N700E INSTRUCTION MANUAL
3-63
Frequency arrival
signal(FA1)
Output frequency[Hz]
F01
C22
0.5Hz
C23
1.5Hz
60 msec
@ FA1 signal LOW
AL0 AL1 AL2
AL0 AL1 AL2
@ FA1 signal HIGH
Set 3: Overload Advanced Notice Signal (OL)
Before the VFD becomes overload, N700E generates an advanced warning signal to prevent any
damage by the excessive output current. Overload detection circuit is designed to operate during
powered motor operation and regenerative braking operation. The OL signal becomes ACTIVE
High when the output current exceeds the setpoint programmed in C21, Overload Advance Notice
Signal Setting
Code
Set Value
Description
C13
3
Set Intelligent Relay Out 1 Terminal to OL
C16
0
Set C13 to Normally Open to Form A configuration
If set to 1, Form B configuration (Normally Closed)
C21
[10~200] % Overload Advanced Notice Signal Setting; % x VFD rated current
VFD F Out
OL
@ OL signal LOW
AL0 AL1 AL2
AL0 AL1 AL2
@ OL signal HIGH
Overload Limit Level, b07
Advanced Notice Level, C21
Set 4: Output Deviation Excess for PID Control (OD)
The PID loop error is defined as the magnitude of the difference between the set point and process
variable. When the error magnitude exceeds the value of C24, the OD terminal signal turns on
Code
Set Value
Description
C13
3
Set Intelligent Relay Out 1 Terminal to OD
C16
0
Set C13 to Normally Open to Form A configuration
If set to 1, Form B configuration (Normally Closed)
C24
[0.0~100] % PID Deviation level Setting
OD
@ OD signal LOW
AL0
AL1
AL2
AL0
AL1
AL2
@ OD signal HIGH
C24
Feedack
Ref
C24
Set 5: Alarm Signal (AL)
The inverter fault signals is active when a fault has occurred