N700E INSTRUCTION MANUAL
3-33
b10
Start Frequency Setpoint
Range 0.50 ~ 10.00 Hz in 0.01 Hz
Setting the starting frequency from the VFD output
Related Parameters:
b11
PWM Carrier Frequency
Range 1.0 ~ 16.0 Hz in 0.1 kHz
Select Heavy Duty or Normal Duty factory setting per VFD model and loading type
Related Parameters:
b12
Initialization Mode
0: Clear Trip History
1: Parameters except b13(Country Code) and A53(Motor Input Voltage)
Select an initialization mode
Related Parameters:
b13
Country Code
0: Korea
1: Europe
2:US
Select a country code of which default parameter values to use
Related Parameters:
b14
RPM Display Scale Factor
Range: 0.01 ~ 99.99 in 0.01
Program RPM Scale factor for d08 Display
Related Parameters: d08
b15
Stop Key Function
0: Enabled
1: Disabled
To avoid un-desired stop by pressing the STOP key on the panel by some other operator
when the main operation is being performed by terminal or remotely.
Related Parameters: