Page 45
9.2 Access to Control Unit
»
Remove cover (or electric compartment cover) and lift
display panel (A) out of its guide.
»
Turn display panel (see drawing) and hang display
panel on the humidifier cabinet (B) by placing the two
guide pins in the two front guides.
»
The PCB (C) is now accessible.
Danger, Hazardous Voltage:
Switch off unit before installing or
removing the display plate.
9.3 Cleaning Steam Cylinder
Removal
»
Close off water supply.
»
Drain steam cylinder (9) by setting main switch to Pos
II.
»
Disconnect power supply and secure against restart
(switch off control switch, remove main fuse and control
fuse F1).
»
Verify absence of electric current.
»
Remove connector plug for steam cylinder lead.
»
Remove power supply cables from the temperature cut-
outs.
»
Disconnect connection hoses to water level control.
»
Remove clip (2) between adapter and cabinet.
»
Push steam hose adapter upwards. (Steam hoses shor-
ter than 0,5 m should be remove before.)
»
»
Note:
Push clip on to steam hose adapter on top of
cabinet to prevent adapter from sliding back.