Installation and Maintenance Manual
31
Options for User Programmable Output Relays 1-3
The Smart Touch Controller can be set to interface to many types of external devices through the use of its
programmable output relays. All of the output functions listed below are accessible in the Installer Menu
under the selection [r1 __], [r2 __] and [r3 __]. Select which relay you wish to use and enter the appropriate
function by the numbers as listed below.
1.
Close Limit output:
This output can also be used to create an interlock signal to another operators interlock
input, or simply to indicate that the gate is secure. The relay is released at full closure.
2.
Close limit pulse output:
This output may be used in a sequenced system to command a 2
nd
machine to
close. Generates a brief pulsed output that occurs when the close limit is triggered.
3.
Open limit output:
This output is used to indicate a full open position indication. This output becomes active
when to open limit is triggered and releases when the open limit is released.
4.
Open limit pulse output:
This output may be used to trip a sequenced barrier arm gate operator to open.
Generates a brief pulsed output occurs when the open limit is triggered. An additional pulse is also generated
with any new open command even when the gate is already fully open.
5.
Warn before/during operate output:
This output may be used to control an external warning device. This
output will operate at the same time as the internal warn before operate buzzer.
6.
Gate Lock output:
This output may be used to control external solenoid locks or magnetic locks. In both
directions of travel, this output will be activated about 7/10
th
of a second before the operator starts moving the
gate, and remains active while moving and for a few seconds after stopping.
7.
Gate forced open output:
Alarms if the gate is forced off the closed limit switch, and operator is not able to
restore the gate to full closed within four seconds. This alarm resets itself in 30 seconds.
8.
Gate open too long output:
Activates when the gate has been open longer than a user-selected period of
time. Adjustable from 0 delay, then 15 seconds delay to 135 seconds delay in 30-second time increments.
9.
Safety Mode Alert output:
Activated when system is in the Safety Mode or the Entrapment Mode. Safety
Mode occurs upon an impact with an obstruction. Entrapment Mode means the gate is stopped and occurs if
the internal inherent sensor triggers while the system is in the Safety Mode.
10.
Entrapment Mode Alert output:
Activated only when system is in the Entrapment Mode.
11.
Unauthorized Vehicle Entry output:
Activated when a 2
nd
vehicle enters from the outside, without a valid
input from an access control device. This output releases when an access control input signals open or the
gate reaches the close limit position.
12.
Outside Obstruction Vehicle Detector output:
This output may be used to interlock to an entry device to
prevent pedestrian use. This output is active whenever the OOLD is tripped.
13.
Special output from “OOLD” only when gate is closed:
Used to annunciate a vehicle or to indicate loitering.
Adjustable from 0 delay, then 15 to 135 seconds delay in 30-second time intervals.
14.
Gate nearing full travel output:
For operators with RPM sensors only. This output is activated when the gate
is three feet from full travel in both the open and close directions. This output can be used to reduce the
sensitivity of a proximity sensor near the ends of gate travel.
15.
Gate Failure output
: This output is activated to report that a problem has occurred. Indicates that system in
an Error Mode, Fault Mode or Entrapment Mode. If active, the gate is disabled.
16.
Motor Running output:
This output is active when the motor is running and the gate is in motion.
17.
AC Power Failure output:
This relay is normally energized, but drops with loss of AC power. This output is
also active on DC machines when the battery charger is off.
18.
DC Power Failure output:
This output is activated when the battery power is very low, but the output ceases
when the battery is dead. The relay is triggered when the battery is less than 20 Volts.
19.
Flasher Relay:
This output is intended to control flashing lights that pulse once per second. The relay is
activated all the time, except when the open limit switch is triggered.
Содержание HRG 220 ST
Страница 15: ...Installation and Maintenance Manual 9 Swing Gate Post Details ...
Страница 16: ...Installation and Maintenance Manual 10 HRG 220 Pump Pack ...
Страница 17: ...Installation and Maintenance Manual 11 HRG 222 Pump Pack ...
Страница 18: ...Installation and Maintenance Manual 12 How Our Hydraulic Swing Gates Work ...
Страница 25: ...Installation and Maintenance Manual 19 Instructions for Hand Pump or Manual Operation ...
Страница 29: ...Installation and Maintenance Manual 23 ...
Страница 47: ...Installation and Maintenance Manual 41 ...
Страница 48: ...Installation and Maintenance Manual 42 ...
Страница 62: ...Installation and Maintenance Manual 56 Battery Connection Diagram ...
Страница 63: ...Installation and Maintenance Manual 57 Battery Connection Diagram ...
Страница 65: ...Installation and Maintenance Manual 59 Wire Size Schedules ...
Страница 66: ...Installation and Maintenance Manual 60 Parts Breakout HRG 220 Pump Packs ...
Страница 67: ...Installation and Maintenance Manual 61 Parts Breakout HRG 222 Pump Packs ...
Страница 68: ...Installation and Maintenance Manual 62 Parts Breakout Control Box ...
Страница 69: ...Installation and Maintenance Manual 63 Parts Breakout Post ...
Страница 70: ...Installation and Maintenance Manual 64 Parts Breakout DC Power Supply ...