Page 34
6.2 Water Supply
»
Install a shut-off valve (AV) in the supply hose
»
Install a water filter (WF) if the water quality requires it
»
Make sure that a backflow preventer is installed in the
water supply line.
Note:
Shut-off valve (AV), water filter (WF) and backflow preven-
ter are not provided by HygroMatik.
Install as follows:
»
Check whether the valve strainer has been inserted in
the solenoid valve.
»
Screw cap nut (Q) onto the supply connection. Tighten
by hand.
The supply connection protrudes from the intermediate tray.
Note:
Excessive tightening will damage the threads.
»
Slide 13mm inner diameter hose (SCH) over the pres-
sure clip (R) and secure with a hose clamp.
water supply (with
backflow preventer)
1-10 bar