3 ft ND4 P1 T15 ND1 P1 T11 1B 1625 mm 5 3 ft ND4 P1 T16 ND1 P1 T12 1W 1625 mm 5 3 ft ND4 P1 T17 ND1 P1 T21 1X 1625 mm 5 3 ft ND4 P1 T18 ND1 P1 T22 4W 1005 mm 3 3 ft ND4 P1 T21 ND3 P1 T21 4X 1005 mm 3 3 ft ND4 P1 T2...

Страница 555: ...1 T30 2Y 1225 mm 4 01 ft ND4 P1 T31 ND2 P1 T29 2Z 1225 mm 4 01 ft ND4 P1 T32 ND2 P1 T30 Cables originating on ND3 5C 880 mm 2 9 ft ND3 P1 T1 ND2 P1 T1 5D 880 mm 2 9 ft ND3 P1 T2 ND2 P1 T2 3C 1225 mm 4 01 ft ND3 P1 T7 ND1 P1 T1 3D 1225 mm 4 01 ft ND3 P1 T8 ND1 P1 T2 5A 1005 mm 3 3 ft ND3 P1 T9 ND2 P1 T9 5B 1005 mm 3 3 ft ND3 P1 T10 ND2 P1 T10 3A 1225 mm 4 01 ft ND3 P1 T15 ND1 P1 T9 3B 1225 mm 4 01 ...

Страница 556: ...1 ft ND2 P1 T15 ND1 P1 T15 6B 1225 mm 4 01 ft ND2 P1 T16 ND1 P1 T16 6W 1225 mm 4 01 ft ND2 P1 T17 ND1 P1 T17 6X 1225 mm 4 01 ft ND2 P1 T18 ND1 P1 T18 6Y 1005 mm 3 3 ft ND2 P1 T25 ND1 P1 T25 6Z 1005 mm 3 3 ft ND2 P1 T26 ND1 P1 T26 a Press the SMP cable and the blue tab together with your fingers and thumb to hold the SMP cable Plug the SMP cable into the previously identified location in the system...

Страница 557: ...ll the SMP cables previously identified are reconnected to the system node you are servicing c If you removed any SMP cable clips from the side of the rack using your labels reattach the cable bundle to the side of the cable management bracket as shown in the following figure Processor VRM 551 ...

Страница 558: ...rmation card inserted into the rear of the system control unit You can also refer to the following figures The number in the cable label indicates the bundle for that cable Two system node configuration The two system node configuration has four cable bundles 552 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 559: ...le attaches to the clip C Three system node configuration The three system node configuration has four cable bundles Figure 479 Bundling and connecting SMP cables for three system nodes Two bundles named B3 with the 3 cables The left B3 bundle contains 3A 3B 3C and 3D This bundle attaches to the clip A The right B3 bundle contains 3W 3X 3Y and 3Z This bundle attaches to the clip F Two bundles name...

Страница 560: ... This bundle attaches to the clips J Two bundles named B4 with the 4 cables The left B4 bundle contains 4A 4B 4C and 4D This bundle attaches to the clip D The right B4 bundle contains 4W 4X 4Y and 4Z This bundle attaches to the clip G Two bundles named B5 with the 5 cables The left B5 bundle contains 5A 5B 5C and 5D This bundle attaches to the clip E The right B5 bundle contains 5W 5X 5Y and 5Z Th...

Страница 561: ...igure 481 Single Node Configuration UPIC Cabling Table 58 Single Node Configuration UPIC Cabling Cable number From To 1 SC1 P1 C1 T1 ND1 P1 C9 T1 2 SC1 P1 C2 T1 ND1 P1 C10 T1 If you have a two three or four node system configuration use Figure 482 on page 556 and Table 59 on page 556 to determine the point to point cabling for UPIC cables Processor VRM 555 ...

Страница 562: ...replace the UPIC cable in the system node complete the following steps 1 Ensure that the white plastic lock is pulled back from the plug housing 2 Plug the UPIC cable A into the previously identified location in the system node by inserting the cable into the connector until it locks into place as shown in the following figure 556 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 563: ...Figure 483 Replacing the UPIC cable into the system node 3 Push the white plastic lock B onto the plug housing as shown in the following figure Processor VRM 557 ...

Страница 564: ...attached to the system b Repeat step 5 a on page 556 until all the UPIC cables previously identified are reconnected to the system node you are servicing c If applicable secure the cable to the side of the rack with the hook and loop fastener 6 Using your labels reconnect the service processor FSP cables that you removed from the system node you are servicing 558 Power Systems Removing and replaci...

Страница 565: ...Figure 485 Service processor FSP cabling Processor VRM 559 ...

Страница 566: ... P1 T3 ND1 P1 C9 T2 B 355 mm 1 16 ft SC1 P1 T5 ND1 P1 C10 T2 7 Review the following information to identify the locations where the USB cable connects to the system node that you are servicing and to the system control unit Then reconnect the USB cable that you removed Figure 486 USB Cabling Table 61 USB Cabling From To ND1 or ND2 P1 C13 T3 SC1 P1 T1 a Plug the USB cable into the previously identi...

Страница 567: ...ing the USB cable into the system node b Plug the USB cable into the previously identified location in the system control unit by inserting the cable into the connector as shown in the following figure Processor VRM 561 ...

Страница 568: ...USB cable into the system control unit 8 Using your labels reconnect the rear power cords to the system node being serviced as shown in the following figure 562 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 569: ...trol unit UPIC cable locations are P1 C1 T1 and P1 C2 T1 a Ensure that the white plastic lock is pulled back from the plug housing b Plug the UPIC cable A into the previously identified location in the system control unit by inserting the cable into the connector until it locks into place Processor VRM 563 ...

Страница 570: ...tached to the system 10 When the service processor comes up to the Flexible Service Processor FSP standby state the power on LED on the control panel is flashing slowly continue to the next step 11 Access the ASMI and run the Cable Plugging Validation utility to validate all of the cables a If you are already connected to the ASMI go to the next step Otherwise click All Systems then select system ...

Страница 571: ...alidation Then select All of the above in the Display Cable Status section and click Continue The system validates that the cables are installed in the correct locations Expand System Service Aids Cable Plugging Validation to display a table with the results Ensure that the plugging status is OK for each cable in the displayed table If the status is OK no further action is required If the status i...

