4.7 Failure records
Record
Possible reason
Action
Inclination failure
The inclination determined at
calibration was <20%.
- Check connections and flow and repeat
calibration
- Clean/replace electrode of probe
- Monitoring 0 or 500 mV:
check mains voltage
Contact our service staff!
Failure input 1
(electrode)
Signal failure at input 1
- Control cable and connection of
electrode
- Measuring range exceeded
Contact our service staff!
Failure input 2
(temperature
sensor)
Signal failure at input 2
- Check temperature sensor and cable
Failure record is even shown if no or a not
suited temperature sensor is connected.
Limit value 1 / 2
Limit value 1 exceeded
or:
Limit value 2 not reached
- Check dosing
Contact our service staff!
Dosing control 1 / 2
Controller 1 (or 2) is dosing too
long with 100 %
- Check dosing and dosing line
Caution!
A damaged dosing line may result in
chemical emission!
Contact our service staff!
Cleaning process
running
The automatic sensor cleaning
will have started no more than 5
minutes ago
The info is cleared automatically after
max. 5 minutes after start of cleaning.
Calibration of chlorine dioxide measuring
is not possible whilst that record is shown!
Содержание HydroDOS HD550G
Страница 19: ...I 19 103 Last change 04 2016 E P AL TW PW Subject to technical modifications 2 2 Installation schematics...
Страница 39: ...I 39 103 Last change 04 2016 E P AL TW PW Subject to technical modifications...
Страница 43: ...I 43 103 Last change 04 2016 E P AL TW PW Subject to technical modifications Calibration...
Страница 98: ...I 98 103 Last change 04 2016 E P AL TW PW Subject to technical modifications Technical documents...
Страница 102: ...I 102 103 Last change 04 2016 E P AL TW PW Subject to technical modifications 4 Installation drawing...