N700E INSTRUCTION MANUAL
3-44
Analog output (DC voltage)
C18 (FM Output selection)
Set “C18=4” display calculated torque value (-150%~+150%) by analog output.
FM output
Torque
0V
-150%
5V
0%
10V
+150%
(
※
C18 = 0~3 are the same as existed function)
Analog output (current)
C25 (AM Output selection)
Set “C25=4” display calculated torque value (-150%~+150%) by analog output.
AM output
Torque
4mA
-150%
12mA
0%
20mA
+150%
(
※
C25 = 0~3 are the same as existed function)
Special parameter: Calculated torque read frame by Modbus
- CMD : 03 (Read)
- Parameter : 10 (Calculated Torque)
Communication Number CMD
Parameter
Data Quantity CRC
TX
01
03
000A
0001
2byte
Communication Number CMD Byte Quantity
Data
CRC
RX
01
03
02
Torque value
2byte
※
This document are written by result of test bench.
Field engineer should be tuned for each field situation by consider above case study.