Страница 572: ...566 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 573: ...level of server firmware in the upper right corner under the copyright statement for example 01EM310 or FW760 00 AM760_019 2 Check and record the following service processor card settings System Name System Power Control System Service Aids System Configuration Network Services Performance Option Login Profile 3 Locate the amber LED for the failed service processor card as shown in the following f...

Страница 574: ...procedures An ESD wrist strap is used for static control It does not increase or decrease your risk of receiving electric shock when using or working on electrical equipment If you do not have an ESD wrist strap just prior to removing the product from ESD packaging and installing or replacing hardware touch an unpainted metal surface of the system for a minimum of 5 seconds If at any point in this...

Страница 575: ... A to the right as shown in the following figure b Hold on to the handle and by using your hand to support the bottom of the service processor card pull out the service processor card from its slot as shown in the following figure Figure 493 Removing the service processor card Replacing the service processor card in the 9080 M9S system control unit Procedure 1 Ensure that you have the electrostati...

Страница 576: ...gure 494 Resetting the service processor card b Ensure that the handle A for the service processor card is open as shown in the following figure c Hold on to the handle and by using your hand to support the bottom of the service processor card push the service processor card into its slot as shown in the following figure d Push the handle A in the direction shown in the following figure e Continue...

Страница 577: ...e processor card 3 Remove the cover for the time of day battery as shown in the following figure by pinching in on the blue plastic cover at A then by pulling the cover away from the service processor card Service processor cards 571 ...

Страница 578: ...Remove the protective plastic insulator B from the time of day battery to allow the time of day battery to make contact with the service processor card as shown in the following figure 572 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 579: ...ic insulator 5 Align the bottom tabs of the time of day battery cover in the two slots under the battery as shown in the following figure Roll the battery cover up and secure the cover to the service processor card Service processor cards 573 ...

Страница 580: ... FSP standby state the power on LED on the control panel is flashing slowly then continue to the next step to validate all of the cables If you did not power off the system skip the next step and continue to the step to validate only the UPIC cables 4 Access the ASMI and run the Cable Plugging Validation utility to validate all of the cables a If you are already connected to the ASMI go to the nex...

Страница 581: ...click Validate UPIC Cables The system verifies that the UPIC cables are present Note Older firmware levels do not support validating the UPIC cables while the system is at FSP standby You can skip this step if it is not available c Expand System Service Aids Cable Plugging Validation In the Display Cable Status section select UPIC Cables and click Continue The system validates that the UPIC cables...

Страница 582: ...used for static control It does not increase or decrease your risk of receiving electric shock when using or working on electrical equipment If you do not have an ESD wrist strap just prior to removing the product from ESD packaging and installing or replacing hardware touch an unpainted metal surface of the system for a minimum of 5 seconds If at any point in this service process you move away fr...

Страница 583: ...lue cable latch B and pull out the UPIC cable from the system control unit Figure 501 Removing the UPIC cable from the system control unit 6 Place your fingers on the indentations located on both sides of the cover A and pull the cover away from the system as shown in the following figure Service processor cards 577 ...

Страница 584: ...e removed with the system operating ensure that all such loose material is secured away from the fan area to prevent any loose material from being pulled into the fan Figure 502 Removing the front cover 7 Disconnect all of the front power cords that plug into the power supplies of the system node that is being serviced 578 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 585: ... ESD clip is plugged into a ground jack or connected to an unpainted metal surface If not do so now 2 To remove a service processor interface card complete the following steps a For the service processor interface card that has the amber LED on pull the blue service processor interface card handle latch A to the right as shown in the following figure b Hold on to the service processor interface ca...

Страница 586: ... so now 2 To replace a service processor interface card complete the following steps a Ensure that the service processor interface card handle A is open as shown in the following figure b Hold on to the service processor interface card handle and by using your hand to support the bottom of the service processor interface card push the service processor interface card into its slot as shown in the ...

Страница 587: ... complete the steps in this procedure Procedure 1 Ensure that you have the electrostatic discharge ESD wrist strap on and that the ESD clip is plugged into a ground jack or connected to an unpainted metal surface If not do so now 2 Using your labels reconnect the cables for the service processor interface card that you replaced 3 Connect all of the front power cords that plug into the power suppli...

Страница 588: ...over A on the front of the system unit as shown in the following figure so that the four pins B on the system match the four holes at the rear of the cover Press the front cover into position 582 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 589: ...les to the system control unit UPIC cable locations are P1 C1 T1 and P1 C2 T1 a Ensure that the white plastic lock is pulled back from the plug housing b Plug the UPIC cable A into the previously identified location in the system control unit by inserting the cable into the connector until it locks into place Service processor cards 583 ...

Страница 590: ...ched to the system 6 If you powered off the system to complete this repair wait for the service processor comes up to the Flexible Service Processor FSP standby state the power on LED on the control panel is flashing slowly then continue to the next step to validate all of the cables If you did not power off the system skip the next step and continue to the step to validate only the UPIC cables 7 ...

Страница 591: ...nd d as needed until the status is OK for all cables e Exit the ASMI and skip the following step 8 Access the ASMI and run the Cable Plugging Validation utility to validate only the UPIC cables Note If you powered off the system to complete this repair you validated the UPIC cables in the previous step You can skip this step a If you are already connected to the ASMI go to the next step Otherwise ...

Страница 592: ...586 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 593: ...ugged into a ground jack or connected to an unpainted metal surface If not do so now 2 At the rear of the system control unit use a T15 Torx screwdriver to loosen the two captive screws A as shown in the following figure Figure 510 Loosening the screws and removing the system backplane 3 Hold on to one side of the bulkhead and use your other hand to support the bottom of the system backplane as yo...

Страница 594: ...ack or connected to an unpainted metal surface If not do so now 2 Remove the new system backplane from its packaging 3 Support the bottom of the system backplane as you slide the backplane into the rear of the chassis as shown in the following figure Figure 511 Replacing the system backplane and tightening the screws 4 At the rear of the system control unit use a T15 Torx screwdriver to tighten th...

Страница 595: ...c discharge ESD mat Service representative tool kit which includes tweezers 4 mm T handle Allen wrench T10 Torx bit T15 Torx bit in hex driver to in square socket adapter driver in driver with 6 in extension in ratchet driver and in driver handle Procedure 1 Ensure that you have the electrostatic discharge ESD wrist strap on and that the ESD clip is plugged into a ground jack or connected to an un...

