Page 52
9.9 Removing Inlet Solenoid Valve and Clean-
ing Fine Mesh Filter
Removal
»
Close off water supply.
»
Drain steam cylinder by setting main switch to Pos II.
»
Disconnect power supply and secure against restart
(switch off control switch, remove main fuse and control
fuse F1).
»
Verify absence of electric current.
»
Remove cylinder as described above in section “Clean-
ing Steam Cylinder.”
»
Seal off water supply and remove screw joint from fresh
water connection.
»
Detach connector hose from base.
»
Remove electrical connectors from solenoid.
»
Remove solenoid valve mounting screws.
»
Take the solenoid valve out of hole.
Cleaning
»
Remove fine mesh filter from the solenoid valve and
clean.
Installation
»
Place solenoid valve with seal in the hole in the unit
cabinet.
»
Secure solenoid valve tightly with screws .
»
Attach fresh water connection.
»
Connect elecrical cable to the solenoid valve.
»
Attach connector hose to the base by using clamps .
»
Install cylinder as described above in section “Cleaning
Steam Cylinder”.
»
Open water supply.
»
Switch on unit and check for leakage after 15-30 min-
utes of operation.
If leakage occurs, switch off power supply and repair the leaks,
following safety instructions for work on live components!
Содержание DemiLine 12
Страница 1: ...DemiLine Electric Heater Steam Humidifier For Fully Demineralized Water Manual...
Страница 29: ...Page 29 5 7 2 Drill Pattern DN40 not to scale Note Due to variable print media the dimensions are not to scale...
Страница 54: ...Page 54 10 EC Declaration of Conformity...
Страница 59: ......
Страница 60: ...Page 60 14 Exploded View...
Страница 61: ...Page 61 15 View of Cabinet...