3. Operation
218
(Example) Repetition of ST1
→
ST2
→
ST1
→
Insert timer
Δ
t if necessary.
[Example of stop position when the ST* signal is turned OFF by the LS* signal]
If the positioning width is set at a position before the original deceleration start position, the
actuator cannot reach the target position.
Caution: (1) If the ST* signal for the position is turned ON after the completion of
positioning, the LS* signal remains ON.
(2) Both the LS* and PEND signals are set to ON in the positioning width zone.
Accordingly, they may be turned ON under operation of the actuator if a large
positioning width is set.
(3) Interlock should be taken so that two or more ST* signals are set to ON
simultaneously. If two or more ST* signals are input simultaneously, they will
be executed according to the following priorities: ST0
→
ST1
→
ST2
Start signal
ST1
(PLC
→
Controller)
Turned ON after
entering into
positioning width zone
Target Position
Position sensing output
LS1
(Controller
→
PLC)
Start signal
ST2
(PLC
→
Controller)
Position sensing output
LS2
(Controller
→
PLC)
Δ
t
Δ
t
Δ
t
Δ
t : Time required to certainly reach the target position after the position sensing output LS1 or 2 is turned on.
Start signal
ST1
(PLC
→
Controller)
Turned ON after
entering into
positioning width zone
Target
Position
Position sensing output
LS1
(Controller
→
PLC)
Operation of actuator
Stop before target position
Orignal deceleration
start position
Positioning
width
Deceleration
start
Velocity
Move
distance
3.2.6
Содержание SCON-CB-F
Страница 2: ......
Страница 4: ......
Страница 10: ......
Страница 16: ......
Страница 48: ...1 Specifications Check 32 1 3 3 SCON CGB 3000W and above ...
Страница 60: ...1 Specifications Check 44 ...
Страница 266: ...3 Operation 250 ...
Страница 276: ...4 Field Network 260 ...
Страница 282: ...5 Vibration Suppress Control Function 266 ...
Страница 362: ...9 Troubleshooting 346 ...
Страница 444: ...10 Appendix 428 ...
Страница 449: ......