Страница 596: ...e cards in the tray one row at a time in the order in which you remove the cards you do not need to label each card When you replace the cards install them row by row in the order that you placed them in the tray e Repeat steps 2 a on page 589 through 2 d on page 590 to remove all of the cards in the row inside the system that is nearest the fans 3 Remove the memory modules from locations P1 C22 t...

Страница 597: ...he remaining memory modules or fillers 4 Remove the processor voltage regulator modules from locations P1 C14 P1 C17 P1 C18 and P1 C21 a Unlock the levers A to release the voltage regulator module from its connector Refer to the following image b Rotate the levers in the direction shown c While holding the voltage regulator module by its levers pull upward to remove the card from its slot d Place ...

Страница 598: ... regulator modules 5 Remove the heat sinks and system processor modules one at a time L007 CAUTION A hot surface nearby L007 a Loosen the heat sink actuation screw by turning the supplied hex key counterclockwise A Loosen the screw until it moves freely Refer to the following figure 592 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 599: ...g upward Note If you plan to remove dust or debris from the heat sink this operation must be performed in another room that is greater than 7 6 m 24 9 ft away from the work area c Using the supplied tweezers remove the TIM from the top of the processor and place it in a clean dry area as shown in the following figure Be careful not to damage the TIM as it is very light and fragile System backplane...

Страница 600: ...ule d Open the system processor module packaging which was included with the replacement system backplane kit e Place the system processor module package cover upside down next to the tray 594 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 601: ... processor module package cover upside down f Ensure that the removal tool A is in the open position as shown in the following figure The middle ring B must be pushed down and blue tabs C must be turned inward System backplanes 595 ...

Страница 602: ...edge on the tool aligns with the beveled edge of the processor C as shown in the following figure h Lower the tool over the system processor module Ensure that the two guide pins A insert into the alignment holes B on each side of the tool as shown in the following figure 596 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 603: ...on the ring A slightly so that the blue tabs B snap outward and the jaws engage with the system processor module as shown in the following figure Make sure that both of the tool jaws are locked onto the system processor module by pushing down on the tool Important Do not press the blue release ring until directed to do so later System backplanes 597 ...

Страница 604: ...ack into the socket of the system processor module If the system processor module falls back into the socket of system processor module the pins may be damaged Place the system processor module at an angle on the top cover of the packaging as shown in the following figure Setting the tool and system processor module at an angle on the top cover of the system processor module packaging makes it eas...

Страница 605: ...hile pushing the blue tabs C inwards as shown in the following figure Ensure that the ring catches the openings on the blue tabs and that the blue tabs are locked in a fixed position To prevent the system processor module from falling pull up on the round lever before you place the tool on the top cover of the system processor module packaging System backplanes 599 ...

Страница 606: ...2 through 5 k on page 599 to remove each heat sink and system processor module one at a time 6 Remove the chassis a Use a T15 Torx driver to remove eight screws from each side of the chassis as shown in the following figures 600 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 607: ...Figure 523 Removing the screws from the side of the chassis b Use a T15 Torx driver to remove the four front screws near the fan slots as shown in the following figure System backplanes 601 ...

Страница 608: ...524 Removing the screws from the front of the chassis c Use a T15 Torx driver to remove two screws from the front of the top of the chassis 602 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 609: ...Figure 525 Removing the screws from the top of the chassis d Lift the chassis straight up away from the system backplane and set the chassis aside until you are ready to replace it System backplanes 603 ...

Страница 610: ...instructions assume two people are performing the removal If you re using a lift tool refer to the lift tool documentation for instructions to use the lift tool a Pull the release latch A on each rail b As you carefully lift the system backplane off the rails keep the back end low and the front end high Figure 527 Lifting the system backplane off the rails 604 Power Systems Removing and replacing ...

Страница 611: ...plane on an appropriate ESD surface 8 Remove both slam latch bracket assemblies from the system backplane by loosening the flat head screws A with a T15 Torx screwdriver as shown in the following figure System backplanes 605 ...

Страница 612: ...f you re using a lift tool refer to the lift tool documentation for instructions to use the lift tool System backplane kit which includes a tray in which you can place the parts as you remove them Note If your system backplane kit does not include a tray you can also place the parts on a large electrostatic discharge ESD mat Service representative tool kit which includes tweezers 4 mm T handle All...

Страница 613: ...29 Replacing the slam latch assemblies 4 Install the new system backplane Remember The system backplane requires two people or a lift tool to install it These instructions assume two people are performing the installation If you re using a lift tool refer to the lift tool documentation for instructions to use the lift tool a Extend the slide rails from the rack if needed b As you carefully lower t...

Страница 614: ... pins d As you continue lowering the front of the system backplane into the rails the middle and front guide pins drop into the slide rail slots You might find it helpful to hold the slide rails tightly against the system backplane so that the pins will be seated flush with the rail slots 5 Replace the chassis a Lower the chassis straight down over the system backplane 608 Power Systems Removing a...

Страница 615: ...re 531 Lowering the chassis over the system backplane b Use a T15 Torx driver to replace two screws in the top of the chassis Figure 532 Replacing the screws in the top of the chassis System backplanes 609 ...

Страница 616: ...c Use a T15 Torx driver to replace four front screws near the fan slots as shown in the following figure 610 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 617: ...screws in the front of the chassis d Use a T15 Torx driver to replace eight screws from each side of the chassis as shown in the following figures Figure 534 Replacing the screws in the side of the chassis System backplanes 611 ...

Страница 618: ...diately install a system processor module in each socket a Grasp the latches on both sides of the socket dust cover and squeeze them inwards until the latches release from the pins on the system backplane See the following figure b Lift the socket dust cover straight up as shown in the following figure Set the dust cover aside 612 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 619: ...from the original system backplane in the exposed socket on the new system backplane a Lower the tool over the system processor module on the top cover of the packaging as shown in the following figure Ensure that the beveled edge on the tool aligns with the beveled edge of the processor Ensure that the two guide pins A are inserted into the alignment holes B on each side of the tool System backpl...

Страница 620: ... that the blue tabs B snap outward and the jaws engage with the system processor module C as shown in the following figure Make sure that both of the tool jaws are locked onto the system processor module by pushing down on the tool Important Do not press the blue release tabs until directed to do so later 614 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 621: ...e tool with the beveled corner on the socket Align the guide pins A with the alignment holes B on each side of the tool Use care to lower the tool evenly without tilting the tool Refer to the following figure Note Do not attempt to slide the tool and the system processor module in any direction while the system processor module is touching the socket If the tool and the system processor module are...

