4. Determine whether the repair operation can continue when the system power is turned on.
To continue the repair operation when the system power is turned on, the following conditions must
be true:
• Fans must be installed in all three slots.
Each of the three fans has a green LED and an amber LED, as shown in Figure 75 on page 88. The
green LED is lit solid for all fans, but the fan with the failure has a flashing amber fault LED.
• If only one amber fault LED is On, the repair operation can be completed when the system power is
turned on.
Figure 75. Fan LEDs in the system control unit
5. Ensure that the amber LED corresponds to the location of the fan with the lit fault LED.
6. If you can complete the procedure with the system power turned on, continue with step “8” on page
88.
7. If you powered off the system earlier in this procedure or you want to power off the system to
complete the repair operation, complete the following steps:
a) If the system is powered off, continue with step “7.b” on page 88. Otherwise, prepare to power
off the system.
Attention: Ensure that you shut down the running logical partitions on the managed system
before you power off the managed system. Powering off the managed system without
shutting down the logical partitions first causes the logical partitions to shut down
abnormally and can cause data loss. If you use a Virtual I/O Server (VIOS) logical partition,
ensure that all clients are shut down or that the clients have access to their devices by using
an alternative method.
When you are ready to power off the system, from the Operation list, select System Level
Deactivate. Then, click OK to confirm the operation.
b) From the Operation list, select FRU Level Deactivate. Then, click OK to confirm the operation.
c) Stop the system. For instructions, see Stopping a system (www.ibm.com/support/
knowledgecenter/POWER9/p9haj/crustopsys.htm).
8. Attach the electrostatic discharge (ESD) wrist strap.
The ESD wrist strap must be connected to an unpainted metal surface until the service procedure is
completed, and if applicable, until the service access cover is replaced.
Attention:
88 Power Systems: Removing and replacing parts in the 9080-M9S system
Содержание 9080-M9S
Страница 1: ...Power Systems Removing and replacing parts in the 9080 M9S system IBM ...
Страница 19: ...Figure 11 Identify LEDs for the service processor cables on the system node Cables 13 ...
Страница 25: ...Figure 17 Service processor FSP cabling Cables 19 ...
Страница 51: ...Figure 37 Identify LEDs for the UPIC cables on the system node Cables 45 ...
Страница 70: ...64 Power Systems Removing and replacing parts in the 9080 M9S system ...
Страница 82: ...76 Power Systems Removing and replacing parts in the 9080 M9S system ...
Страница 85: ...Figure 70 Replacing the concurrent maintenance circuit card Concurrent maintenance circuit card 79 ...
Страница 86: ...80 Power Systems Removing and replacing parts in the 9080 M9S system ...
Страница 92: ...86 Power Systems Removing and replacing parts in the 9080 M9S system ...
Страница 137: ...Figure 111 Cabling a Four Node Configuration Memory modules 131 ...
Страница 149: ...Figure 121 Service processor FSP cabling Memory modules 143 ...
Страница 157: ...Figure 130 Removing the rear power cords L003 or or Memory modules 151 ...
Страница 182: ...Figure 151 Cabling a Four Node Configuration 176 Power Systems Removing and replacing parts in the 9080 M9S system ...
Страница 194: ...Figure 161 Service processor FSP cabling 188 Power Systems Removing and replacing parts in the 9080 M9S system ...
Страница 203: ...Figure 170 Removing the rear power cords L003 or or Memory modules 197 ...
Страница 228: ...Figure 191 Cabling a Four Node Configuration 222 Power Systems Removing and replacing parts in the 9080 M9S system ...
Страница 240: ...Figure 201 Service processor FSP cabling 234 Power Systems Removing and replacing parts in the 9080 M9S system ...
Страница 250: ... L003 or or or or 244 Power Systems Removing and replacing parts in the 9080 M9S system ...
Страница 275: ...Figure 231 Cabling a Four Node Configuration Memory VRMs 269 ...
Страница 287: ...Figure 241 Service processor FSP cabling Memory VRMs 281 ...
Страница 294: ...288 Power Systems Removing and replacing parts in the 9080 M9S system ...
Страница 298: ... L003 or or or or 292 Power Systems Removing and replacing parts in the 9080 M9S system ...
Страница 323: ...Figure 271 Cabling a Four Node Configuration Miscellaneous VRMs 317 ...
Страница 335: ...Figure 281 Service processor FSP cabling Miscellaneous VRMs 329 ...
Страница 369: ...Figure 311 Cabling a Four Node Configuration Miscellaneous VRMs 363 ...
Страница 381: ...Figure 321 Service processor FSP cabling Miscellaneous VRMs 375 ...
Страница 388: ...382 Power Systems Removing and replacing parts in the 9080 M9S system ...
Страница 404: ...398 Power Systems Removing and replacing parts in the 9080 M9S system ...
Страница 434: ...428 Power Systems Removing and replacing parts in the 9080 M9S system ...
Страница 503: ...Figure 433 Replacing the Power APSS and TPM card Power APSS and trusted platform module card 497 ...
Страница 504: ...498 Power Systems Removing and replacing parts in the 9080 M9S system ...
Страница 510: ...504 Power Systems Removing and replacing parts in the 9080 M9S system ...
Страница 523: ...Figure 451 Installing the front cover 9 If applicable close the rack front door Power supplies 517 ...
Страница 524: ...518 Power Systems Removing and replacing parts in the 9080 M9S system ...
Страница 528: ... L003 or or or or 522 Power Systems Removing and replacing parts in the 9080 M9S system ...
Страница 553: ...Figure 475 Cabling a Four Node Configuration Processor VRM 547 ...
Страница 565: ...Figure 485 Service processor FSP cabling Processor VRM 559 ...
Страница 572: ...566 Power Systems Removing and replacing parts in the 9080 M9S system ...
Страница 592: ...586 Power Systems Removing and replacing parts in the 9080 M9S system ...
Страница 634: ...628 Power Systems Removing and replacing parts in the 9080 M9S system ...
Страница 637: ...Figure 552 Removing the rear power cords L003 or or System processor module 631 ...
Страница 681: ...Figure 592 Cabling a Four Node Configuration System processor module 675 ...
Страница 693: ...Figure 602 Service processor FSP cabling System processor module 687 ...
Страница 729: ......
Страница 730: ...IBM ...