Set 11: Unintended Start Protection (USP)
USP function is to prevent the automatic start up at power on. If the Run(FW/RV)
command is activated prior to the power up, as soon as the power is applied, the VFD
starts to run immediately. If USP is enabled, the VFD would not run till VFD is reset.
Code
Set Value
Description
A02
1
Run Command by Terminal Input
C01
0
Set Terminal 1 to FW Operation
C03
11
Set Terminal 3 to USP Operation
C07
0
Set Terminal 1 to Normal Open
When shorted(Closed); FW Run, When Open, FW Stop
C09
0
Set Terminal 3 to Normal Open
USP
VFD
POWER
Relay Alarm
FW(Run)
VFD
RUN
CM1
6
P24
USP
FW
5
4
3
2
1
Set 12: Software Lock Function (SFT)
Software lock function disables all the parameter value editing except b09
Code
Set Value
Description
A02
1
Run Command by Terminal Input
C01
0
Set Terminal 1 to FW Operation
C03
12
Set Terminal 3 to SFT Operation
C07
0
Set Terminal 1 to Normal Open
When shorted(Closed): FW Run, When Open: FW Stop
C09
0
Set Terminal 3 to Normal Open