Страница 622: ...le e Open the latches that hold the system processor module in the supplied removal tool A as shown in the following figure Push down on the ring B while pressing in on the tabs C 616 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 623: ...he following figure The thermal interface material TIM is typically adhered to the heat sink Unless damaged the TIM that is adhered to the heat sink can be reused The previous TIM needs to be perfectly flat to be reused If the TIM is damaged torn wrinkled or if you are unsure do not reuse the removed heat sink Ensure that you have a spare TIM and heat sink on hand System backplanes 617 ...

Страница 624: ...g Carefully remove the TIM holding it by the edges of the carrier strip and holding it away from the shipping container j Remove the protective film from the clear carrier strip by using the supplied tweezers Note The TIM must remain flat Small wrinkles are acceptable but folds are not acceptable k Using the tweezers remove the TIM from the carrier strip and center it onto the system processor mod...

Страница 625: ...s move the old processor s TIM from the clean dry surface and center it onto the new system processor module Then continue to step 7 m on page 620 The TIM has no preferred up side The TIM can be placed on the processor and centered as shown in the following figure System backplanes 619 ...

Страница 626: ...Figure 542 Moving the TIM onto the processor m Place the heat sink on the TIM as shown in the following figure 620 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 627: ...nter load screw clockwise by using the supplied hex key as shown by B in the following figure until a firm stop is reached If the heat sink moves noticeably the load arms are not engaged Unscrew the center load screw and repeat this step again System backplanes 621 ...

Страница 628: ...l the socket dust covers on the original system backplane The socket dust covers protect the sockets during shipping a Lower the socket dust cover over one of the sockets on the system backplane and ensure that the holes B on the socket dust cover align with the two guide pins A on the system backplane Push straight down until the latches D on the socket dust cover engage with the latches C on the...

Страница 629: ...em in the same order in which you placed them in the tray a With the levers A in the open position hold the voltage regulator module by its levers and lower the voltage regulator module into its slot in the system Refer to the following image b Gently push the voltage regulator module into its connector c Rotate the levers in the direction shown and press down on the latches to secure the voltage ...

Страница 630: ... Attention Memory modules are keyed to prevent a memory module from being installed incorrectly Note the location of the key tab within the memory module connector before you attempt to install the memory module b Replace the memory module by pushing it into slot until the tabs A lock into place as shown in the following figure c Repeat steps 11 a on page 624 through 11 b on page 624 to replace th...

Страница 631: ... placed them in the tray This row includes seven memory voltage regulator modules four miscellaneous A voltage regulator modules one miscellaneous B voltage regulator module two power APSS and TPM cards and the concurrent maintenance circuit card in locations P1 C54 through P1 C68 a With the levers A in the open position hold the card by the levers and lift it from the ESD tray System backplanes 6...

Страница 632: ...ard with levers in the open position b Continue holding the card by the levers and lower the card into its slot in the system Refer to the following image 626 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 633: ... nearest the fans c Gently push the card into its connector d Rotate the levers in the direction that is shown and press down on the latches to secure the card in its slot e Repeat these steps to replace all of the cards System backplanes 627 ...

Страница 634: ...628 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 635: ...module Thermal interface material TIM Tweezers Putty knife Heat sink 4MM T handle Allen wrench Procedure 1 Label and disconnect both UPIC cables from the system control unit UPIC cable locations are P1 C1 T1 and P1 C2 T1 a Remove the white plastic lock A from the plug housing Figure 550 Removing the UPIC cable lock b Push down on the blue cable latch B and pull out the UPIC cable from the system c...

Страница 636: ...at a time The rack might become unstable if you pull out more than one drawer at a time a Label and disconnect the rear power cords from the system node being serviced as shown in the following figure Notes This system node might be equipped with two or more power supplies If the removing and replacing procedures require the system power to be turned off ensure that all power sources to the system...

Страница 637: ...Figure 552 Removing the rear power cords L003 or or System processor module 631 ...

Страница 638: ...hazardous voltages disconnect all power cords and power cables L003 b Label and disconnect all of the PCIe cables or transceivers that are attached to the PCIe adapters for the system node you are servicing Use hook and loop fasteners to hold the PCIe cables in place 632 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 639: ...ab A attached to the connector Figure 553 Removing the service processor cable from the system node d Label and unplug the UPIC cables for the system node that you are servicing if applicable 1 Remove the white plastic lock A from the plug housing as shown in the following figure System processor module 633 ...

Страница 640: ...oving the UPIC cable lock 2 Push down on the blue cable latch B and pull out the UPIC cable from the system node as shown in the following figure 634 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 641: ... If needed to allow for more slack in the SMP cables label and unclip the SMP cable bundle from the side of the cable management bracket as shown in the following figure and move the SMP cables to near the center of the system node System processor module 635 ...

Страница 642: ...l connectors are bent or damaged they need to be replaced 1 Slightly push in the cable bundle A as shown in the following figure to relieve the spring pressure of the cable connector 2 Pull the blue latch B as shown in the following figure to release the inner cable latch 3 Remove the SMP cable C from the system node 636 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 643: ... SMP cables for a system node use hook and loop fasteners to connect the cables to the cable management bracket so the cables do not hang loosely h If you are servicing system node ND1 or ND2 label and unplug the USB cable as shown in the following figure System processor module 637 ...

Страница 644: ...8 Removing the USB cable from the system node i If present remove the two screws A at the rear of the system as shown in the following figure 638 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 645: ...Figure 559 Removing the rear screws j If present remove the four screws A at the front of the system as shown in the following figure System processor module 639 ...

Страница 646: ... side latches B for the system node by pressing them downward and then pulling outward as shown in the following figure l Pull out the system node C as shown in the following figure 640 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 647: ...or static control It does not increase or decrease your risk of receiving electric shock when using or working on electrical equipment If you do not have an ESD wrist strap just prior to removing the product from ESD packaging and installing or replacing hardware touch an unpainted metal surface of the system for a minimum of 5 seconds If at any point in this service process you move away from the...

Страница 648: ...ess cover 5 To activate the identify LED for the faulty part press and hold either blue push button on the trusted platform module card as shown in the following figure Verify that the green LED A is lit which indicates that sufficient power exists to light the identify LED on the faulty part If the green LED A does not light use the location code on the service label to find the physical location...

