N700E INSTRUCTION MANUAL
3-35
b22
Speed Search: Speed Decrease
Range: 1.0 ~ 200.0 % in 0.1 %
Controls the speed decrease level during speed search motion.
Related Parameters: b19~b23
b23
Frequency Match
0:
Start from 0 Hz
1:
Start from frequency corresponding motor speed
In case of inverter starting operation, the start frequency of the inverter can be selected
as follows
Related Parameters: b19~b23
Motor
RPM
Power
t
Free Run
i ) When b23 = 0
Motor
RPM
Power
t
VFD
out
i ) When b23 = 1
Free Run
VFD
out
b24
Fault Relay Select
0: Inactive
1: Active only when a long steady trip signal
2: Active for every trip
3:Active only when a long steady trip signal, then auto reset
Combined with Restart, b01 select, various method can be selected as summarized for
“Overvoltage and Over current” trip and “Under voltage” trip respectively.
Related Parameters: