Chapter 2 Wiring
54
4) CompoNet Type
5) EtherNet/IP Type
Master Unit
Switching Hub
Slave Devices
EtherNet Straight Cable, Category 5e or more
Double shielded cable braided with aluminum foil
recommended
MSEP Unit
EtherNet/IP Type
BS+
BDL
BDH
BS-
BS+
BDL
BDH
BS-
BS+
BDL
BDH
BS-
Master Unit
Slave Devices
Terminal
Resistance
121
Ω
MSEP-
CompoNet Type
Connect the terminal
resistor if the unit is
placed at the end of
the network.
24V
Power Supply
Supply power separately to the slave devices
that requires the communication power supply.
It is not necessary to supply communication power
to MSEP Unit, however, there is no problem
even if communication power is supplied.