N700E INSTRUCTION MANUAL
3-82
3.7.5 ModBus Address Table
N700E
*Eu : Europe, *Am : America
FS : Factory Setting
*Data Type is unsigned integer16
Code
Number
Function Name
Address
(Hex)
Address
(Dec)
R/W
attribute
Init.
Value
Min.
Value
Max.
Value
Scale
Unit
d01
Output Frequency
Monitor
0x0101
258
R
0
0
40000
0.01
Hz
d02
Output Current Monitor
0x0102
259
R
0
0
40000
0.1
A
d03
Output Voltage Monitor
0x0103
260
R
0
0
40000
1
V
d04
Rotation Direction
0x0104
261
R
0
0
40000
d05
PID Feedback
0x0105
262
R
0
0
40000
d06
Intelligent Input Terminal
Status
0x0106
263
R
0
0
40000
d07
Intelligent Output
Terminal Status
0x0107
264
R
0
0
40000
d08
RPM Output
0x0108
265
R
0
0
40000
d09
Power Consumption
0x0109
266
R
0
0
40000
W
d10
VFD Runtime (Hours)
0x010a
267
R
0
0
40000
Hour
d11
VFD Runtime (Minutes)
0x010b
268
R
0
0
40000
Minute
d12
DC Bus Voltage
0x010c
269
R
0
0
40000
1
V
d13
Current Fault,
Fault Code
0x010d
270
R
0
0
40000
Trip Monitor 1,
Frequency at Trip
0x010e
271
R
0
0
40000
0.01
Hz
Trip Monitor 1,
Current at Trip
0x010f
272
R
0
0
40000
0.1
A
Trip Monitor 1,
Vdc at Trip
0x0110
273
R
0
0
40000
1
V
d14
Previous Fault 1,
Fault Code
0x0111
274
R
0
0
40000
Trip Monitor 2,
Frequency at Trip
0x0112
275
R
0
0
40000
0.01
Hz
Trip Monitor 2,
Current at Trip
0x0113
276
R
0
0
40000
0.1
A
Trip Monitor 2,
Vdc at Trip
0x0114
277
R
0
0
40000
1
V
d15
Previous Fault 2,
Fault Code
0x0115
278
R
0
0
40000
Trip Monitor 3,
Frequency at Trip
0x0116
279
R
0
0
40000
0.01
Hz
Trip Monitor 3,
Current at Trip
0x0117
280
R
0
0
40000
0.1
A
Trip Monitor 3,
Vdc at Trip
0x0118
281
R
0
0
40000
1
V
d16
Previous Fault 3,
Fault Code
0x0119
282
R
0
0
40000
Trip Monitor 4,
Frequency at Trip
0x011a
283
R
0
0
40000
0.01
Hz
Trip Monitor 4,
Current at Trip
0x011b
284
R
0
0
40000
0.1
A
Trip Monitor 4,
Vdc at Trip
0x011c
285
R
0
0
40000
1
V
d17
Fault Count
0x011d
286
R
0
0
60000
Intelligent
input,
output
Binary value
input : (b15~b6 : reserved, b5: input 6, b4: input 5, b3: input 4, b2: input 3, b1: input 2, b0: input 1
output : (b15~b3 : reserved, b2: Alarm, b1: output 2, b0: output 1
Source of
Trip
1: Over current, 2: Overvoltage, 3: Under voltage, 4: Output Short Circuit, 5: reserved, 6: VFD Over Temperature,
7: Motor Overload , 8: External trip1, 9: EEPROM Error, 10: Communication Error,11: USP Error,
12: Ground Fault ,13: Reserved,14: Inverter thermal overload, 15: Input phase loss,
18: BRD Fault, 19: OVS Fail, 22~26: External trip2~6, 27: Fan fault, 28: Profibus Fault(Option),
29: DeviceNet Fault(Option), 30: System Overload Detection Fault, 31: System Underload Detection Fault