Page 55
13.6.2 Read values submenu
Read values table (visible on both the basic and the advanced levels)
04: Read_values
No. Parameter
No.
Meaning/Comment
[ ] explains the term in the glossary
Min
Max
FS
[ ] refers to a related explanation of the term
1 Status_unit
Operating condition of unit
0
Control performs initialisation [10]
1
Unit is ready for humidification, but the safety interlock [11] is open.
2
Unit is ready for humidification, but there is no demand [5].
3 Humidifying
[47]
5
Unit was switched off via a software command [12] for opening the interlock
(safety) system [83] via the communication interface [13]
6
Steam production was switched off manually via the on/off button [14]
15
The unit is in cooling mode
150
automatic flushing of the nozzle section(s) for humidification
151
automatic flushing of the nozzle section for cooling
152
The system carries out a hygiene flush because there was no humidification or
cooling request for a period of x hours (x is stored as a waiting time in parameter
15/1).
153
The system flushes the feed water pipe to prevent microbial contamination
154
The pressure in the spray system is reduced
155
A flushing process (with line pressure) was triggered manually via the touch
screen
156
Automatic flushing of the nozzle train for humidification and cooling
270
A service message has appeared. For detailed specification, see read value 8 for
cyl. 1 and read value 9 for cyl. 2 (double cylinder units only)
900
Unit is performing diagnostics [15]
901
The control electronics is not yet programmed for the unit type
902
A USB stick was plugged in and a parameter upgrade is run by the unit
903
A parameter upgrade was successfully carried out. Restart of the unit is required
999
There is a fault
4 Fault_message_unit
List of possible unit fault messages
7 Service_message_unit
Service message unit
17 Demand
The demand [5] is the control signal from which the internal actuator signal [42] is
created
18 Control_sig._internal
Internal actuator signal [42] as a percentage of the actuator signal for the nominal
output
20 Safety_interlock
Status of the interlock (Safety) system [11]
0
The interlock (safety) system is open
1
The interlock (safety) system is closed
21 Safety_interlock_virtual
Status of the virtual interlock (safety) system [86]
0
The interlock (safety) system is open
1
The interlock (safety) system is closed
28 Model
Type designation of unit
29 Unit_name
Unit name [90], can be selected by the customer, if required
30 Serial_number
Serial_number
31 Date_of_manufacturing
Date_of_manufacturing
32 Controller_series
Type of control
33 Software_version
Software version of control
34 Humidity_set_value
Set value [3] of rel. humidity [2] in %
35 Humidity_actual_value
Actual value [1] of rel. humidity [2] in %
50 V_Signal
Voltage signal measured on terminal ST0505
Humidification
Remote_off
No_bus-signal
Cooling
Flush_humidification
Flush_cooling
Adjustment/value range
Factory setting (FS) Bold
Read value
Initialization
Safety_interlock_open
No_Demand
Diagnosis
Not_programmed
Update_in_progress
Restart
Fault
Read value
Flush_hygiene
Flush_dead_leg
Discharge
Flush_manually
Flushing_humidification_cooling
Service_message
Off
On
Read value
Off
On
Read value
see: 02-1 Fault_message_unit
Read value
see: 02-4 Service_message_unit
Read value
Read value
Read value
Read value
Read value
Read value
Read value
Read value
Read value
Read value
Read value
51 mA_Signal
Current signal measured on terminal ST0506
52
Ω
_Signal
Resistance signal measured on terminal ST0507
53 Digital_input
Actual state of the digital input [97]
0
No switching signal
1 Switching
signal
present
56 Pressure_acutal_value
The current system pressure in the unit in bar
Read value
Read value
Read value
Off
On
Read value