Qualifications and Requirements
2
62
809480
Instruction Manual
XPR300
Grounding practices
1.
Unless noted, use cables with a minimum gauge of 21.2 mm
2
(4 AWG) (047031) for the EMI
ground cables shown in the
2.
The cutting table is used for the common, or star, EMI ground point and should have threaded
studs welded to the table with a copper bus bar mounted on them. A separate bus bar should
be mounted on the gantry as close to each motor as possible. If there are motors at each end of
the gantry, run a separate EMI ground cable from the far motor to the gantry bus bar. The gantry
bus bar should have a separate, heavy EMI ground cable 21.2 mm
2
(4 AWG; 047031) to the
table bus bar. The EMI ground cables for the torch lifter and the RHF or combined ignition/gas
connect console must each run separately to the table ground bus.
3.
Inadequate grounding not only exposes operators to dangerous voltages, but inadequate
grounding also increases the risk of equipment failure and unnecessary downtime. Ideally a
ground should be zero ohms resistance, but field experience indicates under 1 ohm resistance
is satisfactory for most applications. Consult your local and national electric codes to make sure
that you have satisfactory grounding and resistance in your location.
4.
A ground rod (a PE ground) that meets all applicable local and national electric codes must be
installed within 6 m (20 ft) of the cutting table. The PE ground must be connected to the cutting
table ground bus bar using a minimum 21.2 mm
2
(4 AWG) grounding cable (047031). Consult
an electrician in your location to make sure that your grounding meets all local and national
electric codes.
5.
For the most effective shielding, use the Hypertherm CNC interface cables for I/O signals, serial
communication signals, between plasma systems in multi-drop connections, and for
interconnections between all parts of the Hypertherm system.
6.
All hardware used in the ground system must be brass or copper. While you can use steel studs
welded to the cutting table for mounting the ground bus, no other aluminum or steel hardware
can be used in the ground system.
7.
AC power, PE, and service grounds must be connected to all equipment according to local and
national codes.
8.
For a system with a remote high frequency (RHF) console or combined ignition/gas connect
console, the positive, negative, and pilot arc leads should be bundled together for as long a
distance as possible. The torch lead, work lead, and the pilot arc (nozzle) leads may be run
parallel to other wires or cables only if they are separated by at least 150 mm (6 inches). If
possible, run power and signal cables in separate cable tracks.
9.
For a system with a RHF console or combined ignition/gas connect console, Hypertherm
recommends that you mount this console as close as possible to the torch. This console also
must have a separate ground cable that connects directly to the cutting table ground bus bar.
10.
Each Hypertherm component, as well as any other CNC or motor drive cabinet or enclosure,
must have a separate ground cable to the common (star) ground on the table. This includes the
ignition/gas connect console, whether it is bolted to the plasma system or to the cutting table.
Содержание XPR300
Страница 1: ...XPR300 Plasma Instruction Manual 809480 Revision 2 English ...
Страница 18: ...Contents 18 809480 Instruction Manual XPR300 ...
Страница 34: ...Specifications 1 34 809480 Instruction Manual XPR300 ...
Страница 66: ...Qualifications and Requirements 2 66 809480 Instruction Manual XPR300 ...
Страница 188: ...Connect for Communication 4 188 809480 Instruction Manual XPR300 ...
Страница 192: ...Coolant Installation 5 192 809480 Instruction Manual XPR300 ...
Страница 230: ...Operation 6 230 809480 Instruction Manual XPR300 ...
Страница 337: ...Parts List 9 XPR300 Instruction Manual 809480 337 ...
Страница 343: ...Parts List 9 XPR300 Instruction Manual 809480 343 ...
Страница 380: ...Wiring Diagrams 10 380 809480 Instruction Manual XPR300 ...
Страница 381: ...381 Overview Sheet 1 of 22 013403 013403 ...
Страница 382: ...382 Plasma power supply 1 Sheet 2 of 22 013403 ...
Страница 383: ...383 Plasma power supply 2 Sheet 3 of 22 013403 ...
Страница 384: ...384 Plasma power supply 3 Sheet 4 of 22 013403 ...
Страница 385: ...385 Plasma power supply 4 Sheet 5 of 22 013403 ...
Страница 386: ...386 Plasma power supply 5 Sheet 6 of 22 013403 ...
Страница 387: ...387 Plasma power supply 6 Sheet 7 of 22 013403 ...
Страница 388: ...388 Plasma power supply 7 Sheet 8 of 22 013403 ...
Страница 389: ...389 Gas connect console 1 Sheet 9 of 22 013403 ...
Страница 390: ...390 Gas connect console 2 Sheet 10 of 22 013403 ...
Страница 391: ...391 Torch connect console Sheet 11 of 22 013403 ...
Страница 392: ...392 Coolant system Sheet 12 of 22 013403 ...
Страница 393: ...393 Gas system 1 Sheet 13 of 22 013403 ...
Страница 394: ...394 Gas system 2 Sheet 14 of 22 013403 ...
Страница 395: ...395 Gas system 3 Sheet 15 of 22 013403 ...
Страница 402: ...402 Wireless subsystem block diagram Sheet 22 of 22 013403 ...