HeaterLine:
Lenght of Steam Manifold [mm]*
* For units HL 6 - 12 and DL6-12 HygroMatik delivers one adapter DN40 / 25.
** For units HL 30 - 45 HygroMatik delivers one t-connector for separating the steam on
two steam manifold.
*** Special lenght on request.
****Hl 60.-90 are double units and consist of Hl 30-45 units.
Note:
At lengths of 900mm or more, steam manifolds are
shipped with an extra alternative mounting fixture (Nut, M8) on
the closed end.
5.4.1 Notes on Installation
Placement of the steam manifold on the supply side of the air
duct is preferred.
•
Maximum allowable pressure in the air duct is 1200 Pa
•
On the return side, the maximum allowable negative air
pressure is 500 Pa
With high-pressure air-conditioning systems, the unit's drain or
supply hose must be lengthened depending on the overall pres-
sure. When this is the case please consult HygroMatik.
When installing the steam manifold, please note the following:
•
The air intake can be positioned on the right or the left.
•
Observe a minimum distance of 120 mm from the top of
the air duct.
•
Depending on the design of the air duct, additional
mounting of the steam manifold may be required.
Shown installation and position dimensions are based
on experimental values. Special environmental conditi-
ons could require adjustments.
Type
Steam
Manifold
Steam Hose Condensate
Hose
HL 6-12 *
1x25
DN25
DN12
HL 18-24
1x40
DN40
DN12
HL 30-45 **
2x40
1xDN40
1xDN12
HL 60-90 ****
2x(2x40)
2x(1xDN40) 2x(1xDN12)
l
220
400
600
900
1200
1450
DN25
x
x
x
x
x
x
DN40
x
x
x
x
x
x
Содержание DemiLine 12
Страница 1: ...DemiLine Electric Heater Steam Humidifier For Fully Demineralized Water Manual...
Страница 29: ...Page 29 5 7 2 Drill Pattern DN40 not to scale Note Due to variable print media the dimensions are not to scale...
Страница 54: ...Page 54 10 EC Declaration of Conformity...
Страница 59: ......
Страница 60: ...Page 60 14 Exploded View...
Страница 61: ...Page 61 15 View of Cabinet...