N700E INSTRUCTION MANUAL
3-5
Code
Name
Edit
Range
Unit Res Default
PID Control
A70 PID Function Select
X
0: PID Control Disabled
1: PID Control Enabled
2: F/F Control Enabled
-
-
0
A71 PID Setpoint
O 0.00 to 100.0
%
00.1
0.00
A72 PID Setpoint Source
X
0: Keypad Potentiometer
1: Control Terminal Input
2: Keypad Up/Down
3: Remote Operator(Communication)
-
-
2
A73 PID Feedback Type
X 0: Current Input "OI"
1: Voltage Input "O"
-
-
0
A74 PID P Gain
O 0.1 to 1000
%
0.1
100.0
A75 PID I Gain Time
O 0.0 to 3600
Sec 0.1
1.0
A76 PID D Gain Time
O 0.00 to 10.00
Sec 0.01
0.0
A77 PID Error Limit
O 0.0 to 100.0
%
0.1
100.0
A78 PID Output High Limit
O -100.0 to 100.0
%
0.1
100.0
A79 PID Output Low Limit
O -100.0 to 100.0
%
0.1
0.0
A80 PID Output Invert
X
0: Disabled
1: Enabled
-
-
0
A81 PID Scale Factor
X 0.1 to 1000
%
0.1
100.0
A82 Pre PID Frequency Setpoint
X 0.00 to Max Frequency(A04)
Hz 0.01
0.00
A83 PID Sleep Frequency Setpoint
X 0.00 to Max Frequency(A04)
Hz 0.01
0.00
A84 PID Sleep/Wake Delay Time
X 0.0 to 30.0
Sec 0.1
0.0
A85 PID Wake Frequency Setpoint
X
Sleep Frequency(A83) to Max
Frequency (A04)
Hz 0.01
0.00