Page 70
Entries on the unit info screen
02: Information
No. Parameter
No.
Meaning/Comment
[ ] explains the term in the glossary
Min
Max
FS
[ ] refers to a related explanation of the term
1 Fault_message_unit
List of possible unit fault messages
0 No
fault
10
Connector ST09 on the main board is not plugged in.
12
The external leakage detector connected to the DI has been activated (option)
22
Minimum value of current input not plausible
24
Minimum value of resistance input/NTC input not plausible
25
Maximum value of resistance input/NTC input not plausible
29 System
fault
150
Values provided by pressure sensor not plausible
151 Maximum
pressure
exceeded
152
Minimum pressure not reached
153
Water inlet pressure too low
154
Leakage detected in the pump station
155
Frequency inverter displays error message
156
Motor temperature too high
157
Housing temperature too high
158
Pump temperature too high
210
Humidity sensor, cable or input level defective
211
Humidity sensor 2, cable or input level defective
4 Service_message_unit
Service message unit
0
A service is not required
2
The maximum number of operating cycles for K1 has been reached and a
Service_main_contactor [34] is required
7
A service is required due to the number of operating hours
15
The water inlet pressure is below the specified minimum value. The high pressure
pump operation is on hold until the pressure has maintained the minimum value
for the period defined in parameter 15/14. The occurrence of the service message
is recorded in an internal counter. If the service message has occurred 5 times,
the fault message 'Pressure_water input' (02/1, no. 153) is raised. The internal
counter is counted down by '1' each time when the water input pressure has not
fallen below the minimum value for a contigous period of 10 minutes.
16
The nozzle condition of the spraying system requires maintenance
18
The control of the humidifier should be optimized.
19
The actual pressure falls below the target pressure by > 1bar for at least 180s at
one frequency of 50Hz. Cause: slight leaks in the Area of nozzles and tubing as
well Pump wear. This service notification solves no mistake. The system
continues to run until the Minimum pressure is no longer reached. Then the
system stops with error message 152. Review and eliminate existing ones Leaks
or replace the pump out.
20
The water inlet pressure is above the specified maximum value. The high-
pressure pump is stopped until the pressure drops below the maximum value
again.
7 Model
Type designation of unit
8 Unit_name
Unit name [90], can be selected by the customer, if required
9 Serial_number
Serial_number
10 Date_of_manufacturing
Date_of_manufacturing
11 Software_version
Software version of control
12 Production_total_time
Total duration of steam production since initial operation (specified in
days/months/years/hours/minutes)
13 Unit_total_runtime
The total runtime of the unit since its first connection to the power supply
(specified in days/months/years/hours/minutes)
Plug_ST09
Leakage_sensor
Input_current_min.
Input_resistance_OC
Input_resistance_SC
Internal
Adjustment/value range
Factory setting (FS) Bold
Read value
No_fault
Temperature_engine
Temperature_housing
Temperature_pump
Humidity_sensor
Humidity_sensor 2
Read value
Pressure_sensor
Pressure_max.
Pressure_min.
Pressure_water_inlet
Leakage_pump_station
Frequency_converter
Pressure_set_value
Pressure_water_input_max
Read value
Read value
Read value
Read value
No_service_msg.
Cycles_main_contactor 1
Operating_time
Pressure_water_input_min
Nozzles
Control
Read value
Read value
Read value
18 Service_Reset
Reset all service messages?
0 No
1 Yes
Selection
Off
On