8. Parameter
292
[23] Velocity Loop Proportional Gain (Parameter No.31)
No.
Name
Symbol
Unit
Input Range
Default factory
setting
31 Velocity Loop Proportional Gain
VLPG
–
1 to 9999999 In accordance with
actuator
This parameter determines the response of the speed control loop. When the set value is
increased, the follow-up ability to the velocity command becomes better (the servo-motor
rigidity is enhanced). The higher the load inertia becomes, the larger the value should be set.
However, excessively increasing the setting will cause overshooting or oscillation, which
facilitates producing the vibrations of the mechanical system.
When the set value is high (over-shoot)
When the set value is low
Velocity
Time
[24] Velocity Loop Integral Gain (Parameter No.32)
No.
Name
Symbol
Unit
Input Range
Default factory
setting
32 Velocity Loop Integral Gain
VLPT
–
1 to 9999999 In accordance with
actuator
Any machine produces frictions. This parameter is intended to cope with deviation generated
by external causes including frictions. Increasing the setting value improves the reactive force
against load change. That is, the servo rigidity increases. However, increasing the parameter
value excessively may make the gain too high, which then cause the machine system to be
vibrated due to overshoot or shaking.
Tune it to obtain the optimum setting by watching the velocity response.
When the set value is high (over-shoot)
When the set value is low
Velocity
Time
Содержание SCON-CB-F
Страница 2: ......
Страница 4: ......
Страница 10: ......
Страница 16: ......
Страница 48: ...1 Specifications Check 32 1 3 3 SCON CGB 3000W and above ...
Страница 60: ...1 Specifications Check 44 ...
Страница 266: ...3 Operation 250 ...
Страница 276: ...4 Field Network 260 ...
Страница 282: ...5 Vibration Suppress Control Function 266 ...
Страница 362: ...9 Troubleshooting 346 ...
Страница 444: ...10 Appendix 428 ...
Страница 449: ......