N700E INSTRUCTION MANUAL
3-21
A29
Manual Torque Boost Voltage Setpoint
Range: 0.0 ~ 50.0 % in 0.1 %
For Manual Torque Boost mode, program the value in % of an output voltage.
Related Parameters: A30
A30
Manual Torque Boost Frequency Setpoint
Range: 0.0 ~ 100.0 % in 0.1 %
Program the frequency breakpoint
Related Parameters: A29
100 %
F
5%
A(30)=
10%
A(29)=
5%
10%
Base F
(A03)
V
100 %
F
10%
A(30)=
5%
A(29)=
10%
5%
Base F
(A03)
V
Ex1: A(29)= 5%, A(30) = 10%
Ex2: A(29)= 10%, A(30) = 5%
A31
Motor Control Method
0: Constant Torque
1: Reduced Torque (Variable Torque)
2: Sensorless Vector Control
Reduced torque is effective for fan or pump application which do not require high torque
at low frequency. By reducing the output voltage, increased efficiency, lower noise, and
lower vibration.
For Sensorless Vector method, per specified output voltage, current, motor parameters,
motor rpm, the corresponding torque value is calculated. At very low frequency up to 0.5
Hz, high torque operation is possible
Related Parameters: A29~A30, H01~H11
A32
Voltage Gain Factor
Range: 20.0 ~ 110.0 % in 0.1 %
The output voltage cannot exceed the
input voltage
Related Parameters: A53, A03
A33
DC Injection Braking
0: Disabled
1: Enabled
Enable or Disable DC Injection Braking Function
By adding the force to the rotor, slowing the motor to stop.
Related Parameters: A33~A37
100 %
F
Base F
(A03)
V
Constant Torque
Base F
(A03)
V
Reduced Torque
Max F
(A04)
100 %
F
A(53)
F
Base F
(A03)
Output V
A(53) x A(32)