Install main power supply as follows:
We recommend using a main fuse with a quick or medium blow
rating (applies only to the mains voltages above.) See table
below indicating maximum power consumption corresponding to
each type of circuit protection:
7.2 Control Connection
Warning:
Set the control to prevent overly frequent activation
and deactivation of the steam humidifier. Main contactors are
wearing parts and are guaranteed by the manufacturer for
150,000 cycles. Operation which minimizes activation cycles will
extend the life of the main contactors.
Type
Main Power Supply
HL6-45
400V/3Phases/N
DL6-26
400V/3Phases/N
Type
Power Con-
sumption
Fuses
HL6
11,3
3x16 A
HL9
16,9
3x20 A
HL12
19,5
3x25 A
HL 8
29,3
3x35 A
HL24
39,0
3x50 A
HL30
39,0
3x50 A
HL36
58,5
3x63 A
HL45
58,5
3x63 A
HL60
2 x 39,0
2 x (3x63) A
HL70
2 x 58,5
2 x (3x63) A
HL80
2 x 58,5
2 x (3x63) A
HL90
2 x 58,5
2 x (3x63) A
Type
Power Con-
sumption
Fuses
DL6
11,3
3x16 A
DL9
16,9
3x20 A
DL12
19,5
3x25 A
DL18
29,3
3x35 A
DL27
29,3
3x35 A