Страница 649: ...for the failed system processor module Make a note of which location is flashing that indicates the system processor module to replace The following figure shows the locations of the system processor module LEDs Record the location of the identifying LED System processor module 643 ...

Страница 650: ... and that the ESD clip is plugged into a ground jack or connected to an unpainted metal surface If not do so now 2 Open the packaging of the new system processor module and place the cover upside down next to the tray as shown in Figure 565 on page 645 The cover is used for the system processor module that you are replacing 644 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 651: ... wrench counterclockwise A Loosen the screw until it moves freely See Figure 566 on page 646 b Grip the heat sink B on opposing sides and remove the heat sink by lifting it upward Set the heat sink aside with the module side facing upward Note If you plan to remove dust or debris from the heat sink this operation must be performed in another room that is greater than 7 6 m 24 9 ft away from the wo...

Страница 652: ...emoval by completing the following steps a Ensure that the removal tool A is in the open position as shown in Figure 567 on page 647 The middle ring B must be pushed down and blue tabs C must be turned inward 646 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 653: ...the beveled edge on the tool aligns with the beveled edge of the system processor module C as shown in Figure 568 on page 648 c Lower the tool over the system processor module Ensure that the two guide pins A insert into the alignment holes B on each side of the tool as shown in Figure 568 on page 648 System processor module 647 ...

Страница 654: ... that the blue tabs B snap outward and the jaws engage with the system processor module as shown in Figure 569 on page 649 Make sure that both of the tool jaws are locked onto the system processor module by pushing down on the tool Important Do not press the blue release ring until directed to do so later 648 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 655: ...disengage and fall back into the socket of the system processor module If the system processor module falls back into the socket of system processor module the pins may be damaged Place the system processor module at an angle on the top cover of the packaging as shown in Figure 570 on page 650 Setting the tool and system processor module at an angle on the top cover of the system processor module ...

Страница 656: ...s C inwards as shown in Figure 571 on page 651 Ensure that the ring catches the openings on the blue tabs and that the blue tabs are locked in a fixed position To prevent the system processor module from falling pull up on the round lever before you place the tool on the top cover of the system processor module packaging 650 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 657: ...arge ESD wrist strap on and that the ESD clip is plugged into a ground jack or connected to an unpainted metal surface If not do so now 2 Prepare the system processor module for installation a Ensure that the removal tool is in the open position as shown in Figure 572 on page 652 The middle ring must be pushed down and blue tabs must be turned inward System processor module 651 ...

Страница 658: ...module as shown in Figure 573 on page 653 Ensure that the beveled edge on the tool aligns with the beveled edge of the system processor module Ensure that the two guide pins A are inserted into the alignment holes B on each side of the tool 652 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 659: ...e ring A slightly so that the blue tabs B snap outward and the jaws engage with the system processor module C as shown in Figure 574 on page 654 Make sure that both of the tool jaws are locked onto the system processor module by pushing down on the tool Important Do not press the blue release tabs until directed to do so later System processor module 653 ...

Страница 660: ... module a If dust or debris is present on the system processor socket use the supplied air pump to clean the socket Blow small bursts of air from the center toward the sides of the socket as shown in Figure 575 on page 655 654 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 661: ...veled corner on the socket Align the guide pins A with the alignment holes B on each side of the tool Use care to lower the tool evenly without tilting the tool See Figure 576 on page 656 Note Do not attempt to slide the tool and the system processor module in any direction while the system processor module is touching the socket If the tool and the system processor module are not aligned with the...

Страница 662: ...e d Open the latches that hold the system processor module in the supplied removal tool A as shown in Figure 577 on page 657 Push down on the ring B while pressing in on the tabs C 656 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 663: ...ng the system processor module tool e Lift the tool off the system processor module 4 Inspect the thermal interface material TIM for visible signs of damage as shown in Figure 578 on page 658 System processor module 657 ...

Страница 664: ...ing heat sink a Open the TIM packaging and carefully remove the TIM holding it by the edges of the carrier strip and holding it away from the shipping container b Remove the protective film from the clear carrier strip by using the supplied tweezers Note The TIM must remain flat Small wrinkles are acceptable but folds are not acceptable c Using the tweezers remove the TIM from the carrier strip an...

Страница 665: ...Figure 579 Installing a new TIM onto the system processor module d Place the heat sink on the TIM as shown in Figure 580 on page 660 System processor module 659 ...

Страница 666: ... Using the tweezers move the old processor s TIM from the clean dry surface and center it onto the new system processor module The TIM has no preferred up side The TIM can be placed on the processor and centered as shown in Figure 581 on page 661 660 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 667: ...Figure 581 Moving the TIM onto the processor b Place the heat sink on the TIM as shown in Figure 582 on page 662 System processor module 661 ...

Страница 668: ...n by A in Figure 583 on page 663 b Tighten the center load screw clockwise by using the supplied 4MM T handle Allen wrench as shown by B in Figure 583 on page 663 until a firm stop is reached If the heat sink moves noticeably the load arms are not engaged Unscrew the center load screw and repeat this step again 662 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 669: ...ocessor module that you replaced by the edges and lift it off of the packaging cover Align the beveled corner of the module A to the corner of the packaging with triangle B and place it in the packaging as shown in Figure 584 on page 664 Close the packaging cover System processor module 663 ...

Страница 670: ...D wrist strap on and that the ESD clip is plugged into a ground jack or connected to an unpainted metal surface If not do so now 2 Replace the service access cover by completing the following steps a Slide the cover A onto the system unit as shown in the following figure b Close the release latch B by pushing it in the direction shown in the following figure 664 Power Systems Removing and replacin...

Страница 671: ...de slowly into the rack to ensure that your fingers do not get caught in the side rails a Unlock the blue rail safety latches A by pushing them towards the front as shown in the following figure b Push the system node back into the rack as shown in the following figure until both system node release latches lock into position System processor module 665 ...

Страница 672: ... system node into the operating position c Replace the two screws A at the rear of the system if you removed them earlier as shown in the following figure 666 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 673: ...Figure 587 Replacing the rear screws d Replace the four screws A at the front of the system node as shown in the following figure System processor module 667 ...

Страница 674: ...eplacing the front screws 4 Using your labels reconnect the rear power cords to the system node being serviced as shown in the following figure 668 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 675: ...stem node that you are servicing Then refer to your labels and the following steps to reconnect the SMP cables that you removed from the system node you are servicing If you have a two node system configuration use Figure 590 on page 670 and Table 62 on page 670 to determine the point to point cabling for SMP cables System processor module 669 ...

