N700E INSTRUCTION MANUAL
3-34
b16
Resume Frequency on FRS Cancellation
0: Start from 0Hz
1: Restart from frequency corresponding motor speed
Select what frequency VFD to resume its operation when the Free Run Sop (FRS) is
cancelled.
Related Parameters: b03
Motor
RPM
FW(Run)
t
b03
FRS
Free Run
i) When b16 = 0
Motor
RPM
FW(Run)
t
FRS
i) When b16 = 1
Free Run
b17
Modbus Node ID
Range: 1~32
Node ID for Modbus Communication
Related Parameters:
b18
Ground Fault Detection Setpoint
Range: 0.0 ~ 100.0 % in 0.1 %
0: Disabled
Program to enable the Ground fault detection and its fault level as a percentage of rated
current. For N700E models under 3.7 kW(5 HP), this function is turned off from the
Factory
Related Parameters:
b19
Speed Search: Current Level
Range: 90 ~ 180 % in 1%
Controls the starting current level during speed search motion on the basis of the motor
rated current
Related Parameters: b19~b23
b20
Speed Search: Voltage Increase
Range: 10 ~ 300 % in 1 %
In case of the lower starting current level during speed search motion on the basis of the
motor rated current, the increase level of the output voltage is set from 10% to 300%
Related Parameters: b19~b23
b21
Speed Search: Voltage Decrease
Range: 10 ~ 300 % in 1 %
In case of the higher starting current level during speed search motion on the basis of the
motor rated current, the decrease level of the output voltage is set from 10% to 300%
Related Parameters: b19~b23