Installation
»
Install thermo sensor. Do not screw the nut in too
tightly!
»
Neatly connect the capillary tube to the heater element.
Having humidifiers with two or more heating elements
the capillary tube is connected to two heating elements.
»
To proceed further, follow the steps described above in
section “Cleaning Steam Cylinder”.
9.6 Unlocking of a Released Thermo Sensor
(for heater element)
If a thermo sensor (for heater element) has released due to a too
high temperature the blue button (P) is on the same level as the
top of its holder. Additional the control reports a failure „thermo
sensor activated“. After the system has cooled down the release
button (P) can be unlocked by pressing it down a few millime-
tres.
9.7 Unlocking of a Released Thermo Sensor
(for Solid State Relay)
If a thermo sensor (for solid state relay) has released due to a
too high temperature (>100°C +/- 5°K) the control reports a fail-
ure „thermo sensor activated“. After the system has cooled down
the release pin (that lays between the both plain connectors)
can be released by pressing it carefully down until there is a klick
sound.
Release but-
ton
Release
button