Страница 676: ...ram represents a pair of SMP cables Cable Cable type and length From To 5C 880 mm 2 9 ft ND1 P1 T1 ND2 P1 T1 5D 880 mm 2 9 ft ND1 P1 T2 ND2 P1 T2 6C 1005 mm 3 3 ft ND1 P1 T7 ND2 P1 T7 6D 1005 mm 3 3 ft ND1 P1 T8 ND2 P1 T8 5A 1005 mm 3 3 ft ND1 P1 T9 ND2 P1 T9 670 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 677: ...5 mm 4 01 ft ND1 P1 T17 ND2 P1 T17 6X 1225 mm 4 01 ft ND1 P1 T18 ND2 P1 T18 5W 1005 mm 3 3 ft ND1 P1 T23 ND2 P1 T23 5X 1005 mm 3 3 ft ND1 P1 T24 ND2 P1 T24 6Y 1005 mm 3 3 ft ND1 P1 T25 ND2 P1 T25 6Z 1005 mm 3 3 ft ND1 P1 T26 ND2 P1 T26 5Y 880 mm 2 9 ft ND1 P1 T31 ND2 P1 T31 5Z 880 mm 2 9 ft ND1 P1 T32 ND2 P1 T32 If you have a three node system configuration use Figure 591 on page 672 and Table 63 ...

Страница 678: ...ing a Three Node Configuration Table 63 Cabling a Three Node Configuration Cable Cable type and length From To 5C 880 mm 2 9 ft ND3 P1 T1 ND2 P1 T1 672 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 679: ...4 01 ft ND3 P1 T15 ND1 P1 T9 3B 1225 mm 4 01 ft ND3 P1 T16 ND1 P1 T10 3W 1225 mm 4 01 ft ND3 P1 T17 ND1 P1 T23 3X 1225 mm 4 01 ft ND3 P1 T18 ND1 P1 T24 5W 1005 mm 3 3 ft ND3 P1 T23 ND2 P1 T23 5X 1005 mm 3 3 ft ND3 P1 T24 ND2 P1 T24 3Y 1225 mm 4 01 ft ND3 P1 T25 ND1 P1 T31 3Z 1225 mm 4 01 ft ND3 P1 T26 ND1 P1 T32 5Y 880 mm 2 9 ft ND3 P1 T31 ND2 P1 T31 5Z 880 mm 2 9 ft ND3 P1 T32 ND2 P1 T32 6C 1005 ...

Страница 680: ...25 mm 4 01 ft ND2 P1 T17 ND1 P1 T17 6X 1225 mm 4 01 ft ND2 P1 T18 ND1 P1 T18 6Y 1005 mm 3 3 ft ND2 P1 T25 ND1 P1 T25 6Z 1005 mm 3 3 ft ND2 P1 T26 ND1 P1 T26 If you have a four node system configuration use Figure 592 on page 675 and Table 64 on page 676 to determine the point to point cabling for SMP cables 674 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 681: ...Figure 592 Cabling a Four Node Configuration System processor module 675 ...

Страница 682: ...8 ND1 P1 T4 2A 1225 mm 4 01 ft ND4 P1 T9 ND2 P1 T11 2B 1225 mm 4 01 ft ND4 P1 T10 ND2 P1 T12 4A 1005 mm 3 3 ft ND4 P1 T11 ND3 P1 T11 4B 1005 mm 3 3 ft ND4 P1 T12 ND3 P1 T12 1A 1625 mm 5 3 ft ND4 P1 T15 ND1 P1 T11 1B 1625 mm 5 3 ft ND4 P1 T16 ND1 P1 T12 1W 1625 mm 5 3 ft ND4 P1 T17 ND1 P1 T21 1X 1625 mm 5 3 ft ND4 P1 T18 ND1 P1 T22 4W 1005 mm 3 3 ft ND4 P1 T21 ND3 P1 T21 4X 1005 mm 3 3 ft ND4 P1 T2...

Страница 683: ... 2Y 1225 mm 4 01 ft ND4 P1 T31 ND2 P1 T29 2Z 1225 mm 4 01 ft ND4 P1 T32 ND2 P1 T30 Cables originating on ND3 5C 880 mm 2 9 ft ND3 P1 T1 ND2 P1 T1 5D 880 mm 2 9 ft ND3 P1 T2 ND2 P1 T2 3C 1225 mm 4 01 ft ND3 P1 T7 ND1 P1 T1 3D 1225 mm 4 01 ft ND3 P1 T8 ND1 P1 T2 5A 1005 mm 3 3 ft ND3 P1 T9 ND2 P1 T9 5B 1005 mm 3 3 ft ND3 P1 T10 ND2 P1 T10 3A 1225 mm 4 01 ft ND3 P1 T15 ND1 P1 T9 3B 1225 mm 4 01 ft ND...

Страница 684: ...1 ft ND2 P1 T15 ND1 P1 T15 6B 1225 mm 4 01 ft ND2 P1 T16 ND1 P1 T16 6W 1225 mm 4 01 ft ND2 P1 T17 ND1 P1 T17 6X 1225 mm 4 01 ft ND2 P1 T18 ND1 P1 T18 6Y 1005 mm 3 3 ft ND2 P1 T25 ND1 P1 T25 6Z 1005 mm 3 3 ft ND2 P1 T26 ND1 P1 T26 a Press the SMP cable and the blue tab together with your fingers and thumb to hold the SMP cable Plug the SMP cable into the previously identified location in the system...

Страница 685: ...e SMP cables previously identified are reconnected to the system node you are servicing c If you removed any SMP cable clips from the side of the rack using your labels reattach the cable bundle to the side of the cable management bracket as shown in the following figure System processor module 679 ...

Страница 686: ...rmation card inserted into the rear of the system control unit You can also refer to the following figures The number in the cable label indicates the bundle for that cable Two system node configuration The two system node configuration has four cable bundles 680 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 687: ...taches to the clip C Three system node configuration The three system node configuration has four cable bundles Figure 596 Bundling and connecting SMP cables for three system nodes Two bundles named B3 with the 3 cables The left B3 bundle contains 3A 3B 3C and 3D This bundle attaches to the clip A The right B3 bundle contains 3W 3X 3Y and 3Z This bundle attaches to the clip F Two bundles named B5 ...

