9. Putting dosing pump out of operation.
This must only be carried out if the pump must be dismounted or replaced.
Caution!
- Chemicals must always be stored carefully in separate tubs!
- Protective clothing must be worn when working at the dosing
head, the connections or connection lines (protective glasses
and protective gloves)!
➢
Switch-off plant and pump from plant control and isolate from mains.
➢
The pressure must be allowed to escape via the ventilation hose.
➢
Appropriate measures must be taken to collect returning material.
➢
All connections must be removed from the pump and the pipeline removed carefully.
➢
The dosing pump must be dismounted from the assembly plate.
All parts that had been in contact with the conveying material must be washed very carefully
- Pipelines
- Valves
- Dosing head
- Membrane
All chemical traces at the pump casing must be removed prior to dispatch, repair of disposal of dosing
pump