Страница 688: ... This bundle attaches to the clips J Two bundles named B4 with the 4 cables The left B4 bundle contains 4A 4B 4C and 4D This bundle attaches to the clip D The right B4 bundle contains 4W 4X 4Y and 4Z This bundle attaches to the clip G Two bundles named B5 with the 5 cables The left B5 bundle contains 5A 5B 5C and 5D This bundle attaches to the clip E The right B5 bundle contains 5W 5X 5Y and 5Z Th...

Страница 689: ... 598 Single Node Configuration UPIC Cabling Table 65 Single Node Configuration UPIC Cabling Cable number From To 1 SC1 P1 C1 T1 ND1 P1 C9 T1 2 SC1 P1 C2 T1 ND1 P1 C10 T1 If you have a two three or four node system configuration use Figure 599 on page 684 and Table 66 on page 684 to determine the point to point cabling for UPIC cables System processor module 683 ...

Страница 690: ...replace the UPIC cable in the system node complete the following steps 1 Ensure that the white plastic lock is pulled back from the plug housing 2 Plug the UPIC cable A into the previously identified location in the system node by inserting the cable into the connector until it locks into place as shown in the following figure 684 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 691: ...Figure 600 Replacing the UPIC cable into the system node 3 Push the white plastic lock B onto the plug housing as shown in the following figure System processor module 685 ...

Страница 692: ...attached to the system b Repeat step 6 a on page 684 until all the UPIC cables previously identified are reconnected to the system node you are servicing c If applicable secure the cable to the side of the rack with the hook and loop fastener 7 Using your labels reconnect the service processor FSP cables that you removed from the system node you are servicing 686 Power Systems Removing and replaci...

Страница 693: ...Figure 602 Service processor FSP cabling System processor module 687 ...

Страница 694: ... P1 T3 ND1 P1 C9 T2 B 355 mm 1 16 ft SC1 P1 T5 ND1 P1 C10 T2 8 Review the following information to identify the locations where the USB cable connects to the system node that you are servicing and to the system control unit Then reconnect the USB cable that you removed Figure 603 USB Cabling Table 68 USB Cabling From To ND1 or ND2 P1 C13 T3 SC1 P1 T1 a Plug the USB cable into the previously identi...

Страница 695: ...he USB cable into the system node b Plug the USB cable into the previously identified location in the system control unit by inserting the cable into the connector as shown in the following figure System processor module 689 ...

Страница 696: ...ation Then click Verify Node Position Otherwise if your configuration includes only one node continue to the next step If the system is cabled correctly the blue identify LED on each system node will light up in sequence from the top node to the bottom node If the LEDs do not light up in sequence the FSP cables need to be re installed d Expand System Service Aids Cable Plugging Validation Then sel...

Страница 697: ...to confirm the operation 2 Ensure that the amber LED corresponds to the location of the time of day battery with the flashing amber LED Figure 606 Finding the time of day battery indicator 3 Attach the electrostatic discharge ESD wrist strap The ESD wrist strap must be connected to an unpainted metal surface until the service procedure is completed and if applicable until the service access cover ...

Страница 698: ...ving the time of day battery from the 9080 M9S system To remove the time of day battery complete the steps in this procedure Procedure 1 Ensure that you have the electrostatic discharge ESD wrist strap on and that the ESD clip is plugged into a ground jack or connected to an unpainted metal surface If not do so now 2 Access the Advanced System Management Interface ASMI Attention During this proced...

Страница 699: ...ge the battery to avoid possible explosion as the battery contains lithium Throw or immerse the battery in water Heat the battery to more than 100 C 212 F Repair or disassemble the battery Exchange the battery only with the IBM approved part Recycle or discard the battery as instructed by local regulations In the United States IBM has a process for the collection of this battery For information ca...

Страница 700: ... that you have the electrostatic discharge ESD wrist strap on and that the ESD clip is plugged into a ground jack or connected to an unpainted metal surface If not do so now 2 Insert the time of day battery into its slot as shown in the following figure the plus side of the battery orients towards the bottom of the server 694 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 701: ...ay battery 3 Align the bottom tabs of the time of day battery cover in the two slots under the battery as shown in the following figure Roll the battery cover up and secure the cover to the service processor card Time of day battery 695 ...

Страница 702: ... removing and replacing the time of day battery Procedure 1 Ensure that you have the electrostatic discharge ESD wrist strap on and that the ESD clip is plugged into a ground jack or connected to an unpainted metal surface If not do so now 2 If you powered off the system to complete this repair wait for the service processor comes up to the Flexible Service Processor FSP standby state the power on...

Страница 703: ...step You can skip this step a If you are already connected to the ASMI go to the next step Otherwise click All Systems then select system being serviced Then click Actions View All Actions Launch Advanced Systems Management ASM b In the navigation area expand System Service Aids Cable Plugging Validation Then click Validate UPIC Cables The system verifies that the UPIC cables are present Note Olde...

Страница 704: ...t pane displays a form that shows the current date month day and year and time hours minutes and seconds c Change the date the time or both and then click Save Settings 9 If applicable close the rack front and rear doors 698 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 705: ... that the USB devices are not being used Label and remove the USB cables from the USB card 2 If you chose to complete this repair with the power off label and disconnect both UPIC cables from the system control unit UPIC cable locations are P1 C1 T1 and P1 C2 T1 a Remove the white plastic lock A from the plug housing Figure 611 Removing the UPIC cable lock b Push down on the blue cable latch B and...

Страница 706: ... 612 Removing the UPIC cable from the system control unit 3 Check that the amber identify LED is flashing as shown in the following figure 700 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 707: ...rdware When you use an ESD wrist strap follow all electrical safety procedures An ESD wrist strap is used for static control It does not increase or decrease your risk of receiving electric shock when using or working on electrical equipment If you do not have an ESD wrist strap just prior to removing the product from ESD packaging and installing or replacing hardware touch an unpainted metal surf...

Страница 708: ...ve the USB card complete the following steps a Press the blue USB card handle latch A to the left as shown in the following figure b Rotate the handle to the left in the direction shown in the following figure to unlock the USB card from its slot c Hold on to the USB card handle and by using your hand to support the bottom of the USB card pull out the USB card from its slot as shown in the followi...

Страница 709: ...urface If not do so now 2 To replace the USB card complete the following steps a Ensure that the USB card handle A is open as shown in the following figure b Hold on to the USB card handle and by using your hand to support the bottom of the USB card push the USB card into its slot as shown in the following figure c Rotate the handle to the right in the direction shown in the following figure to lo...

Страница 710: ...are levels do not support validating the UPIC cables while the system is at FSP standby You can skip this step if it is not available c Expand System Service Aids Cable Plugging Validation In the Display Cable Status section select UPIC Cables and click Continue The system validates that the UPIC cables are installed in the correct locations and displays a table with the results Ensure that the pl...

Страница 711: ...The cables should be firmly attached to the system 5 When the service processor comes up to the Flexible Service Processor FSP standby state the power on LED on the control panel is flashing slowly continue to the next step 6 Access the ASMI and run the Cable Plugging Validation utility to validate all of the cables a If you are already connected to the ASMI go to the next step Otherwise click All...

Страница 712: ... in the correct locations Expand System Service Aids Cable Plugging Validation to display a table with the results Ensure that the plugging status is OK for each cable in the displayed table If the status is OK no further action is required If the status is not OK review the error logs correct the problems and repeat steps b c and d as needed until the status is OK for all cables e Exit the ASMI I...

Страница 713: ...ctric shock when using or working on electrical equipment If you do not have an ESD wrist strap just prior to removing the product from ESD packaging and installing or replacing hardware touch an unpainted metal surface of the system for a minimum of 5 seconds If at any point in this service process you move away from the system it is important to again discharge yourself by touching an unpainted ...

Страница 714: ...the USB card To prepare the system for operation after installing the USB card complete the steps in this procedure Procedure 1 Ensure that you have the electrostatic discharge ESD wrist strap on and that the ESD clip is plugged into a ground jack or connected to an unpainted metal surface If not do so now 2 To complete the procedure with the power on access the ASMI and run the Cable Plugging Val...

Страница 715: ... table If the status is OK no further action is required If the status is not OK review the error logs correct the problems and repeat steps b and c as needed until the status is OK for all cables d Exit the ASMI e Continue with step unique_130 unique_130_Connect_42_step_activate_partitions 3 If you chose to complete this repair with the power off using your labels reconnect the UPIC cables to the...

Страница 716: ... If your configuration includes two or more nodes expand System Service Aids Cable Plugging Validation Then click Verify Node Position Otherwise if your configuration includes only one node continue to the next step If the system is cabled correctly the blue identify LED on each system node will light up in sequence from the top node to the bottom node If the LEDs do not light up in sequence the F...

Страница 717: ...B devices are not being used Label and remove the USB cables from the USB card 2 If you chose to complete this repair with the power off label and disconnect both UPIC cables from the system control unit UPIC cable locations are P1 C1 T1 and P1 C2 T1 a Remove the white plastic lock A from the plug housing Figure 623 Removing the UPIC cable lock b Push down on the blue cable latch B and pull out th...

Страница 718: ... 624 Removing the UPIC cable from the system control unit 3 Check that the amber identify LED is flashing as shown in the following figure 712 Power Systems Removing and replacing parts in the 9080 M9S system ...

Страница 719: ...rdware When you use an ESD wrist strap follow all electrical safety procedures An ESD wrist strap is used for static control It does not increase or decrease your risk of receiving electric shock when using or working on electrical equipment If you do not have an ESD wrist strap just prior to removing the product from ESD packaging and installing or replacing hardware touch an unpainted metal surf...

Страница 720: ...d complete the following steps a Press the blue USB card handle latch A to the left as shown in the following figure b Rotate the handle to the left in the direction shown in the following figure to unlock the USB card from its slot c Hold on to the USB card handle and by using your hand to support the bottom of the USB card pull out the USB card from its slot as shown in the following figure Figu...

Страница 721: ...the system is at FSP standby You can skip this step if it is not available c Expand System Service Aids Cable Plugging Validation In the Display Cable Status section select UPIC Cables and click Continue The system validates that the UPIC cables are installed in the correct locations and displays a table with the results Ensure that the plugging status is OK for each cable in the displayed table I...

Страница 722: ...pected cables are present c If your configuration includes two or more nodes expand System Service Aids Cable Plugging Validation Then click Verify Node Position Otherwise if your configuration includes only one node continue to the next step If the system is cabled correctly the blue identify LED on each system node will light up in sequence from the top node to the bottom node If the LEDs do not...

Страница 723: ...www ibm com support knowledgecenter POWER9 p9haj crustopsys htm 3 Access the ASMI If you are already connected to the ASMI go to the next step a For instructions see Accessing the ASMI without an HMC www ibm com support knowledgecenter POWER9 p9hby connect_asmi htm b Click Tasks c Click Operations Launch Advanced System Management ASM 4 Record the system identifiers Note To perform this operation ...

Страница 724: ...D packaging and installing or replacing hardware touch an unpainted metal surface of the system for a minimum of 5 seconds If at any point in this service process you move away from the system it is important to again discharge yourself by touching an unpainted metal surface for at least 5 seconds before you continue with the service process Removing the vital product data card from the 9080 M9S s...

Страница 725: ...roduct data card Procedure 1 Ensure that you have the electrostatic discharge ESD wrist strap on and that the ESD clip is plugged into a ground jack or connected to an unpainted metal surface If not do so now 2 Replace the VPD card a Ensure that the VPD card handle is open as shown in the following figure b Hold on to the VPD card handle and use your hand to support the bottom of the card as you s...

Страница 726: ...trap on and that the ESD clip is plugged into a ground jack or connected to an unpainted metal surface If not do so now 2 If you powered off the system to complete this repair wait for the service processor comes up to the Flexible Service Processor FSP standby state the power on LED on the control panel is flashing slowly then continue to the next step to validate all of the cables If you did not...

Страница 727: ...MI go to the next step Otherwise click All Systems then select system being serviced Then click Actions View All Actions Launch Advanced Systems Management ASM b In the navigation area expand System Service Aids Cable Plugging Validation Then click Validate UPIC Cables The system verifies that the UPIC cables are present Note Older firmware levels do not support validating the UPIC cables while th...

Страница 728: ...RB Keyword then click Save settings to update the system keywords and to save them to the VPD f In the ASMI navigation panel expand Power Restart Control Power On Off System Then click Save settings and power on g In the ASMI navigation panel expand On demand Utilities CoD Activation Enter the CoD and VET activation codes that you obtained from IBM for this new VPD card Then click Continue to writ...

Страница 729: ......

Страница 730: ...IBM ...

Отзывы: